-- ************************************************************************* -- AMERICAN POWER CONVERSION PowerNet-MIB -- ************************************************************************* -- Copyright (c) 2004 American Power Conversion, Inc. -- PowerNet is a Trademark of American Power Conversion Corp. -- -- Title: APC TOP LEVEL PowerNet MIB -- -- Version : 3.6.8 -- -- Generated by script: tomib.awk -- -- Input File: powernetPS.mib -- -- Created: Monday, November, 22, 2004 -- -- Revision History: -- ************************************************************************* -- - v3.2.0 Added functionality for MasterSwitch Plus -- - v3.3.0 Added functionality for MX28B (dcDM3) and 3-phase UPS -- - v3.3.2 New traps for Symmetra PX UPS -- 07/15/01 - v3.4.0 Added transfer switch -- - v3.4.3 Added functionality for External and Integrated Environmental Monitor -- 06/14/02 - v3.4.4 Added dcmim2(Siemens) branch, Battery Manager(Reading) traps, and -- Psx Traps for PDU and RM-PDU and Netlock branch/traps -- 06/18/02 - v3.5.0a Sync Control Group support -- 08/06/02 - v3.5.0a Environmental Management System branch/traps -- 09/16/02 - v3.5.0b Fixed some odds/ends ... going to RM-PDU for MS additions -- 09/25/02 - v3.5.0c MS3 additions -- 11/05/02 - v3.5.0e More Environmental Management System/A-Link devices(ARU) -- 11/22/02 - v3.5.0g Added General APC device status OID -- 11/27/02 - v3.5.0h Wrapped up MS3 ((Controlled or Metered) Rack PDU) changes -- 12/26/02 - v3.5.1a Changed MS3 name again, Controlled to Switched Rack PDU -- 01/07/03 - v3.6.0a Added OIDs/Traps for UPS Switchable Outlet Groups. -- 01/09/03 - Adding the General APC device discovery OIDs (hidden) -- 01/28/03 - v3.6.0c Made some small trap pair fixes for Switched Rack PDU (MS3) -- 02/13/03 - v3.6.0d Mods from the review and some EMS fixes. -- Added OID for the new 20kVA Symmetra 3 Phase type. -- Added OIDs to upsAdvConfig for Symmetra type UPSs. -- Added upsDiagnostics branch OID for Symmetra module information. -- 04/05/03 - v3.6.2 Added OID for the new Smart-UPS 7500 and 10000 types. -- 06/04/03 - v3.6.3 Added OIDs/Traps for AirFM. -- 06/24/03 - v3.6.4 Moved some AirFM temps and humidities from system level to module level. -- 10/24/03 - v3.6.4a Added OIDs/Traps for xPDU. -- 10/27/03 - v3.6.4f Added AirPA OIDs. -- 11/03/03 - v3.6.4g Merge of 3.6.4e and 3.6.4f -- 11/07/03 - v3.6.4h Additional review corrections -- 12/01/03 - v3.6.5a Added group OIDs for Air FM. Added C & F OIDs for Air PA setpoint. -- 12/19/03 - v3.6.5b Review corrections. -- 02/23/04 - v3.6.5c Added Modbus to experimental and multiple CB(bank) rPDU support -- 05/05/04 - v3.6.6 Adding EMS status OID and trap for H/W issues, redefined duplicate -- trap #228 (to ARU Device config change) and minor clean-up -- 05/12/04 - v3.6.7a Added Air FM alarm status OIDs. -- 06/03/04 - v3.6.7b Added UPS Config for Simple Signal Shutdowns and Number of External -- batteries. Added Mute option to the UPS Config Audible Alarm. -- 07/12/04 - v3.6.7d Removed Air FM alarm status OIDs due to delay in release. -- 07/14/04 - v3.6.7d Added a detailed description to the UPSAdvConfigAlarm OID -- 07/14/04 - v3.6.7e Added Custom Event traps -- 08/04/04 - v3.6.7 Tag for final builds, see v3.6.7 beta build notes for changes -- 08/26/04 - v3.6.8a Added new traps for UPS internal over temperature fault and cleared. -- 09/01/04 - v3.6.8b Adding new thresholds for EMS probe config & status -- 09/08/04 - v3.6.8c Corrections from MIB review. -- 09/30/04 - v3.6.8d Added new traps for AIS ^F Message events. -- 10/21/04 - v3.6.8e EMS. Added missing traps and new Rate functionality. -- 10/22/04 - v3.6.8f Added resetNetworkLeaveModeAndRestart option to the mcontrolRestartAgent OID. -- 10/28/04 - v3.6.8g Updated EMS sections from mib committee review. -- 11/22/04 - v3.6.8 Tag for final build. -- ************************************************************************* -- ************************************************************************* -- PowerNet-MIB { iso org(3) dod(6) internet(1) private(4) -- enterprises(1) apc(318) } PowerNet-MIB DEFINITIONS ::= BEGIN IMPORTS enterprises, IpAddress, Gauge, TimeTicks FROM RFC1155-SMI DisplayString FROM RFC1213-MIB OBJECT-TYPE FROM RFC-1212 TRAP-TYPE FROM RFC-1215; apc OBJECT IDENTIFIER ::= { enterprises 318 } products OBJECT IDENTIFIER ::= { apc 1 } apcmgmt OBJECT IDENTIFIER ::= { apc 2 } hardware OBJECT IDENTIFIER ::= { products 1 } software OBJECT IDENTIFIER ::= { products 2 } system OBJECT IDENTIFIER ::= { products 3 } experimental OBJECT IDENTIFIER ::= { products 4 } mconfig OBJECT IDENTIFIER ::= { apcmgmt 1 } mcontrol OBJECT IDENTIFIER ::= { apcmgmt 2 } mtrapargs OBJECT IDENTIFIER ::= { apcmgmt 3 } mfiletransfer OBJECT IDENTIFIER ::= { apcmgmt 4 } mconfigClock OBJECT IDENTIFIER ::= { mconfig 6 } mfiletransferStatus OBJECT IDENTIFIER ::= { mfiletransfer 1 } mfiletransferConfig OBJECT IDENTIFIER ::= { mfiletransfer 2 } mfiletransferControl OBJECT IDENTIFIER ::= { mfiletransfer 3 } mfiletransferConfigSettings OBJECT IDENTIFIER ::= { mfiletransferConfig 1 } mfiletransferConfigTFTP OBJECT IDENTIFIER ::= { mfiletransferConfig 2 } mfiletransferConfigFTP OBJECT IDENTIFIER ::= { mfiletransferConfig 3 } ups OBJECT IDENTIFIER ::= { hardware 1 } measureUps OBJECT IDENTIFIER ::= { hardware 2 } miniSNMPadapter OBJECT IDENTIFIER ::= { hardware 3 } masterswitch OBJECT IDENTIFIER ::= { hardware 4 } masterswitchVM OBJECT IDENTIFIER ::= { hardware 5 } masterswitchMSP OBJECT IDENTIFIER ::= { hardware 6 } dcDM3 OBJECT IDENTIFIER ::= { hardware 7 } automaticTransferSwitch OBJECT IDENTIFIER ::= { hardware 8 } dc2 OBJECT IDENTIFIER ::= { hardware 9 } environmentalMonitor OBJECT IDENTIFIER ::= { hardware 10 } netlock OBJECT IDENTIFIER ::= { hardware 11 } rPDU OBJECT IDENTIFIER ::= { hardware 12 } airConditioners OBJECT IDENTIFIER ::= { hardware 13 } rARU OBJECT IDENTIFIER ::= { hardware 14 } xPDU OBJECT IDENTIFIER ::= { hardware 15 } powerNetSubAgent OBJECT IDENTIFIER ::= { software 1 } powerNetSoftwareSystem OBJECT IDENTIFIER ::= { powerNetSubAgent 1 } powerNetSoftwareConfig OBJECT IDENTIFIER ::= { powerNetSubAgent 2 } backUPS OBJECT IDENTIFIER ::= { system 1 } smartUPS OBJECT IDENTIFIER ::= { system 2 } matrixUPS OBJECT IDENTIFIER ::= { system 3 } masterSwitch OBJECT IDENTIFIER ::= { system 4 } symmetraUPS OBJECT IDENTIFIER ::= { system 5 } dp100E OBJECT IDENTIFIER ::= { system 6 } dp300E OBJECT IDENTIFIER ::= { system 7 } monitors OBJECT IDENTIFIER ::= { system 8 } redundantSwitch OBJECT IDENTIFIER ::= { system 9 } dcPower OBJECT IDENTIFIER ::= { system 10 } automaticXferSwitch OBJECT IDENTIFIER ::= { system 11 } netLock OBJECT IDENTIFIER ::= { system 12 } symmetra3PhaseUPS OBJECT IDENTIFIER ::= { system 13 } networkAir OBJECT IDENTIFIER ::= { system 14 } infraXurePDU OBJECT IDENTIFIER ::= { system 15 } ais5000UPS OBJECT IDENTIFIER ::= { system 16 } smartUPS3Phase OBJECT IDENTIFIER ::= { system 17 } xPDUIdent OBJECT IDENTIFIER ::= { xPDU 1 } xPDUDevice OBJECT IDENTIFIER ::= { xPDU 2 } xPDUACMonitoringPoint OBJECT IDENTIFIER ::= { xPDU 3 } xPDUCircuitBreakers OBJECT IDENTIFIER ::= { xPDU 4 } xPDUInputContacts OBJECT IDENTIFIER ::= { xPDU 5 } xPDUOutputRelays OBJECT IDENTIFIER ::= { xPDU 6 } xPDUMiscGroup OBJECT IDENTIFIER ::= { xPDU 7 } xPDUMainInput OBJECT IDENTIFIER ::= { xPDUACMonitoringPoint 1 } xPDUBypassInput OBJECT IDENTIFIER ::= { xPDUACMonitoringPoint 2 } xPDUUPSInput OBJECT IDENTIFIER ::= { xPDUACMonitoringPoint 3 } xPDUSystemOutput OBJECT IDENTIFIER ::= { xPDUACMonitoringPoint 4 } xPDUGroundMonitorPoint OBJECT IDENTIFIER ::= { xPDUACMonitoringPoint 5 } xPDUSystemBreakers OBJECT IDENTIFIER ::= { xPDUCircuitBreakers 1 } xPDUBranchBreakers OBJECT IDENTIFIER ::= { xPDUCircuitBreakers 2 } smartUPS250 OBJECT IDENTIFIER ::= { smartUPS 1 } smartUPS400 OBJECT IDENTIFIER ::= { smartUPS 2 } smartUPS600 OBJECT IDENTIFIER ::= { smartUPS 3 } smartUPS900 OBJECT IDENTIFIER ::= { smartUPS 4 } smartUPS1250 OBJECT IDENTIFIER ::= { smartUPS 5 } smartUPS2000 OBJECT IDENTIFIER ::= { smartUPS 6 } smartUPS450 OBJECT IDENTIFIER ::= { smartUPS 7 } smartUPS700 OBJECT IDENTIFIER ::= { smartUPS 8 } smartUPS1000 OBJECT IDENTIFIER ::= { smartUPS 9 } smartUPS1400 OBJECT IDENTIFIER ::= { smartUPS 10 } smartUPS2200 OBJECT IDENTIFIER ::= { smartUPS 11 } smartUPS3000 OBJECT IDENTIFIER ::= { smartUPS 12 } smartUPS5000 OBJECT IDENTIFIER ::= { smartUPS 13 } smartUPS7500 OBJECT IDENTIFIER ::= { smartUPS 14 } smartUPS10000 OBJECT IDENTIFIER ::= { smartUPS 15 } smartUPS1500 OBJECT IDENTIFIER ::= { smartUPS 16 } matrixUPS3000 OBJECT IDENTIFIER ::= { matrixUPS 1 } matrixUPS5000 OBJECT IDENTIFIER ::= { matrixUPS 2 } masterSwitchV1 OBJECT IDENTIFIER ::= { masterSwitch 1} masterSwitchV2 OBJECT IDENTIFIER ::= { masterSwitch 2} masterSwitchVM OBJECT IDENTIFIER ::= { masterSwitch 3} masterSwitchMSP OBJECT IDENTIFIER ::= { masterSwitch 4} masterSwitchrPDU OBJECT IDENTIFIER ::= { masterSwitch 5} symmetraUPS4kVA OBJECT IDENTIFIER ::= { symmetraUPS 1 } symmetraUPS8kVA OBJECT IDENTIFIER ::= { symmetraUPS 2 } symmetraUPS12kVA OBJECT IDENTIFIER ::= { symmetraUPS 3 } symmetraUPS16kVA OBJECT IDENTIFIER ::= { symmetraUPS 4 } environmental OBJECT IDENTIFIER ::= { monitors 1 } environmentalMgtSystem OBJECT IDENTIFIER ::= { monitors 2 } emu2 OBJECT IDENTIFIER ::= { monitors 3 } dm3 OBJECT IDENTIFIER ::= { dcPower 1 } dcmim2 OBJECT IDENTIFIER ::= { dcPower 2 } symmetra3PhaseUPS40kVA OBJECT IDENTIFIER ::= { symmetra3PhaseUPS 1 } symmetra3PhaseUPS60kVA OBJECT IDENTIFIER ::= { symmetra3PhaseUPS 2 } symmetra3PhaseUPS80kVA OBJECT IDENTIFIER ::= { symmetra3PhaseUPS 3 } symmetra3PhaseUPS20kVA OBJECT IDENTIFIER ::= { symmetra3PhaseUPS 4 } airFMSeries OBJECT IDENTIFIER ::= { networkAir 1 } rackAirRemovalUnit OBJECT IDENTIFIER ::= { networkAir 2 } airPASeries OBJECT IDENTIFIER ::= { networkAir 3 } ais5000UPS10kVA OBJECT IDENTIFIER ::= { ais5000UPS 1 } ais5000UPS20kVA OBJECT IDENTIFIER ::= { ais5000UPS 2 } ais5000UPS30kVA OBJECT IDENTIFIER ::= { ais5000UPS 3 } ais5000UPS40kVA OBJECT IDENTIFIER ::= { ais5000UPS 4 } ais5000UPS60kVA OBJECT IDENTIFIER ::= { ais5000UPS 5 } ais5000UPS80kVA OBJECT IDENTIFIER ::= { ais5000UPS 6 } ais5000UPS100kVA OBJECT IDENTIFIER ::= { ais5000UPS 7 } smartUPS3Phase10kVA OBJECT IDENTIFIER ::= { smartUPS3Phase 1 } smartUPS3Phase15kVA OBJECT IDENTIFIER ::= { smartUPS3Phase 2 } smartUPS3Phase20kVA OBJECT IDENTIFIER ::= { smartUPS3Phase 3 } smartUPS3Phase30kVA OBJECT IDENTIFIER ::= { smartUPS3Phase 4 } smartUPS3Phase40kVA OBJECT IDENTIFIER ::= { smartUPS3Phase 5 } upsIdent OBJECT IDENTIFIER ::= { ups 1 } upsBattery OBJECT IDENTIFIER ::= { ups 2 } upsInput OBJECT IDENTIFIER ::= { ups 3 } upsOutput OBJECT IDENTIFIER ::= { ups 4 } upsConfig OBJECT IDENTIFIER ::= { ups 5 } upsControl OBJECT IDENTIFIER ::= { ups 6 } upsTest OBJECT IDENTIFIER ::= { ups 7 } upsComm OBJECT IDENTIFIER ::= { ups 8 } upsPhase OBJECT IDENTIFIER ::= { ups 9 } upsSyncCtrlGroup OBJECT IDENTIFIER ::= { ups 10 } upsState OBJECT IDENTIFIER ::= { ups 11 } upsOutletGroups OBJECT IDENTIFIER ::= { ups 12 } upsDiagnostics OBJECT IDENTIFIER ::= { ups 13 } upsBasicIdent OBJECT IDENTIFIER ::= { upsIdent 1 } upsAdvIdent OBJECT IDENTIFIER ::= { upsIdent 2 } upsBasicBattery OBJECT IDENTIFIER ::= { upsBattery 1 } upsAdvBattery OBJECT IDENTIFIER ::= { upsBattery 2 } upsBasicInput OBJECT IDENTIFIER ::= { upsInput 1 } upsAdvInput OBJECT IDENTIFIER ::= { upsInput 2 } upsBasicOutput OBJECT IDENTIFIER ::= { upsOutput 1 } upsAdvOutput OBJECT IDENTIFIER ::= { upsOutput 2 } upsBasicConfig OBJECT IDENTIFIER ::= { upsConfig 1 } upsAdvConfig OBJECT IDENTIFIER ::= { upsConfig 2 } upsBasicControl OBJECT IDENTIFIER ::= { upsControl 1 } upsAdvControl OBJECT IDENTIFIER ::= { upsControl 2 } upsBasicTest OBJECT IDENTIFIER ::= { upsTest 1 } upsAdvTest OBJECT IDENTIFIER ::= { upsTest 2 } upsPhaseResetValues OBJECT IDENTIFIER ::= { upsPhase 1 } upsPhaseInput OBJECT IDENTIFIER ::= { upsPhase 2 } upsPhaseOutput OBJECT IDENTIFIER ::= { upsPhase 3 } upsSyncCtrlGroupConfig OBJECT IDENTIFIER ::= { upsSyncCtrlGroup 1 } upsSyncCtrlGroupStatus OBJECT IDENTIFIER ::= { upsSyncCtrlGroup 2 } upsBasicState OBJECT IDENTIFIER ::= { upsState 1 } upsAdvState OBJECT IDENTIFIER ::= { upsState 2 } upsOutletGroupStatus OBJECT IDENTIFIER ::= { upsOutletGroups 1 } upsOutletGroupConfig OBJECT IDENTIFIER ::= { upsOutletGroups 2 } upsOutletGroupControl OBJECT IDENTIFIER ::= { upsOutletGroups 3 } upsDiagnosticIM OBJECT IDENTIFIER ::= { upsDiagnostics 1 } upsDiagnosticPowerModules OBJECT IDENTIFIER ::= { upsDiagnostics 2 } upsDiagnosticBatteries OBJECT IDENTIFIER ::= { upsDiagnostics 3 } upsDiagnosticSubsystem OBJECT IDENTIFIER ::= { upsDiagnostics 4 } upsDiagnosticExternalDevices OBJECT IDENTIFIER ::= { upsDiagnostics 5 } upsDiagnosticComBus OBJECT IDENTIFIER ::= { upsDiagnostics 6 } upsDiagSwitchGear OBJECT IDENTIFIER ::= { upsDiagnosticExternalDevices 1 } upsDiagMCCBBox OBJECT IDENTIFIER ::= { upsDiagnosticExternalDevices 2 } upsDiagTransformer OBJECT IDENTIFIER ::= { upsDiagnosticExternalDevices 3 } mUpsEnviron OBJECT IDENTIFIER ::= { measureUps 1 } mUpsContact OBJECT IDENTIFIER ::= { measureUps 2 } serialPort OBJECT IDENTIFIER ::= { miniSNMPadapter 1} serialPort1 OBJECT IDENTIFIER ::= { serialPort 1} serialPort2 OBJECT IDENTIFIER ::= { serialPort 2} serialPort2Config OBJECT IDENTIFIER ::= { serialPort2 1} serialPort2Control OBJECT IDENTIFIER ::= { serialPort2 2} sPDUIdent OBJECT IDENTIFIER ::= { masterswitch 1 } sPDUMasterControl OBJECT IDENTIFIER ::= { masterswitch 2 } sPDUMasterConfig OBJECT IDENTIFIER ::= { masterswitch 3 } sPDUOutletControl OBJECT IDENTIFIER ::= { masterswitch 4 } sPDUOutletConfig OBJECT IDENTIFIER ::= { masterswitch 5 } sPDUIdentVM OBJECT IDENTIFIER ::= { masterswitchVM 1 } sPDUMasterControlVM OBJECT IDENTIFIER ::= { masterswitchVM 2 } sPDUMasterConfigVM OBJECT IDENTIFIER ::= { masterswitchVM 3 } sPDUMasterStatusVM OBJECT IDENTIFIER ::= { masterswitchVM 4 } sPDUOutletControlVM OBJECT IDENTIFIER ::= { masterswitchVM 5 } sPDUOutletConfigVM OBJECT IDENTIFIER ::= { masterswitchVM 6 } sPDUOutletStatusVM OBJECT IDENTIFIER ::= { masterswitchVM 7 } sPDUIdentMSP OBJECT IDENTIFIER ::= { masterswitchMSP 1 } sPDUMasterControlMSP OBJECT IDENTIFIER ::= { masterswitchMSP 2 } sPDUMasterConfigMSP OBJECT IDENTIFIER ::= { masterswitchMSP 3 } sPDUMasterStatusMSP OBJECT IDENTIFIER ::= { masterswitchMSP 4 } sPDUOutletControlMSP OBJECT IDENTIFIER ::= { masterswitchMSP 5 } sPDUOutletConfigMSP OBJECT IDENTIFIER ::= { masterswitchMSP 6 } sPDUOutletStatusMSP OBJECT IDENTIFIER ::= { masterswitchMSP 7 } sPDUOutletConfigMSPall OBJECT IDENTIFIER ::= { sPDUOutletConfigMSP 1 } sPDUOutletConfigMSPgs OBJECT IDENTIFIER ::= { sPDUOutletConfigMSP 2 } sPDUOutletConfigMSPannun OBJECT IDENTIFIER ::= { sPDUOutletConfigMSP 3 } sPDUOutletConfigMSPmups OBJECT IDENTIFIER ::= { sPDUOutletConfigMSP 4 } rPDUIdent OBJECT IDENTIFIER ::= { rPDU 1 } rPDULoad OBJECT IDENTIFIER ::= { rPDU 2 } rPDUOutlet OBJECT IDENTIFIER ::= { rPDU 3 } rPDUPowerSupply OBJECT IDENTIFIER ::= { rPDU 4 } rPDULoadDevice OBJECT IDENTIFIER ::= { rPDULoad 1 } rPDULoadPhaseConfig OBJECT IDENTIFIER ::= { rPDULoad 2 } rPDULoadStatus OBJECT IDENTIFIER ::= { rPDULoad 3 } rPDULoadBankConfig OBJECT IDENTIFIER ::= { rPDULoad 4 } rPDUOutletDevice OBJECT IDENTIFIER ::= { rPDUOutlet 1 } rPDUOutletPhase OBJECT IDENTIFIER ::= { rPDUOutlet 2 } rPDUOutletControl OBJECT IDENTIFIER ::= { rPDUOutlet 3 } rPDUOutletConfig OBJECT IDENTIFIER ::= { rPDUOutlet 4 } rPDUOutletStatus OBJECT IDENTIFIER ::= { rPDUOutlet 5 } rPDUOutletBank OBJECT IDENTIFIER ::= { rPDUOutlet 6 } rPDUPowerSupplyDevice OBJECT IDENTIFIER ::= { rPDUPowerSupply 1 } dm3Ident OBJECT IDENTIFIER ::= { dcDM3 1 } dm3Config OBJECT IDENTIFIER ::= { dcDM3 2 } dm3Status OBJECT IDENTIFIER ::= { dcDM3 3 } dm3IdentSystem OBJECT IDENTIFIER ::= { dm3Ident 1} dm3ConfigSystem OBJECT IDENTIFIER ::= { dm3Config 1 } dm3ConfigLVD OBJECT IDENTIFIER ::= { dm3Config 2 } dm3ConfigBattery OBJECT IDENTIFIER ::= { dm3Config 3 } dm3ConfigPowerModules OBJECT IDENTIFIER ::= { dm3Config 4 } dm3ConfigRelays OBJECT IDENTIFIER ::= { dm3Config 5 } dm3ConfigDistribution OBJECT IDENTIFIER ::= { dm3Config 6 } dm3ConfigRectifier OBJECT IDENTIFIER ::= { dm3ConfigPowerModules 1 } dm3ConfigConverter OBJECT IDENTIFIER ::= { dm3ConfigPowerModules 2 } dm3ConfigRectThresh OBJECT IDENTIFIER ::= { dm3ConfigRectifier 1 } dm3ConfigRectAlarms OBJECT IDENTIFIER ::= { dm3ConfigRectifier 2 } dm3ConfigConvThresh OBJECT IDENTIFIER ::= { dm3ConfigConverter 1 } dm3ConfigConvAlarms OBJECT IDENTIFIER ::= { dm3ConfigConverter 2 } dm3ConfigOutputRelays OBJECT IDENTIFIER ::= { dm3ConfigRelays 1 } dm3ConfigInputRelays OBJECT IDENTIFIER ::= { dm3ConfigRelays 2 } dm3ConfigBreakers OBJECT IDENTIFIER ::= { dm3ConfigDistribution 1 } dm3ConfigFuses OBJECT IDENTIFIER ::= { dm3ConfigDistribution 2 } dm3StatusSystem OBJECT IDENTIFIER ::= { dm3Status 1 } dm3StatusAlarms OBJECT IDENTIFIER ::= { dm3Status 2 } dm3StatusBattery OBJECT IDENTIFIER ::= { dm3Status 3 } dm3StatusOEM OBJECT IDENTIFIER ::= { dm3Status 4 } dm3StatusLVD OBJECT IDENTIFIER ::= { dm3Status 5 } dm3StatusPowerModules OBJECT IDENTIFIER ::= { dm3Status 6 } dm3StatusRelays OBJECT IDENTIFIER ::= { dm3Status 7 } dm3StatusDistribution OBJECT IDENTIFIER ::= { dm3Status 8 } dm3StatusRectifier OBJECT IDENTIFIER ::= { dm3StatusPowerModules 1 } dm3StatusConverter OBJECT IDENTIFIER ::= { dm3StatusPowerModules 2 } dm3StatusOutputRelays OBJECT IDENTIFIER ::= { dm3StatusRelays 1 } dm3StatusInputRelays OBJECT IDENTIFIER ::= { dm3StatusRelays 2 } dm3StatusBreakers OBJECT IDENTIFIER ::= { dm3StatusDistribution 1 } dm3StatusFuses OBJECT IDENTIFIER ::= { dm3StatusDistribution 2 } atsIdent OBJECT IDENTIFIER ::= { automaticTransferSwitch 1 } atsCalibration OBJECT IDENTIFIER ::= { automaticTransferSwitch 2 } atsControl OBJECT IDENTIFIER ::= { automaticTransferSwitch 3 } atsConfig OBJECT IDENTIFIER ::= { automaticTransferSwitch 4 } atsStatus OBJECT IDENTIFIER ::= { automaticTransferSwitch 5 } atsCalibrationInput OBJECT IDENTIFIER ::= { atsCalibration 1 } atsCalibrationPowerSupply OBJECT IDENTIFIER ::= { atsCalibration 2 } atsCalibrationOutput OBJECT IDENTIFIER ::= { atsCalibration 3 } atsStatusDeviceStatus OBJECT IDENTIFIER ::= { atsStatus 1 } atsStatusResetValues OBJECT IDENTIFIER ::= { atsStatus 2 } atsStatusInput OBJECT IDENTIFIER ::= { atsStatus 3 } atsStatusOutput OBJECT IDENTIFIER ::= { atsStatus 4 } dcmim2Ident OBJECT IDENTIFIER ::= { dc2 1 } dcmim2Control OBJECT IDENTIFIER ::= { dc2 2 } dcmim2Config OBJECT IDENTIFIER ::= { dc2 3 } dcmim2Status OBJECT IDENTIFIER ::= { dc2 4 } dcmim2IdentSystem OBJECT IDENTIFIER ::= { dcmim2Ident 1 } dcmim2ControlSystem OBJECT IDENTIFIER ::= { dcmim2Control 1 } dcmim2ConfigSystem OBJECT IDENTIFIER ::= { dcmim2Config 1 } dcmim2ConfigBattery OBJECT IDENTIFIER ::= { dcmim2Config 2 } dcmim2ConfigLVD OBJECT IDENTIFIER ::= { dcmim2Config 3 } dcmim2StatusSystem OBJECT IDENTIFIER ::= { dcmim2Status 1 } dcmim2StatusRectifier OBJECT IDENTIFIER ::= { dcmim2Status 2 } dcmim2StatusBattery OBJECT IDENTIFIER ::= { dcmim2Status 3 } dcmim2StatusLVD OBJECT IDENTIFIER ::= { dcmim2Status 4 } dcmim2StatusAlarms OBJECT IDENTIFIER ::= { dcmim2Status 5 } external OBJECT IDENTIFIER ::= { environmentalMonitor 1 } integrated OBJECT IDENTIFIER ::= { environmentalMonitor 2 } envMgtSystem OBJECT IDENTIFIER ::= { environmentalMonitor 3 } emIdent OBJECT IDENTIFIER ::= { external 1 } emConfig OBJECT IDENTIFIER ::= { external 2 } emStatus OBJECT IDENTIFIER ::= { external 3 } iemIdent OBJECT IDENTIFIER ::= { integrated 1 } iemConfig OBJECT IDENTIFIER ::= { integrated 2 } iemStatus OBJECT IDENTIFIER ::= { integrated 3 } emsIdent OBJECT IDENTIFIER ::= { envMgtSystem 1 } emsOutputRelayControl OBJECT IDENTIFIER ::= { envMgtSystem 2 } emsOutletControl OBJECT IDENTIFIER ::= { envMgtSystem 3 } emsSensorControl OBJECT IDENTIFIER ::= { envMgtSystem 4 } emsAlarmDeviceControl OBJECT IDENTIFIER ::= { envMgtSystem 5 } emsConfig OBJECT IDENTIFIER ::= { envMgtSystem 6 } emsProbeConfig OBJECT IDENTIFIER ::= { envMgtSystem 7 } emsInputContactConfig OBJECT IDENTIFIER ::= { envMgtSystem 8 } emsOutputRelayConfig OBJECT IDENTIFIER ::= { envMgtSystem 9 } emsOutletConfig OBJECT IDENTIFIER ::= { envMgtSystem 10 } emsSensorConfig OBJECT IDENTIFIER ::= { envMgtSystem 11 } emsStatus OBJECT IDENTIFIER ::= { envMgtSystem 12 } emsProbeStatus OBJECT IDENTIFIER ::= { envMgtSystem 13 } emsInputContactStatus OBJECT IDENTIFIER ::= { envMgtSystem 14 } emsOutputRelayStatus OBJECT IDENTIFIER ::= { envMgtSystem 15 } emsOutletStatus OBJECT IDENTIFIER ::= { envMgtSystem 16 } emsAlarmDeviceStatus OBJECT IDENTIFIER ::= { envMgtSystem 17 } emsSensorStatus OBJECT IDENTIFIER ::= { envMgtSystem 18 } nlIdent OBJECT IDENTIFIER ::= { netlock 1 } nlStatus OBJECT IDENTIFIER ::= { netlock 2 } airFM OBJECT IDENTIFIER ::= { airConditioners 1 } airFMIdent OBJECT IDENTIFIER ::= { airFM 1 } airFMStatus OBJECT IDENTIFIER ::= { airFM 2 } airFMGroup OBJECT IDENTIFIER ::= { airFM 3 } airPA OBJECT IDENTIFIER ::= { airConditioners 2 } airPAIdent OBJECT IDENTIFIER ::= { airPA 1 } airPAStatus OBJECT IDENTIFIER ::= { airPA 2 } rARUIdent OBJECT IDENTIFIER ::= { rARU 1 } rARUConfig OBJECT IDENTIFIER ::= { rARU 2 } rARUStatus OBJECT IDENTIFIER ::= { rARU 3 } -- object types -- the products group -- the experimental group -- the apcmgmt group -- the mconfig group mconfigNumTrapReceivers OBJECT-TYPE SYNTAX INTEGER ACCESS read-only STATUS mandatory DESCRIPTION "The number of managers to send traps to." ::= { mconfig 1 } mconfigTrapReceiverTable OBJECT-TYPE SYNTAX SEQUENCE OF MconfigTrapReceiverEntry ACCESS not-accessible STATUS mandatory DESCRIPTION "A list of managers to send traps to. The number of entries is given by the value of mconfigNumTrapReceivers. Maximum number of Trap Receivers is four." ::= { mconfig 2 } mconfigTrapReceiverEntry OBJECT-TYPE SYNTAX MconfigTrapReceiverEntry ACCESS not-accessible STATUS mandatory DESCRIPTION "The managers to send traps to." INDEX { trapIndex} ::= { mconfigTrapReceiverTable 1 } MconfigTrapReceiverEntry ::= SEQUENCE { trapIndex INTEGER, receiverAddr IpAddress, communityString DisplayString, severity INTEGER, acceptThisReceiver INTEGER, receiveTrapType INTEGER } trapIndex OBJECT-TYPE SYNTAX INTEGER ACCESS read-only STATUS mandatory DESCRIPTION "The index to a trap receiver entry." ::= { mconfigTrapReceiverEntry 1 } receiverAddr OBJECT-TYPE SYNTAX IpAddress ACCESS read-write STATUS mandatory DESCRIPTION "The IP address of the manager to send a trap to." ::= { mconfigTrapReceiverEntry 2 } communityString OBJECT-TYPE SYNTAX DisplayString ACCESS read-write STATUS mandatory DESCRIPTION "The community name to use in the trap when sent to the manager." ::= { mconfigTrapReceiverEntry 3 } severity OBJECT-TYPE SYNTAX INTEGER { information(1), warning(2), severe(3) } ACCESS read-only STATUS obsolete DESCRIPTION "The severity threshold of traps to send to the manager. traps are labeled in severity as informational(1), warning(2), severe(3). Only traps of equal or greater severity than this value are sent to the manager." ::= { mconfigTrapReceiverEntry 4 } acceptThisReceiver OBJECT-TYPE SYNTAX INTEGER { yes (1), no (2) } ACCESS read-write STATUS mandatory DESCRIPTION "An entry will become active if yes, and will be deleted if no." ::= { mconfigTrapReceiverEntry 5 } receiveTrapType OBJECT-TYPE SYNTAX INTEGER { powernet (1), ietf (2), both (3) } ACCESS read-write STATUS mandatory DESCRIPTION "The node in this entry will receive traps defined in APC PowerNet MIB, if this OID is set to yes." ::= { mconfigTrapReceiverEntry 6 } mconfigBOOTPEnabled OBJECT-TYPE SYNTAX INTEGER { yes (1), no (2) } ACCESS read-only STATUS mandatory DESCRIPTION "The value of yes(1) indicates the PowerNet Adapter is configured to obtain its IP configuration parameters from a BOOTP server. The value of no(2) indicates adapter will assume IP configuration parameters values saved in adapter's eeprom, which was originally configured at local console." ::= { mconfig 3 } mconfigTFTPServerIP OBJECT-TYPE SYNTAX IpAddress ACCESS read-write STATUS mandatory DESCRIPTION "The IP address of TFTP server. If mconfigBOOTPEnabled is yes(1), then this IP address is provided by BOOTP server and not allowed to be modified; otherwise, this IP address can be modified. Before using TFTP to load new code image, the image file should be placed in proper directory of the specified TFTP server. This OID is only supported by AP9605, AP9205, and AP9603 PowerNet SNMP Adapters." ::= { mconfig 4 } newCodeAuthentViaTFTP OBJECT-TYPE SYNTAX INTEGER { unknown (1), validNewAgentCodeImage (2), sameAgentCodeImage (3), invalidAgentCodeImage (4) } ACCESS read-only STATUS mandatory DESCRIPTION "Once mcontrolRestartAgent is set to loadAndExecuteNewAgent (3), PowerNet adapter will start to load the remote image file, for authentication only, instead of saving the code into flash memory. Only if a validNewAgentCodeImage (1) is found will the agent reboot the PowerNet adapter and invoke the loader to load and save new code into the flash memory. Otherwise, the current agent code will continue to run. This OID shows the result of the above authentication process. validNewAgentCodeImage (1) means the code image on TFTP server is a valid APC agent code and is different version from the current agent. Once agent identifies this, loader will start to update flash memory with the new agent code. sameAgentCodeImage (2) means the code image on TFTP server is exactly the same as the currently running agent. Currently running agent will not invoke loader to load the same again. invalidAgentCodeImage (3) means the code image on TFTP server is NOT a valid APC agent code. Thus, current agent will not load it into the flash memory. The value of this OID will be associated with TRAP codeImageAuthentDone. This OID is only supported by AP9605, AP9205, and AP9603 PowerNet SNMP Adapters." ::= { mconfig 5 } mconfigClockDate OBJECT-TYPE SYNTAX DisplayString ACCESS read-write STATUS mandatory DESCRIPTION "The current date in the mm/dd/yyyy format. Example: 01/01/2000." ::= { mconfigClock 1 } mconfigClockTime OBJECT-TYPE SYNTAX DisplayString ACCESS read-write STATUS mandatory DESCRIPTION "The current time in the hh:mm:ss am/pm format. Example: 12:00:00 am." ::= { mconfigClock 2 } mcontrolRestartAgent OBJECT-TYPE SYNTAX INTEGER { restartCurrentAgent (1), continueCurrentAgent (2), loadAndExecuteNewAgent (3), restartWithoutAgent (4), resetNetworkAndRestart (5), resetNetworkLeaveModeAndRestart (6) } ACCESS read-write STATUS mandatory DESCRIPTION "Setting this OID to restartCurrentAgent (1) will restart the same SNMP agent code currently saved in flash memory. Setting this OID to loadAndExecuteNewAgent (3) will enable adapter to load a new agent code into the flash memory and start to execute this new agent code. Bootp/tftp is the default protocol. loadAndExecuteNewAgent is only supported by AP9605, AP9205, and AP9603 PowerNet SNMP Adapters. Setting this OID to restartWithoutAgent (4) will restart the system and not start the agent. The subsequent time the system restarts the agent will also automatically restart. Setting this OID to resetNetworkAndRestart (5) will set the Boot Mode, IP Address, Subnet Mask, and Default Gateway to defaults, expire any existing DHCP lease and then restart the system. Setting this OID to resetNetworkLeaveModeAndRestart (6) will leave the Boot Mode at the current setting, set the IP Address, Subnet Mask, and Default Gateway to defaults, expire any existing DHCP lease and then restart the system." ::= { mcontrol 1 } -- The mtrapargs group -- These OIDs allows APC traps to be sent with additional arguments -- which may not be defined in the APC MIB. mtrapargsInteger OBJECT-TYPE SYNTAX INTEGER ACCESS read-only STATUS mandatory DESCRIPTION "This OID allows APC traps to be sent with an integer argument that my not be defined in the APC MIB. A get of this OID will return 0." ::= { mtrapargs 1 } mtrapargsIpAddress OBJECT-TYPE SYNTAX IpAddress ACCESS read-only STATUS mandatory DESCRIPTION "This OID allows APC traps to be sent with an IP address argument that my not be defined in the APC MIB. A get of this OID will return 0.0.0.0." ::= { mtrapargs 2 } mtrapargsString OBJECT-TYPE SYNTAX DisplayString ACCESS read-only STATUS mandatory DESCRIPTION "This OID allows APC traps to be sent with an octet string argument that my not be defined in the APC MIB. A get of this OID will return a NULL string." ::= { mtrapargs 3 } mtrapargsGauge OBJECT-TYPE SYNTAX Gauge ACCESS read-only STATUS mandatory DESCRIPTION "This OID allows APC traps to be sent with a Gauge argument that my not be defined in the APC MIB. A get of this OID will return 0." ::= { mtrapargs 4 } mtrapargsTimeTicks OBJECT-TYPE SYNTAX TimeTicks ACCESS read-only STATUS mandatory DESCRIPTION "This OID allows APC traps to be sent with a TimeTicks argument that my not be defined in the APC MIB. A get of this OID will return 0." ::= { mtrapargs 5 } mtrapargsInteger02 OBJECT-TYPE SYNTAX INTEGER ACCESS read-only STATUS mandatory DESCRIPTION "This OID allows APC traps to be sent with an integer argument that my not be defined in the APC MIB. A get of this OID will return 0." ::= { mtrapargs 6 } mtrapargsInteger03 OBJECT-TYPE SYNTAX INTEGER ACCESS read-only STATUS mandatory DESCRIPTION "This OID allows APC traps to be sent with an integer argument that my not be defined in the APC MIB. A get of this OID will return 0." ::= { mtrapargs 7 } mtrapargsIpAddress02 OBJECT-TYPE SYNTAX IpAddress ACCESS read-only STATUS mandatory DESCRIPTION "This OID allows APC traps to be sent with an IP address argument that my not be defined in the APC MIB. A get of this OID will return 0.0.0.0." ::= { mtrapargs 8 } mtrapargsIpAddress03 OBJECT-TYPE SYNTAX IpAddress ACCESS read-only STATUS mandatory DESCRIPTION "This OID allows APC traps to be sent with an IP address argument that my not be defined in the APC MIB. A get of this OID will return 0.0.0.0." ::= { mtrapargs 9 } mtrapargsString02 OBJECT-TYPE SYNTAX DisplayString ACCESS read-only STATUS mandatory DESCRIPTION "This OID allows APC traps to be sent with an octet string argument that my not be defined in the APC MIB. A get of this OID will return a NULL string." ::= { mtrapargs 10 } mtrapargsString03 OBJECT-TYPE SYNTAX DisplayString ACCESS read-only STATUS mandatory DESCRIPTION "This OID allows APC traps to be sent with an octet string argument that my not be defined in the APC MIB. A get of this OID will return a NULL string." ::= { mtrapargs 11 } mtrapargsGauge02 OBJECT-TYPE SYNTAX Gauge ACCESS read-only STATUS mandatory DESCRIPTION "This OID allows APC traps to be sent with a Gauge argument that my not be defined in the APC MIB. A get of this OID will return 0." ::= { mtrapargs 12 } mtrapargsGauge03 OBJECT-TYPE SYNTAX Gauge ACCESS read-only STATUS mandatory DESCRIPTION "This OID allows APC traps to be sent with a Gauge argument that my not be defined in the APC MIB. A get of this OID will return 0." ::= { mtrapargs 13 } mtrapargsTimeTicks02 OBJECT-TYPE SYNTAX TimeTicks ACCESS read-only STATUS mandatory DESCRIPTION "This OID allows APC traps to be sent with a TimeTicks argument that my not be defined in the APC MIB. A get of this OID will return 0." ::= { mtrapargs 14 } mtrapargsTimeTicks03 OBJECT-TYPE SYNTAX TimeTicks ACCESS read-only STATUS mandatory DESCRIPTION "This OID allows APC traps to be sent with a TimeTicks argument that my not be defined in the APC MIB. A get of this OID will return 0." ::= { mtrapargs 15 } -- the mfiletransfer group -- the mfiletransferStatus group mfiletransferStatusLastTransferResult OBJECT-TYPE SYNTAX INTEGER { lastFileTransferResultSuccessful (1), lastFileTransferResultNotAvailable (2), lastFileTransferResultFailureUnknown (3), lastFileTransferResultFailureServerInaccessible (4), lastFileTransferResultFailureServerAccessDenied (5), lastFileTransferResultFailureFileNotFound (6), lastFileTransferResultFailureFileTypeUnknown (7), lastFileTransferResultFailureFileCorrupted (8) } ACCESS read-only STATUS mandatory DESCRIPTION "Once mfiletransferControlInitiateFileTransfer is set to a value other than doNotInitiateFileTransfer a file transfer of mfiletransferConfigSettingsFilename will be attempted from either a TFTP or FTP server. This OID shows the last attempted file transfer result. lastFileTransferResultSuccessful (1) means the file transfer was successful. lastFileTransferResultNotAvailable (2) means that there have been no previous file transfers. lastFileTransferResultFailureUnknown (3) means that the last file transfer failed for an unknown reason. lastFileTransferResultFailureServerInaccessible (4) means that the TFTP or FTP server could not be found on the network. lastFileTransferResultFailureServerAccessDenied (5) means that the TFTP or FTP server denied access. lastFileTransferResultFailureFileNotFound (6) means that the file could not be located. lastFileTransferResultFailureFileTypeUnknown (7) means the file was examined, but the contents were unknown. lastFileTransferResultFailureFileCorrupt (8) means the transferred file was corrupt." ::= { mfiletransferStatus 1 } -- the mfiletransferConfig group -- the mfiletransferConfigSettings group mfiletransferConfigSettingsFilename OBJECT-TYPE SYNTAX DisplayString ACCESS read-write STATUS mandatory DESCRIPTION "The path and name of the file to transfer using the mfiletransferControlInitiateFileTransfer OID. If the file to transfer exists in the default server directory then the path may be omitted." ::= { mfiletransferConfigSettings 1 } -- the mfiletransferConfigTFTP group mfiletransferConfigTFTPServerAddress OBJECT-TYPE SYNTAX DisplayString ACCESS read-write STATUS mandatory DESCRIPTION "The IP Address in dotted decimal notation of the TFTP server involved in the file transfer." ::= { mfiletransferConfigTFTP 1 } -- the mfiletransferConfigFTP group mfiletransferConfigFTPServerAddress OBJECT-TYPE SYNTAX DisplayString ACCESS read-write STATUS mandatory DESCRIPTION "The IP Address in dotted decimal notation of the FTP server involved in the file transfer." ::= { mfiletransferConfigFTP 1 } mfiletransferConfigFTPServerUser OBJECT-TYPE SYNTAX DisplayString ACCESS read-write STATUS mandatory DESCRIPTION "The user identification for logging into the FTP server specified with mfiletransferConfigFTPServerAddress." ::= { mfiletransferConfigFTP 2 } mfiletransferConfigFTPServerPassword OBJECT-TYPE SYNTAX DisplayString ACCESS read-write STATUS mandatory DESCRIPTION "The password for logging into the FTP server specified with mfiletransferConfigFTPServerAddress." ::= { mfiletransferConfigFTP 3 } -- the mfiletransferControl group mfiletransferControlInitiateFileTransfer OBJECT-TYPE SYNTAX INTEGER { doNotInitiateFileTransfer (1), initiateFileTransferDownloadViaTFTP (2), initiateFileTransferDownloadViaFTP (3) } ACCESS read-write STATUS mandatory DESCRIPTION "Setting this OID to doNotInitiateFileTransfer (1) will do nothing. Setting this OID to initiateFileTransferDownloadViaTFTP (2) will attempt to transfer the file named in mfiletransferConfigSettingsFilename from the TFTP Server identified in mfiletransferConfigTFTPAddress. Setting this OID to initiateFileTransferDownloadViaFTP (3) will attempt to transfer the file named in mfiletransferConfigSettingsFilename from the FTP Server identified in mfiletransferConfigFTPAddress using mfiletransferConfigFTPUser and mfiletransferConfigFTPPassword for the FTP Server login process." ::= { mfiletransferControl 1 } -- the xPDUIdent group xPDUIdentProductName OBJECT-TYPE SYNTAX DisplayString ACCESS read-write STATUS mandatory DESCRIPTION "The name of the PDU. Maximum size is dependent on device. An error will be returned if the set request exceeds the max size." ::= { xPDUIdent 1 } xPDUIdentHardwareRev OBJECT-TYPE SYNTAX DisplayString ACCESS read-only STATUS mandatory DESCRIPTION "The hardware revision of the PDU. This value is set at the factory." ::= { xPDUIdent 2 } xPDUIdentFirmwareRev OBJECT-TYPE SYNTAX DisplayString ACCESS read-only STATUS mandatory DESCRIPTION "An ID string identifying the PDU firmware revision. This value is set at the factory." ::= { xPDUIdent 3 } xPDUIdentDateOfManufacture OBJECT-TYPE SYNTAX DisplayString ACCESS read-only STATUS mandatory DESCRIPTION "The date when the PDU was manufactured in mm/dd/yyyy format. This value is set at the factory." ::= { xPDUIdent 4 } xPDUIdentModelNumber OBJECT-TYPE SYNTAX DisplayString ACCESS read-only STATUS mandatory DESCRIPTION "A character string identifying the model number of the PDU. This value is set at the factory." ::= { xPDUIdent 5 } xPDUIdentSerialNumber OBJECT-TYPE SYNTAX DisplayString ACCESS read-only STATUS mandatory DESCRIPTION "A character string identifying the serial number of the. This value is set at the factory." ::= { xPDUIdent 6 } -- the xPDUDevice group xPDUDeviceNominalMainInputVoltage OBJECT-TYPE SYNTAX INTEGER ACCESS read-only STATUS mandatory DESCRIPTION "The Nominal Main Input Voltage to the PDU. Measured in VRMS, line-to-line for a delta service or line-to-neutral for a wye service." ::= { xPDUDevice 1 } xPDUDeviceServiceType OBJECT-TYPE SYNTAX INTEGER { delta(1), wye(2) } ACCESS read-only STATUS mandatory DESCRIPTION "The type of utility input to the PDU. Either 3 wires (delta), or 4 wires (wye)." ::= { xPDUDevice 2 } xPDUDeviceNominalOutputVoltage OBJECT-TYPE SYNTAX INTEGER ACCESS read-only STATUS mandatory DESCRIPTION "The nominal line-to-neutral output voltage to the load measured in VRMS." ::= { xPDUDevice 3 } xPDUDeviceMainInputBreakerRating OBJECT-TYPE SYNTAX INTEGER ACCESS read-only STATUS mandatory DESCRIPTION "The rating of the Main Input Breaker measured in ARMS." ::= { xPDUDevice 4 } xPDUDevicePanelBreakerRating OBJECT-TYPE SYNTAX INTEGER ACCESS read-only STATUS mandatory DESCRIPTION "The rating of the Panel Breaker measured in ARMS." ::= { xPDUDevice 5 } xPDUDeviceTransformerPresent OBJECT-TYPE SYNTAX INTEGER { notPresent(1), present(2) } ACCESS read-only STATUS mandatory DESCRIPTION "Indicates whether or not a transformer is installed in the PDU." ::= { xPDUDevice 6 } xPDUIdentCallibrationDate OBJECT-TYPE SYNTAX DisplayString ACCESS read-only STATUS mandatory DESCRIPTION "The date when the PDU was last callibrated in mm/dd/yyyy format." ::= { xPDUDevice 7 } xPDUDeviceLoadTieBreakerPresent OBJECT-TYPE SYNTAX INTEGER { notPresent(1), present(2) } ACCESS read-only STATUS mandatory DESCRIPTION "Indicates whether or not a Load Tie Breaker is installed in the PDU." ::= { xPDUDevice 8 } xPDUDeviceLoadTestPortPresent OBJECT-TYPE SYNTAX INTEGER { notPresent(1), present(2) } ACCESS read-only STATUS mandatory DESCRIPTION "Indicates whether or not a Load Test Port is installed in the PDU." ::= { xPDUDevice 9 } xPDUDeviceFusesPresent OBJECT-TYPE SYNTAX INTEGER { notPresent(1), present(2) } ACCESS read-only STATUS mandatory DESCRIPTION "Indicates whether or not the UPS feed from the PDU includes fuses." ::= { xPDUDevice 10 } xPDUDeviceFansPresent OBJECT-TYPE SYNTAX INTEGER { notPresent(1), present(2) } ACCESS read-only STATUS mandatory DESCRIPTION "Indicates whether or not cooling fans are installed in the PDU." ::= { xPDUDevice 11 } xPDUDeviceBypassInputPresent OBJECT-TYPE SYNTAX INTEGER { notPresent(1), present(2) } ACCESS read-only STATUS mandatory DESCRIPTION "Indicates whether or not the PDU is equipped with a second feed for the UPS's bypass input." ::= { xPDUDevice 12 } xPDUDeviceCrossTieOutputPresent OBJECT-TYPE SYNTAX INTEGER { notPresent(1), present(2) } ACCESS read-only STATUS mandatory DESCRIPTION "Indicates whether or not the PDU is equipped with a cross-tie output." ::= { xPDUDevice 13 } xPDUDeviceEarthGroundMonitorPresent OBJECT-TYPE SYNTAX INTEGER { notPresent(1), present(2) } ACCESS read-only STATUS mandatory DESCRIPTION "Indicates whether or not the PDU can provide ground current measurements." ::= { xPDUDevice 14 } xPDUDeviceInfraXureType OBJECT-TYPE SYNTAX INTEGER { typeB(1), typeC(2) } ACCESS read-only STATUS mandatory DESCRIPTION "Indicates the configuration of this PDU system. Type-B PDU is in a distributed UPS system and has bypass capabilities. Type-C PDU receives power from a larger central UPS." ::= { xPDUDevice 15 } -- Main Input xPDUMainInputOverVoltThreshold OBJECT-TYPE SYNTAX INTEGER (0..30) ACCESS read-write STATUS mandatory DESCRIPTION "Threshold above which an Input Over Voltage condition will be generated. Specified as percent deviation from nominal." ::= { xPDUMainInput 1 } xPDUMainInputUnderVoltThreshold OBJECT-TYPE SYNTAX INTEGER (0..30) ACCESS read-write STATUS mandatory DESCRIPTION "Threshold below which an Input Under Voltage condition will be generated. Specified as percent deviation from nominal." ::= { xPDUMainInput 2 } -- Main Input Voltage Table xPDUMainInputVoltageTableSize OBJECT-TYPE SYNTAX INTEGER ACCESS read-only STATUS mandatory DESCRIPTION "The number of Main Input voltage records." ::= { xPDUMainInput 3 } xPDUMainInputVoltageTable OBJECT-TYPE SYNTAX SEQUENCE OF XPDUMainInputVoltagePhaseEntry ACCESS not-accessible STATUS mandatory DESCRIPTION "A list of input voltage table entries. The number of entries is the sum of phases. The number of entries is contained in the xPDUMainInputVoltageTableSize OID." ::= { xPDUMainInput 4 } xPDUMainInputVoltagePhaseEntry OBJECT-TYPE SYNTAX XPDUMainInputVoltagePhaseEntry ACCESS not-accessible STATUS mandatory DESCRIPTION "An entry containing information applicable to a particular Main Input Voltage phase." INDEX { xPDUMainInputVoltagePhaseIndex } ::= { xPDUMainInputVoltageTable 1 } XPDUMainInputVoltagePhaseEntry ::= SEQUENCE { xPDUMainInputVoltagePhaseIndex INTEGER, xPDUMainInputVoltageLtoL INTEGER, xPDUMainInputVoltageLtoN INTEGER } xPDUMainInputVoltagePhaseIndex OBJECT-TYPE SYNTAX INTEGER{ phase1(1), phase2(2), phase3(3) } ACCESS read-only STATUS mandatory DESCRIPTION "Description of each each input phase utilized in this device." ::= { xPDUMainInputVoltagePhaseEntry 1 } xPDUMainInputVoltageLtoL OBJECT-TYPE SYNTAX INTEGER ACCESS read-only STATUS mandatory DESCRIPTION "Line-to-line PDU input voltage when an isolation transformer is present, or -1 if no transformer present in this PDU. Measured in 0.1 VRMS" ::= { xPDUMainInputVoltagePhaseEntry 2 } xPDUMainInputVoltageLtoN OBJECT-TYPE SYNTAX INTEGER ACCESS read-only STATUS mandatory DESCRIPTION "Line-to-neutral PDU input voltage when an isolation transformer is not present, or -1 if a transformer is present in this PDU. Measured in 0.1 VRMS" ::= { xPDUMainInputVoltagePhaseEntry 3 } xPDUBypassInputOverVoltThreshold OBJECT-TYPE SYNTAX INTEGER (0..30) ACCESS read-write STATUS mandatory DESCRIPTION "Threshold above which a Bypass Input Over Voltage condition will be generated. Specified as percent deviation from nominal." ::= { xPDUBypassInput 1 } xPDUBypassInputUnderVoltThreshold OBJECT-TYPE SYNTAX INTEGER (0..30) ACCESS read-write STATUS mandatory DESCRIPTION "Threshold below which an Bypass Input Under Voltage condition will be generated. Specified as percent deviation from nominal." ::= { xPDUBypassInput 2 } -- Bypass Input Voltage Table xPDUBypassInputVoltageTableSize OBJECT-TYPE SYNTAX INTEGER ACCESS read-only STATUS mandatory DESCRIPTION "The number of Bypass Input voltage records." ::= { xPDUBypassInput 3 } xPDUBypassInputVoltageTable OBJECT-TYPE SYNTAX SEQUENCE OF XPDUBypassInputVoltagePhaseEntry ACCESS not-accessible STATUS mandatory DESCRIPTION "A list of output table entries. The number of entries is given by the sum of phases. The number of entries is contained in the xPDUBypassInputVoltageTableSize OID." ::= { xPDUBypassInput 4 } xPDUBypassInputVoltagePhaseEntry OBJECT-TYPE SYNTAX XPDUBypassInputVoltagePhaseEntry ACCESS not-accessible STATUS mandatory DESCRIPTION "An entry containing information applicable to a particular Bypass Input Voltage phase." INDEX { xPDUBypassInputVoltagePhaseIndex } ::= { xPDUBypassInputVoltageTable 1 } XPDUBypassInputVoltagePhaseEntry ::= SEQUENCE { xPDUBypassInputVoltagePhaseIndex INTEGER, xPDUBypassInputVoltageLtoL INTEGER, xPDUBypassInputVoltageLtoN INTEGER } xPDUBypassInputVoltagePhaseIndex OBJECT-TYPE SYNTAX INTEGER ACCESS read-only STATUS mandatory DESCRIPTION "Index of each input phase entry in the table." ::= { xPDUBypassInputVoltagePhaseEntry 1 } xPDUBypassInputVoltageLtoL OBJECT-TYPE SYNTAX INTEGER ACCESS read-only STATUS mandatory DESCRIPTION "Line-to-line bypass input voltage, or -1 if no bypass feed is present in this PDU. Measured in 0.1 VRMS" ::= { xPDUBypassInputVoltagePhaseEntry 2 } xPDUBypassInputVoltageLtoN OBJECT-TYPE SYNTAX INTEGER ACCESS read-only STATUS mandatory DESCRIPTION "Line-to-neutral bypass input voltage, or -1 if no bypass feed is present in this PDU. Measured in 0.1 VRMS" ::= { xPDUBypassInputVoltagePhaseEntry 3 } -- UPS Input Table xPDUUPSInputVoltageTableSize OBJECT-TYPE SYNTAX INTEGER ACCESS read-only STATUS mandatory DESCRIPTION "The number of UPS Input voltage records." ::= { xPDUUPSInput 1 } xPDUUPSInputVoltageTable OBJECT-TYPE SYNTAX SEQUENCE OF XPDUUPSInputVoltagePhaseEntry ACCESS not-accessible STATUS mandatory DESCRIPTION "A list of UPS input table entries. The number of entries is given by the sum the phases. The number of entries is contained in the xPDUUPSInputVoltageTableSize OID." ::= { xPDUUPSInput 2 } xPDUUPSInputVoltagePhaseEntry OBJECT-TYPE SYNTAX XPDUUPSInputVoltagePhaseEntry ACCESS not-accessible STATUS mandatory DESCRIPTION "An entry containing information applicable to a particular UPS Input Voltage phase." INDEX { xPDUUPSInputVoltagePhaseIndex } ::= { xPDUUPSInputVoltageTable 1 } XPDUUPSInputVoltagePhaseEntry ::= SEQUENCE { xPDUUPSInputVoltagePhaseIndex INTEGER, xPDUUPSInputVoltageLtoNPresent INTEGER } xPDUUPSInputVoltagePhaseIndex OBJECT-TYPE SYNTAX INTEGER{ phase1(1), phase2(2), phase3(3) } ACCESS read-only STATUS mandatory DESCRIPTION "Description of each each input phase utilized in this device." ::= { xPDUUPSInputVoltagePhaseEntry 1 } xPDUUPSInputVoltageLtoNPresent OBJECT-TYPE SYNTAX INTEGER { notPresent(1), present(2) } ACCESS read-only STATUS mandatory DESCRIPTION "Indicates whether or not voltage is present at the UPS feed." ::= { xPDUUPSInputVoltagePhaseEntry 2 } -- System Output xPDUSystemOutputFrequency OBJECT-TYPE SYNTAX INTEGER ACCESS read-only STATUS mandatory DESCRIPTION "The system output frequency in 0.1 Hertz." ::= { xPDUSystemOutput 1 } xPDUSystemOutputNeutralCurrent OBJECT-TYPE SYNTAX INTEGER ACCESS read-only STATUS mandatory DESCRIPTION "Shows the Neutral Current measured at the System Output in 0.1 ARMS." ::= { xPDUSystemOutput 2 } xPDUSystemOutputTotalPower OBJECT-TYPE SYNTAX INTEGER ACCESS read-only STATUS mandatory DESCRIPTION "Shows the Total System Output Power in 1000 Watts (KW)." ::= { xPDUSystemOutput 3 } xPDUSystemOutputTotalVoltAmps OBJECT-TYPE SYNTAX INTEGER ACCESS read-only STATUS mandatory DESCRIPTION "Shows the Total System Output Power in 1000 Volt-Amps (KVA)." ::= { xPDUSystemOutput 4 } xPDUSystemOutputTotalPowerFactor OBJECT-TYPE SYNTAX INTEGER ACCESS read-only STATUS mandatory DESCRIPTION "Indicates the Total Power Factor of the System Output. A value of 100 representing a unity power factor (1.00)" ::= { xPDUSystemOutput 5 } xPDUSystemOutputFrequencyTolerance OBJECT-TYPE SYNTAX INTEGER ACCESS read-write STATUS mandatory DESCRIPTION "Shows the Circuit Panel Output Frequency Tolerance (Hz)." ::= { xPDUSystemOutput 6 } xPDUSystemOutputMaxKWPower OBJECT-TYPE SYNTAX INTEGER ACCESS read-write STATUS mandatory DESCRIPTION "Defines 100% load in 1000 Watts (KW). Purpose is to set to match UPS capabilities." ::= { xPDUSystemOutput 7 } xPDUSystemOutputOverVoltThreshold OBJECT-TYPE SYNTAX INTEGER (0..30) ACCESS read-write STATUS mandatory DESCRIPTION "Threshold above which an Output Over Voltage condition will be generated. Specified as percent deviation from nominal." ::= { xPDUSystemOutput 8 } xPDUSystemOutputUnderVoltThreshold OBJECT-TYPE SYNTAX INTEGER (0..30) ACCESS read-write STATUS mandatory DESCRIPTION "Threshold below which an Output Under Voltage condition will be generated. Specified as percent deviation from nominal." ::= { xPDUSystemOutput 9 } xPDUSystemOutputOverCurrentThreshold OBJECT-TYPE SYNTAX INTEGER (0..100) ACCESS read-write STATUS mandatory DESCRIPTION "Threshold above which an Over Current condition will be generated. Specified as a percent of the Panel Breaker rating." ::= { xPDUSystemOutput 10 } xPDUSystemOutputOverCurrentNeutralThreshold OBJECT-TYPE SYNTAX INTEGER (0..100) ACCESS read-write STATUS mandatory DESCRIPTION "Threshold above which an Over Current Neutral condition will be generated. Specified as a percent of the Panel Breaker rating." ::= { xPDUSystemOutput 11 } xPDUSystemOutputUnderCurrentThreshold OBJECT-TYPE SYNTAX INTEGER (0..100) ACCESS read-write STATUS mandatory DESCRIPTION "Threshold below which an Under Current condition will be generated. Specified as a percent of the Panel Breaker rating." ::= { xPDUSystemOutput 12 } xPDUSystemOutputTableSize OBJECT-TYPE SYNTAX INTEGER ACCESS read-only STATUS mandatory DESCRIPTION "The number of System Output phase records." ::= { xPDUSystemOutput 13 } xPDUSystemOutputTable OBJECT-TYPE SYNTAX SEQUENCE OF XPDUSystemOutputPhaseEntry ACCESS not-accessible STATUS mandatory DESCRIPTION "A list of system output table entries. The number of entries is contained in the xPDUSystemOutputTableSize OID." ::= { xPDUSystemOutput 14 } xPDUSystemOutputPhaseEntry OBJECT-TYPE SYNTAX XPDUSystemOutputPhaseEntry ACCESS not-accessible STATUS mandatory DESCRIPTION "An entry containing information applicable to a particular system output phase." INDEX { xPDUSystemOutputPhaseIndex } ::= { xPDUSystemOutputTable 1 } XPDUSystemOutputPhaseEntry ::= SEQUENCE { xPDUSystemOutputPhaseIndex INTEGER, xPDUSystemOutputVoltageLtoL INTEGER, xPDUSystemOutputVoltageLtoN INTEGER, xPDUSystemOutputPhaseCurrent INTEGER, xPDUSystemOutputPower INTEGER, xPDUSystemOutputVoltAmps INTEGER, xPDUSystemOutputPowerFactor INTEGER } xPDUSystemOutputPhaseIndex OBJECT-TYPE SYNTAX INTEGER{ phase1(1), phase2(2), phase3(3) } ACCESS read-only STATUS mandatory DESCRIPTION "Description of each system output phase utilized in this device." ::= { xPDUSystemOutputPhaseEntry 1 } xPDUSystemOutputVoltageLtoL OBJECT-TYPE SYNTAX INTEGER ACCESS read-only STATUS mandatory DESCRIPTION "Line-to-line system output voltage available at the cicuit panel. Measured in 0.1 VRMS." ::= { xPDUSystemOutputPhaseEntry 2 } xPDUSystemOutputVoltageLtoN OBJECT-TYPE SYNTAX INTEGER ACCESS read-only STATUS mandatory DESCRIPTION "Line-to-neutral system output voltage available at the cicuit panel. Measured in 0.1 VRMS." ::= { xPDUSystemOutputPhaseEntry 3 } xPDUSystemOutputPhaseCurrent OBJECT-TYPE SYNTAX INTEGER ACCESS read-only STATUS mandatory DESCRIPTION "System load current per phase. Measured in 0.1 ARMS." ::= { xPDUSystemOutputPhaseEntry 4 } xPDUSystemOutputPower OBJECT-TYPE SYNTAX INTEGER ACCESS read-only STATUS mandatory DESCRIPTION "System Output Power per phase. Measured in 1000 Watts (KW)." ::= { xPDUSystemOutputPhaseEntry 5 } xPDUSystemOutputVoltAmps OBJECT-TYPE SYNTAX INTEGER ACCESS read-only STATUS mandatory DESCRIPTION "System Output Power per phase. Measured in 1000 Volt-Amps (KVA)." ::= { xPDUSystemOutputPhaseEntry 6 } xPDUSystemOutputPowerFactor OBJECT-TYPE SYNTAX INTEGER ACCESS read-only STATUS mandatory DESCRIPTION "indicates the Power Factor of the System Output per phase. A value of 100 representing a unity Power Factor (1.00)" ::= { xPDUSystemOutputPhaseEntry 7 } xPDUGroundCurrent OBJECT-TYPE SYNTAX INTEGER ACCESS read-only STATUS mandatory DESCRIPTION "Shows the current measured in the earth ground conductor in 0.1 ARMS." ::= { xPDUGroundMonitorPoint 1 } xPDUGroundCurrentThreshold OBJECT-TYPE SYNTAX INTEGER (0..100) ACCESS read-write STATUS mandatory DESCRIPTION "Threshold above which a Ground Current Over current condition will be generated. Measured in 0.1 ARMS." ::= { xPDUGroundMonitorPoint 2 } -- System Breakers xPDUSystemBreakerTableSize OBJECT-TYPE SYNTAX INTEGER ACCESS read-only STATUS mandatory DESCRIPTION "The number of System Breaker records." ::= { xPDUSystemBreakers 1 } xPDUSystemBreakerTable OBJECT-TYPE SYNTAX SEQUENCE OF XPDUSystemBreakerTableEntry ACCESS not-accessible STATUS mandatory DESCRIPTION "A list of System Breaker entries. The number of entries is contained in the xPDUSystemBreakerTableSize OID." ::= { xPDUSystemBreakers 2 } xPDUSystemBreakerTableEntry OBJECT-TYPE SYNTAX XPDUSystemBreakerTableEntry ACCESS not-accessible STATUS mandatory DESCRIPTION "An entry containing information applicable to a particular System Breaker." INDEX { xPDUSystemBreakerTableIndex } ::= { xPDUSystemBreakerTable 1 } XPDUSystemBreakerTableEntry ::= SEQUENCE { xPDUSystemBreakerTableIndex INTEGER, xPDUSystemBreakerDescription DisplayString, xPDUSystemBreakerPosition INTEGER } xPDUSystemBreakerTableIndex OBJECT-TYPE SYNTAX INTEGER ACCESS read-only STATUS mandatory DESCRIPTION "Description of each system breaker utilized in this device." ::= { xPDUSystemBreakerTableEntry 1 } xPDUSystemBreakerDescription OBJECT-TYPE SYNTAX DisplayString (SIZE (0..79)) ACCESS read-only STATUS mandatory DESCRIPTION "A brief description of the System Breakers." ::= { xPDUSystemBreakerTableEntry 2 } xPDUSystemBreakerPosition OBJECT-TYPE SYNTAX INTEGER { open(1), closed(2) } ACCESS read-only STATUS mandatory DESCRIPTION "Indicates whether this breaker is open(1) or closed(2)." ::= { xPDUSystemBreakerTableEntry 3 } -- Branch Breakers (Breaker Panel) xPDUNumOfBranchBreakers OBJECT-TYPE SYNTAX INTEGER ACCESS read-only STATUS mandatory DESCRIPTION "The number Branch Breakers in the Panel." ::= { xPDUBranchBreakers 1 } -- Branch Breakers Table xPDUBranchBreakerTableSize OBJECT-TYPE SYNTAX INTEGER ACCESS read-only STATUS mandatory DESCRIPTION "The number of Branch Breaker records." ::= { xPDUBranchBreakers 2 } xPDUBranchBreakerTable OBJECT-TYPE SYNTAX SEQUENCE OF XPDUBranchBreakerEntry ACCESS not-accessible STATUS mandatory DESCRIPTION "A list of Branch Breaker table entries. The number of entries is given by the value of xPDUBranchBreakerTableSize The number of entries is contained in the xPDUBranchBreakerTableSize OID." ::= { xPDUBranchBreakers 3 } xPDUBranchBreakerEntry OBJECT-TYPE SYNTAX XPDUBranchBreakerEntry ACCESS not-accessible STATUS mandatory DESCRIPTION "An entry containing information applicable to a particular Branch Breaker." INDEX { xPDUBranchBreakerTableIndex } ::= { xPDUBranchBreakerTable 1 } XPDUBranchBreakerEntry ::= SEQUENCE { xPDUBranchBreakerTableIndex INTEGER, xPDUBranchBreakerRating INTEGER, xPDUBranchBreakerRDPFeed INTEGER, xPDUBranchBreakerTieIndicator INTEGER, xPDUBranchBreakerCurrent INTEGER, xPDUBranchBreakerOverCurrentThreshold INTEGER, xPDUBranchBreakerUnderCurrentThreshold INTEGER } xPDUBranchBreakerTableIndex OBJECT-TYPE SYNTAX INTEGER ACCESS read-only STATUS mandatory DESCRIPTION "Description of each each branch circuit utilized in this device." ::= { xPDUBranchBreakerEntry 1 } xPDUBranchBreakerRating OBJECT-TYPE SYNTAX INTEGER (0..100) ACCESS read-write STATUS mandatory DESCRIPTION "Indicates current rating of this breaker. 0=Breaker is not present. 1=Earth breaker. A value greater than 2 indicates breaker current rating." ::= { xPDUBranchBreakerEntry 2 } xPDUBranchBreakerRDPFeed OBJECT-TYPE SYNTAX INTEGER { remoteDistribution(1), noRemoteDistribution(2) } ACCESS read-write STATUS mandatory DESCRIPTION "Indicates that a breaker position is feeding a Remote Distribution Panel" ::= { xPDUBranchBreakerEntry 3 } xPDUBranchBreakerTieIndicator OBJECT-TYPE SYNTAX INTEGER { breakerTied(1), breakerUntied(2) } ACCESS read-write STATUS mandatory DESCRIPTION "Indicates whether or not the breaker pole is physically connected to the breaker immediately below." ::= { xPDUBranchBreakerEntry 4 } xPDUBranchBreakerCurrent OBJECT-TYPE SYNTAX INTEGER ACCESS read-only STATUS mandatory DESCRIPTION "Indicates the Branch Current in 0.1 ARMS or -1 when not available" ::= { xPDUBranchBreakerEntry 5 } xPDUBranchBreakerOverCurrentThreshold OBJECT-TYPE SYNTAX INTEGER (0..100) ACCESS read-write STATUS mandatory DESCRIPTION "Threshold above which a Branch Circuit Over Current condition will be generated. Specified as a percent of the Branch Breaker rating." ::= { xPDUBranchBreakerEntry 6 } xPDUBranchBreakerUnderCurrentThreshold OBJECT-TYPE SYNTAX INTEGER (0..100) ACCESS read-write STATUS mandatory DESCRIPTION "Threshold below which a Branch Circuit Under Current condition will be generated. Specified as a percent of the Branch Breaker rating." ::= { xPDUBranchBreakerEntry 7 } -- the xPDUInputContacts group xPDUInputContactNumContacts OBJECT-TYPE SYNTAX INTEGER ACCESS read-only STATUS mandatory DESCRIPTION "The number of contacts supported by the PDU." ::= { xPDUInputContacts 1 } xPDUInputContactTableSize OBJECT-TYPE SYNTAX INTEGER ACCESS read-only STATUS mandatory DESCRIPTION "The number of input contact records." ::= { xPDUInputContacts 2 } xPDUInputContactTable OBJECT-TYPE SYNTAX SEQUENCE OF XPDUContactEntry ACCESS not-accessible STATUS mandatory DESCRIPTION "A list of contacts supported by the PDU. The number of entries is contained in the xPDUInputContactTableSize OID." ::= { xPDUInputContacts 3 } xPDUInputContactEntry OBJECT-TYPE SYNTAX XPDUContactEntry ACCESS not-accessible STATUS mandatory DESCRIPTION "A contact entry containing information for a given contact." INDEX { xPDUInputContactNumber } ::= { xPDUInputContactTable 1 } XPDUContactEntry ::= SEQUENCE { xPDUInputContactNumber INTEGER, xPDUInputContactName DisplayString, xPDUNormalState INTEGER, xPDUCurrentState INTEGER } xPDUInputContactNumber OBJECT-TYPE SYNTAX INTEGER ACCESS read-only STATUS mandatory DESCRIPTION "An index identifying the contact on the PDU." ::= { xPDUInputContactEntry 1 } xPDUInputContactName OBJECT-TYPE SYNTAX DisplayString ACCESS read-write STATUS mandatory DESCRIPTION "The description of the purpose/use of the contact." ::= { xPDUInputContactEntry 2 } xPDUNormalState OBJECT-TYPE SYNTAX INTEGER { open(1), closed(2) } ACCESS read-write STATUS mandatory DESCRIPTION "The normal operating position of the contact." ::= { xPDUInputContactEntry 3 } xPDUCurrentState OBJECT-TYPE SYNTAX INTEGER { open(1), closed(2) } ACCESS read-only STATUS mandatory DESCRIPTION "This value indicates the current state of the contact." ::= { xPDUInputContactEntry 4 } -- the xPDUOutputRelays group xPDUOutputRelaysNumContacts OBJECT-TYPE SYNTAX INTEGER ACCESS read-only STATUS mandatory DESCRIPTION "The number of Output Relays supported by the PDU." ::= { xPDUOutputRelays 1 } xPDUOutputRelaysTableSize OBJECT-TYPE SYNTAX INTEGER ACCESS read-only STATUS mandatory DESCRIPTION "The number of Output Relay records." ::= { xPDUOutputRelays 2 } xPDUOutputRelayTable OBJECT-TYPE SYNTAX SEQUENCE OF XPDUOutputRelayEntry ACCESS not-accessible STATUS mandatory DESCRIPTION "A list of Output Relays supported by the PDU. The number of entries is contained in the xPDUOutputRelayTableSize OID." ::= { xPDUOutputRelays 3 } xPDUOutputRelayEntry OBJECT-TYPE SYNTAX XPDUOutputRelayEntry ACCESS not-accessible STATUS mandatory DESCRIPTION "A Output Relay entry containing information for a given contact." INDEX { xPDUOutputRelayNumber } ::= { xPDUOutputRelayTable 1 } XPDUOutputRelayEntry ::= SEQUENCE { xPDUOutputRelayNumber INTEGER, xPDUOutputRelayName DisplayString, xPDUOutputNormalState INTEGER, xPDUOutputCurrentState INTEGER } xPDUOutputRelayNumber OBJECT-TYPE SYNTAX INTEGER ACCESS read-only STATUS mandatory DESCRIPTION "An index identifying the Output Relay on the PDU." ::= { xPDUOutputRelayEntry 1 } xPDUOutputRelayName OBJECT-TYPE SYNTAX DisplayString ACCESS read-write STATUS mandatory DESCRIPTION "The description of the purpose/use of the Oudescription of the purpose/use of the Output Relay." ::= { xPDUOutputRelayEntry 2 } xPDUOutputNormalState OBJECT-TYPE SYNTAX INTEGER { open(1), closed(2) } ACCESS read-write STATUS mandatory DESCRIPTION "The normal operating position of the Output Relay." ::= { xPDUOutputRelayEntry 3 } xPDUOutputCurrentState OBJECT-TYPE SYNTAX INTEGER { open(1), closed(2) } ACCESS read-only STATUS mandatory DESCRIPTION "This value indicates the current state of the Output Relay." ::= { xPDUOutputRelayEntry 4 } -- the xPDUMiscGroup xPDUEPOMode OBJECT-TYPE SYNTAX INTEGER { armed(1), disarmed(2) } ACCESS read-only STATUS mandatory DESCRIPTION "Indicates whether the EPO System is armed(1) or disarmed(2)." ::= { xPDUMiscGroup 1 } xPDUTransformTempStatus OBJECT-TYPE SYNTAX INTEGER { normal(1), overtemp(2) } ACCESS read-only STATUS mandatory DESCRIPTION "Indicates if the PDU's isolation transformer is over temperature, or -1 if no transformer is present in this PDU." ::= { xPDUMiscGroup 2 } xPDUCoolingFanStatus OBJECT-TYPE SYNTAX INTEGER { normal(1), failed(2) } ACCESS read-only STATUS mandatory DESCRIPTION "Indicates if one or more of the PDU's cooling fans have failed, or -1 if no cooling fans are present in this PDU" ::= { xPDUMiscGroup 3 } -- the software group -- the powerNetSubAgent group -- the powerNetSoftwareSystem group powerNetSoftwareSystemDescription OBJECT-TYPE SYNTAX DisplayString (SIZE (0..79)) ACCESS read-only STATUS mandatory DESCRIPTION "A brief description of the PowerNet sub-agent." ::= { powerNetSoftwareSystem 1 } powerNetSoftwareOid OBJECT-TYPE SYNTAX OBJECT IDENTIFIER ACCESS read-only STATUS mandatory DESCRIPTION "The object identifier of the PowerNet sub-agent." ::= { powerNetSoftwareSystem 2 } -- powerNetSmuxPeer OBJECT IDENTIFIER ::= { powerNetSoftwareOid 1 } -- powerNetDPIPeer OBJECT IDENTIFIER ::= { powerNetSoftwareOid 2 } powerNetSoftwareSystemUpTime OBJECT-TYPE SYNTAX TimeTicks ACCESS read-only STATUS mandatory DESCRIPTION "The time that the sub-agent has been running." ::= { powerNetSoftwareSystem 3 } -- powerNetSoftwareConfig group powerNetSoftwareTableSize OBJECT-TYPE SYNTAX INTEGER ACCESS read-only STATUS mandatory DESCRIPTION "The number of software modules supporting the UPS." ::= { powerNetSoftwareConfig 1 } powerNetSoftwareTable OBJECT-TYPE SYNTAX SEQUENCE OF SoftwareEntry ACCESS not-accessible STATUS mandatory DESCRIPTION "A list of the software monitoring the UPS." ::= { powerNetSoftwareConfig 2 } powerNetSoftwareEntry OBJECT-TYPE SYNTAX SoftwareEntry ACCESS not-accessible STATUS mandatory DESCRIPTION "An entry containing information on a software module." INDEX { moduleNumber } ::= { powerNetSoftwareTable 1 } SoftwareEntry ::= SEQUENCE { moduleNumber INTEGER, moduleName DisplayString, moduleVersion DisplayString, moduleDate DisplayString } moduleNumber OBJECT-TYPE SYNTAX INTEGER ACCESS read-only STATUS mandatory DESCRIPTION "The index into the Software Entry Table" ::= { powerNetSoftwareEntry 1 } moduleName OBJECT-TYPE SYNTAX DisplayString (SIZE (0..79)) ACCESS read-only STATUS mandatory DESCRIPTION "The name of the software module." ::= { powerNetSoftwareEntry 2 } moduleVersion OBJECT-TYPE SYNTAX DisplayString (SIZE (0..8)) ACCESS read-only STATUS mandatory DESCRIPTION "The version of the software module." ::= { powerNetSoftwareEntry 3 } moduleDate OBJECT-TYPE SYNTAX DisplayString (SIZE (0..9)) ACCESS read-only STATUS mandatory DESCRIPTION "The date of the software module represented as mm-dd-yy." ::= { powerNetSoftwareEntry 4 } -- the ups group -- the upsIdent group -- the upsBasicIdent upsBasicIdentModel OBJECT-TYPE SYNTAX DisplayString ACCESS read-only STATUS mandatory DESCRIPTION "The UPS model name (e.g. 'APC Smart-UPS 600')." ::= { upsBasicIdent 1 } upsBasicIdentName OBJECT-TYPE SYNTAX DisplayString ACCESS read-write STATUS mandatory DESCRIPTION "An 8 byte ID string identifying the UPS. This object can be set by the administrator." ::= { upsBasicIdent 2 } -- the upsAdvIdent group upsAdvIdentFirmwareRevision OBJECT-TYPE SYNTAX DisplayString ACCESS read-only STATUS mandatory DESCRIPTION "The firmware revision of the UPS system's microprocessor." ::= { upsAdvIdent 1 } upsAdvIdentDateOfManufacture OBJECT-TYPE SYNTAX DisplayString ACCESS read-only STATUS mandatory DESCRIPTION "The date when the UPS was manufactured in mm/dd/yy format." ::= { upsAdvIdent 2 } upsAdvIdentSerialNumber OBJECT-TYPE SYNTAX DisplayString ACCESS read-only STATUS mandatory DESCRIPTION "An 8-character string identifying the serial number of the UPS internal microprocessor. This number is set at the factory. NOTE: This number does NOT correspond to the serial number on the rear of the UPS." ::= { upsAdvIdent 3 } -- the upsBattery group -- the upsBasicBattery group upsBasicBatteryStatus OBJECT-TYPE SYNTAX INTEGER { unknown(1), batteryNormal(2), batteryLow(3) } ACCESS read-only STATUS mandatory DESCRIPTION "The status of the UPS batteries. A batteryLow(3) value indicates the UPS will be unable to sustain the current load, and its services will be lost if power is not restored. The amount of run time in reserve at the time of low battery can be configured by the upsAdvConfigLowBatteryRunTime." ::= { upsBasicBattery 1 } upsBasicBatteryTimeOnBattery OBJECT-TYPE SYNTAX TimeTicks ACCESS read-only STATUS mandatory DESCRIPTION "The elapsed time since the UPS has switched to battery power." ::= { upsBasicBattery 2 } upsBasicBatteryLastReplaceDate OBJECT-TYPE SYNTAX DisplayString ACCESS read-write STATUS mandatory DESCRIPTION "The date when the UPS system's batteries were last replaced in mm/dd/yy format. For Smart-UPS models, this value is originally set in the factory. When the UPS batteries are replaced, this value should be reset by the administrator." ::= { upsBasicBattery 3 } -- the upsAdvBattery group upsAdvBatteryCapacity OBJECT-TYPE SYNTAX Gauge ACCESS read-only STATUS mandatory DESCRIPTION "The remaining battery capacity expressed in percent of full capacity." ::= { upsAdvBattery 1 } upsAdvBatteryTemperature OBJECT-TYPE SYNTAX Gauge ACCESS read-only STATUS mandatory DESCRIPTION "The current internal UPS temperature expressed in Celsius." ::= { upsAdvBattery 2 } upsAdvBatteryRunTimeRemaining OBJECT-TYPE SYNTAX TimeTicks ACCESS read-only STATUS mandatory DESCRIPTION "The UPS battery run time remaining before battery exhaustion." ::= { upsAdvBattery 3 } upsAdvBatteryReplaceIndicator OBJECT-TYPE SYNTAX INTEGER { noBatteryNeedsReplacing(1), batteryNeedsReplacing(2) } ACCESS read-only STATUS mandatory DESCRIPTION "Indicates whether the UPS batteries need replacing." ::= { upsAdvBattery 4 } upsAdvBatteryNumOfBattPacks OBJECT-TYPE SYNTAX INTEGER ACCESS read-only STATUS mandatory DESCRIPTION "The number of external battery packs connected to the UPS. If the UPS does not use smart cells then the agent reports ERROR_NO_SUCH_NAME." ::= { upsAdvBattery 5 } upsAdvBatteryNumOfBadBattPacks OBJECT-TYPE SYNTAX INTEGER ACCESS read-only STATUS mandatory DESCRIPTION "The number of external battery packs connected to the UPS that are defective. If the UPS does not use smart cells then the agent reports ERROR_NO_SUCH_NAME." ::= { upsAdvBattery 6 } upsAdvBatteryNominalVoltage OBJECT-TYPE SYNTAX INTEGER ACCESS read-only STATUS mandatory DESCRIPTION "The nominal battery voltage in Volts." ::= { upsAdvBattery 7 } upsAdvBatteryActualVoltage OBJECT-TYPE SYNTAX INTEGER ACCESS read-only STATUS mandatory DESCRIPTION "The actual battery bus voltage in Volts." ::= { upsAdvBattery 8 } upsAdvBatteryCurrent OBJECT-TYPE SYNTAX INTEGER ACCESS read-only STATUS mandatory DESCRIPTION "The battery current in Amps." ::= { upsAdvBattery 9 } upsAdvTotalDCCurrent OBJECT-TYPE SYNTAX INTEGER ACCESS read-only STATUS mandatory DESCRIPTION "The total DC current in Amps." ::= { upsAdvBattery 10 } -- the upsBasicInput group upsBasicInputPhase OBJECT-TYPE SYNTAX INTEGER ACCESS read-only STATUS mandatory DESCRIPTION "The current AC input phase." ::= { upsBasicInput 1 } -- the upsAdvInput group upsAdvInputLineVoltage OBJECT-TYPE SYNTAX Gauge ACCESS read-only STATUS mandatory DESCRIPTION "The current utility line voltage in VAC." ::= { upsAdvInput 1 } upsAdvInputMaxLineVoltage OBJECT-TYPE SYNTAX Gauge ACCESS read-only STATUS mandatory DESCRIPTION "The maximum utility line voltage in VAC over the previous 1 minute period." ::= { upsAdvInput 2 } upsAdvInputMinLineVoltage OBJECT-TYPE SYNTAX Gauge ACCESS read-only STATUS mandatory DESCRIPTION "The minimum utility line voltage in VAC over the previous 1 minute period." ::= { upsAdvInput 3 } upsAdvInputFrequency OBJECT-TYPE SYNTAX Gauge ACCESS read-only STATUS mandatory DESCRIPTION "The current input frequency to the UPS system in Hz." ::= { upsAdvInput 4 } upsAdvInputLineFailCause OBJECT-TYPE SYNTAX INTEGER { noTransfer(1), highLineVoltage(2), brownout(3), blackout(4), smallMomentarySag(5), deepMomentarySag(6), smallMomentarySpike(7), largeMomentarySpike(8), selfTest(9), rateOfVoltageChnage(10) } ACCESS read-only STATUS mandatory DESCRIPTION "The reason for the occurrence of the last transfer to UPS battery power. The variable is set to: - noTransfer(1) -- if there is no transfer yet. - highLineVoltage(2) -- if the transfer to battery is caused by an over voltage greater than the high transfer voltage. - brownout(3) -- if the duration of the outage is greater than five seconds and the line voltage is between 40% of the rated output voltage and the low transfer voltage. - blackout(4) -- if the duration of the outage is greater than five seconds and the line voltage is between 40% of the rated output voltage and ground. - smallMomentarySag(5) -- if the duration of the outage is less than five seconds and the line voltage is between 40% of the rated output voltage and the low transfer voltage. - deepMomentarySag(6) -- if the duration of the outage is less than five seconds and the line voltage is between 40% of the rated output voltage and ground. The variable is set to - smallMomentarySpike(7) -- if the line failure is caused by a rate of change of input voltage less than ten volts per cycle. - largeMomentarySpike(8) -- if the line failure is caused by a rate of change of input voltage greater than ten volts per cycle. - selfTest(9) -- if the UPS was commanded to do a self test. - rateOfVoltageChange(10) -- if the failure is due to the rate of change of the line voltage." ::= { upsAdvInput 5 } -- the upsBasicOutput group upsBasicOutputStatus OBJECT-TYPE SYNTAX INTEGER { unknown(1), onLine(2), onBattery(3), onSmartBoost(4), timedSleeping(5), softwareBypass(6), off(7), rebooting(8), switchedBypass(9), hardwareFailureBypass(10), sleepingUntilPowerReturn(11), onSmartTrim(12) } ACCESS read-only STATUS mandatory DESCRIPTION "The current state of the UPS. If the UPS is unable to determine the state of the UPS this variable is set to unknown(1)." ::= { upsBasicOutput 1 } upsBasicOutputPhase OBJECT-TYPE SYNTAX INTEGER ACCESS read-only STATUS mandatory DESCRIPTION "The current output phase." ::= { upsBasicOutput 2 } -- the upsAdvOutput group upsAdvOutputVoltage OBJECT-TYPE SYNTAX Gauge ACCESS read-only STATUS mandatory DESCRIPTION "The output voltage of the UPS system in VAC." ::= { upsAdvOutput 1 } upsAdvOutputFrequency OBJECT-TYPE SYNTAX Gauge ACCESS read-only STATUS mandatory DESCRIPTION "The current output frequency of the UPS system in Hz." ::= { upsAdvOutput 2 } upsAdvOutputLoad OBJECT-TYPE SYNTAX Gauge ACCESS read-only STATUS mandatory DESCRIPTION "The current UPS load expressed in percent of rated capacity." ::= { upsAdvOutput 3 } upsAdvOutputCurrent OBJECT-TYPE SYNTAX Gauge ACCESS read-only STATUS mandatory DESCRIPTION "The current in amperes drawn by the load on the UPS." ::= { upsAdvOutput 4 } -- the upsBasicConfig group upsBasicConfigNumDevices OBJECT-TYPE SYNTAX INTEGER ACCESS read-only STATUS mandatory DESCRIPTION "The number of devices that are plugged into the UPS." ::= { upsBasicConfig 1 } upsBasicConfigDeviceTable OBJECT-TYPE SYNTAX SEQUENCE OF UpsBasicConfigDeviceEntry ACCESS not-accessible STATUS mandatory DESCRIPTION "A list of devices that are plugged into the UPS. The number of entries is given by the value of upsBasicConfigNumDevices." ::= { upsBasicConfig 2 } upsBasicConfigDeviceEntry OBJECT-TYPE SYNTAX UpsBasicConfigDeviceEntry ACCESS not-accessible STATUS mandatory DESCRIPTION "The devices plugged in to the UPS." INDEX { deviceIndex } ::= { upsBasicConfigDeviceTable 1 } UpsBasicConfigDeviceEntry ::= SEQUENCE { deviceIndex INTEGER, deviceName DisplayString, vaRating INTEGER, acceptThisDevice INTEGER } deviceIndex OBJECT-TYPE SYNTAX INTEGER ACCESS read-only STATUS mandatory DESCRIPTION "The index of the device that is plugged into the UPS." ::= { upsBasicConfigDeviceEntry 1 } deviceName OBJECT-TYPE SYNTAX DisplayString ACCESS read-write STATUS mandatory DESCRIPTION "The name/description of the device plugged into the UPS." ::= { upsBasicConfigDeviceEntry 2 } vaRating OBJECT-TYPE SYNTAX INTEGER ACCESS read-write STATUS mandatory DESCRIPTION "The volt-amp rating of the device plugged into the UPS." ::= { upsBasicConfigDeviceEntry 3 } acceptThisDevice OBJECT-TYPE SYNTAX INTEGER { yes(1), no(2) } ACCESS read-write STATUS mandatory DESCRIPTION "An entry is added if yes, the entry is deleted if no." ::= { upsBasicConfigDeviceEntry 4 } -- the upsAdvConfig group upsAdvConfigRatedOutputVoltage OBJECT-TYPE SYNTAX INTEGER ACCESS read-write STATUS mandatory DESCRIPTION "The nominal output voltage from the UPS in VAC. For a list of allowed values supported by your UPS model, see the UPS User's Manual. If a value other than a supported value is provided in a set request, the UPS interprets it as the next lower acceptable value. If the provided value is lower than the lowest acceptable value, the lowest acceptable value is used." ::= { upsAdvConfig 1 } upsAdvConfigHighTransferVolt OBJECT-TYPE SYNTAX INTEGER ACCESS read-write STATUS mandatory DESCRIPTION "The maximum line voltage in VAC allowed before the UPS system transfers to battery backup. For a list of allowed values supported by your UPS model, see the UPS User's Manual. If a value other than a supported value is provided in a set request, the UPS interprets it as a the next higher acceptable value. If the provided value is higher than the highest acceptable value, the highest acceptable value is used." ::= { upsAdvConfig 2 } upsAdvConfigLowTransferVolt OBJECT-TYPE SYNTAX INTEGER ACCESS read-write STATUS mandatory DESCRIPTION "The minimum line voltage in VAC allowed before the UPS system transfers to battery backup. For a list of allowed values supported by your UPS model, see the UPS User's Manual. If a value other than a supported value is provided in a set request, the UPS interprets it as the next lower acceptable value. If the provided value is lower than the lowest acceptable value, the lowest acceptable value is used." ::= { upsAdvConfig 3 } upsAdvConfigAlarm OBJECT-TYPE SYNTAX INTEGER { timed(1), atLowBattery(2), never(3), mute(4) } ACCESS read-write STATUS mandatory DESCRIPTION "A flag indicating how the UPS should handle audible line fail alarms: timed(1): UPS alarm will sound after a preset timed duration starting from the line fail condition (see OID upsAdvConfigAlarmTimer for the alarm timer value) atLowBattery(2): UPS alarm will sound when the UPS has reached a Low Battery condition during a line fail never(3): Disables the UPS audible alarm mute(4): Mutes the current alarm for some UPSs only when it is in an alarm state and will return to the previously configured option when the UPS recovers from the alarm condition" ::= { upsAdvConfig 4 } upsAdvConfigAlarmTimer OBJECT-TYPE SYNTAX TimeTicks ACCESS read-write STATUS mandatory DESCRIPTION "The time after initial line failure at which the UPS begins emitting audible alarms (beeping). This timer is observed only if the value of extControlAlarm is timed(2). Allowed values are 0 or 30 seconds. If a value other than a supported value is provided in a set request, the UPS interprets it as a the next lower acceptable value. If the provided value is lower than the lowest acceptable value, the lowest acceptable value is used." ::= { upsAdvConfig 5 } upsAdvConfigMinReturnCapacity OBJECT-TYPE SYNTAX INTEGER ACCESS read-write STATUS mandatory DESCRIPTION "The minimum battery capacity required before the UPS will return from a low battery shutdown condition. The capacity is measured from 0% battery capacity (or Low Battery) as a percent of full capacity (100%). In other words, the UPS will not re-energize the output until the battery has charged so that its' capacity is equal to this value. For a list of allowed values supported by your UPS model, see the UPS User's Manual. If a value other than a supported value is provided in a set request, the UPS interprets it as a the next higher acceptable value. If the provided value is higher than the highest acceptable value, the highest acceptable value is used." ::= { upsAdvConfig 6 } upsAdvConfigSensitivity OBJECT-TYPE SYNTAX INTEGER { auto(1), low(2), medium(3), high(4) } ACCESS read-write STATUS mandatory DESCRIPTION "The sensitivity of the UPS to utility line abnormalities or noises." ::= { upsAdvConfig 7 } upsAdvConfigLowBatteryRunTime OBJECT-TYPE SYNTAX TimeTicks ACCESS read-write STATUS mandatory DESCRIPTION "The desired run time of the UPS, in seconds, once the low battery condition is reached. During this time the UPS will produce a constant warning tone which can not be disabled. For a list of allowed values supported by your UPS model, see the UPS User's Manual. If a value other than a supported value is provided in a set request, the UPS interprets the value as the next higher acceptable value. If the provided value is higher than the highest acceptable value, the highest acceptable value is used." ::= { upsAdvConfig 8 } upsAdvConfigReturnDelay OBJECT-TYPE SYNTAX TimeTicks ACCESS read-write STATUS mandatory DESCRIPTION "The delay in seconds after utility line power returns before the UPS will turn on. This value is also used when the UPS comes out of a reboot and before the UPS wakes up from 'sleep' mode. For a list of allowed values supported by your UPS model, see the UPS User's Manual. If a value other than a supported value is provided in a set request, the UPS interprets it as a the next higher acceptable value. If the provided value is higher than the highest acceptable value, the highest acceptable value is used." ::= { upsAdvConfig 9 } upsAdvConfigShutoffDelay OBJECT-TYPE SYNTAX TimeTicks ACCESS read-write STATUS mandatory DESCRIPTION "The delay in seconds the UPS remains on after being told to turn off. For a list of allowed values supported by your UPS model, see the UPS User's Manual. If a value other than a supported value is provided in a set request, the UPS interprets it as a the next higher acceptable value. If the provided value is higher than the highest acceptable value, the highest acceptable value is used." ::= { upsAdvConfig 10 } upsAdvConfigUpsSleepTime OBJECT-TYPE SYNTAX TimeTicks ACCESS read-write STATUS mandatory DESCRIPTION "The time in seconds for the UPS to go to 'sleep' when instructed. When in sleep mode, the UPS will not provide output power regardless of the input line state. Once the specified time has elapsed, output power will be restored. This is a configuration setting. The UPS will not go to sleep until told to do so by the manager from a management station. Any input value is allowed, however the UPS only recognizes 1/10 of an hour increments. The provided value will be rounded to the closest 1/10 of an hour with one exception: Any value entered between 1 and 540 seconds will be rounded to 360 seconds (or 6 minutes)." ::= { upsAdvConfig 11 } upsAdvConfigSetEEPROMDefaults OBJECT-TYPE SYNTAX INTEGER { noSetEEPROMDefaults(1), setEEPROMDefaults(2) } ACCESS read-write STATUS mandatory DESCRIPTION "WRITE: Resets the UPS EEPROM variables to default values. READ: returns 0" ::= { upsAdvConfig 12 } upsAdvConfigDipSwitchSetting OBJECT-TYPE SYNTAX SEQUENCE OF UpsAdvConfigDipSwitchEntry ACCESS not-accessible STATUS mandatory DESCRIPTION "Current settings of UPS dip switches." ::= { upsAdvConfig 13 } upsAdvConfigDipSwitchEntry OBJECT-TYPE SYNTAX UpsAdvConfigDipSwitchEntry ACCESS not-accessible STATUS mandatory DESCRIPTION "The current setting of one dip switch." INDEX { dipSwitchIndex } ::= { upsAdvConfigDipSwitchSetting 1 } UpsAdvConfigDipSwitchEntry ::= SEQUENCE { dipSwitchIndex INTEGER, dipSwitchStatus INTEGER } dipSwitchIndex OBJECT-TYPE SYNTAX INTEGER ACCESS read-only STATUS mandatory DESCRIPTION "The index of a UPS dip switch." ::= { upsAdvConfigDipSwitchEntry 1 } dipSwitchStatus OBJECT-TYPE SYNTAX INTEGER { on(1), off(2) } ACCESS read-only STATUS mandatory DESCRIPTION "The setting of a UPS dip switch." ::= { upsAdvConfigDipSwitchEntry 2 } upsAdvConfigBattExhaustThresh OBJECT-TYPE SYNTAX TimeTicks ACCESS read-write STATUS mandatory DESCRIPTION "The number of seconds prior to battery exhaustion when the UPS will switch off power to its load." ::= { upsAdvConfig 14 } upsAdvConfigPassword OBJECT-TYPE SYNTAX DisplayString ACCESS read-write STATUS mandatory DESCRIPTION "The password entered at the UPS front panel to enable local configuration of the EEProm. If the password is disabled or is not supported, then the agent returns a null string." ::= { upsAdvConfig 15 } upsAdvConfigAllowedSetTable OBJECT-TYPE SYNTAX SEQUENCE OF ApcUpsConfigEntry ACCESS not-accessible STATUS mandatory DESCRIPTION "The table listing the allowed values for all discrete configurable UPS variables." ::= { upsAdvConfig 16 } apcUpsConfigEntry OBJECT-TYPE SYNTAX ApcUpsConfigEntry ACCESS not-accessible STATUS mandatory DESCRIPTION "The table entry for a configurable UPS variable." INDEX { apcUpsConfigFieldIndex } ::= { upsAdvConfigAllowedSetTable 1 } ApcUpsConfigEntry ::= SEQUENCE { apcUpsConfigFieldIndex INTEGER, apcUpsConfigFieldOID OBJECT IDENTIFIER, apcUpsConfigFieldValueRange DisplayString } apcUpsConfigFieldIndex OBJECT-TYPE SYNTAX INTEGER ACCESS read-only STATUS mandatory DESCRIPTION "The index to an eeprom field entry." ::= { apcUpsConfigEntry 1 } apcUpsConfigFieldOID OBJECT-TYPE SYNTAX OBJECT IDENTIFIER ACCESS read-only STATUS mandatory DESCRIPTION "The OID of the current configurable value." ::= { apcUpsConfigEntry 2 } apcUpsConfigFieldValueRange OBJECT-TYPE SYNTAX DisplayString ACCESS read-only STATUS mandatory DESCRIPTION "The discrete set of allowed values of a configurable register. Individual values are delimited by a comma." ::= { apcUpsConfigEntry 3 } upsAdvConfigBattCabAmpHour OBJECT-TYPE SYNTAX INTEGER ACCESS read-write STATUS mandatory DESCRIPTION "Configure settings of UPS battery cabinet amp hour setting." ::= { upsAdvConfig 17 } upsAdvConfigPositionSelector OBJECT-TYPE SYNTAX INTEGER { unknown (1), rack (2), tower (3) } ACCESS read-write STATUS mandatory DESCRIPTION "Configure UPS position selector. If the UPS doesn't support this configuration it will report unknown (1). The positions are either rack (2) for rack mounted or tower (3) for tower unit." ::= { upsAdvConfig 18 } upsAdvConfigOutputFreqRange OBJECT-TYPE SYNTAX INTEGER { unknown (1), freqRangeAUTO (2), freqRange60Var1 (3), freqRange60Var3 (4), freqRange50Var1 (5), freqRange50Var3 (6), freqRange60Var10 (7), freqRange50Var10 (8) } ACCESS read-write STATUS mandatory DESCRIPTION "Configure the output frequency tolerance range. unknown(1) indicates the output frequency is unknown. freqRangeAUTO(2) configure the output frequency range for automatic. freqRange60Var1(3) configure the output frequency range for 60 +/- 0.1 Hz freqRange60Var3(4) configure the output frequency range for 60 +/- 3.0 Hz freqRange50Var1(5) configure the output frequency range for 50 +/- 0.1 Hz freqRange50Var3(6) configure the output frequency range for 50 +/- 3.0 Hz freqRange60Var10(7) configure the output frequency range for 60 +/- 10 Hz freqRange50Var10(8) configure the output frequency range for 50 +/- 10 Hz" ::= { upsAdvConfig 19 } upsAdvConfigUPSFail OBJECT-TYPE SYNTAX INTEGER { unknown (1), gotoBypass (2), dropLoad (3) } ACCESS read-write STATUS mandatory DESCRIPTION "Configure the UPS fail action. If UPS fails, and frequency or voltage is out of range it will either GotoBypass (2) or DropLoad (3). This OID will report unknown (1) if it is not supported feature or option." ::= { upsAdvConfig 20 } upsAdvConfigAlarmRedundancy OBJECT-TYPE SYNTAX INTEGER ACCESS read-write STATUS mandatory DESCRIPTION "Configure settings of UPS alarm if the redundancy is under the current redundancy. Use -1 for never." ::= { upsAdvConfig 21 } upsAdvConfigAlarmLoadOver OBJECT-TYPE SYNTAX INTEGER ACCESS read-write STATUS mandatory DESCRIPTION "Configure settings of UPS alarm if the load is over the current load in kVA. Use -1 for never." ::= { upsAdvConfig 22 } upsAdvConfigAlarmRuntimeUnder OBJECT-TYPE SYNTAX INTEGER ACCESS read-write STATUS mandatory DESCRIPTION "Configure settings of UPS alarm if the runtime is under the current time of minutes. Use -1 for never." ::= { upsAdvConfig 23 } upsAdvConfigVoutReporting OBJECT-TYPE SYNTAX INTEGER { unknown (1), voutAUTO (2), vout208 (3), vout240 (4) } ACCESS read-write STATUS mandatory DESCRIPTION "Configure the way the UPS scales its output voltage readings. unknown(1) indicates the Vout Reporting is unknown. voutAUTO(2) configure the Vout Reporting for automatic scalling. vout208(3) configure the Vout Reporting for 208 Volts. vout240(4) configure the Vout Reporting for 240 Volts." ::= { upsAdvConfig 24 } upsAdvConfigNumExternalBatteries OBJECT-TYPE SYNTAX INTEGER ACCESS read-write STATUS mandatory DESCRIPTION "Configure the number of external batteries connected to the UPS." ::= { upsAdvConfig 25 } upsAdvConfigSimpleSignalShutdowns OBJECT-TYPE SYNTAX INTEGER { unknown (1), disabled (2), enabled (3) } ACCESS read-write STATUS mandatory DESCRIPTION "Configure Simple Signal shutdown commands from the Simple Signal port to be issued to the UPS. unknown(1) indicates the Simple Signal Shutdown setting is unknown. disabled(2) configure to disable Simple Signal Shutdowns. enabled(3) configure to enable Simple Signal Shutdowns." ::= { upsAdvConfig 26 } -- the upsSyncCtrlGroupConfig group upsSCGMembershipGroupNumber OBJECT-TYPE SYNTAX INTEGER ACCESS read-write STATUS mandatory DESCRIPTION "The SCG Membership Group number (MGN) is a 16-bit number allowing up to 65534 separate groups that can be identified and distinguished per IP subnet. Zero and 65535 are not used. The MGN is used in all communication between members of the SCG and a Network Management Card (NMC) will listen and only respond to commands sent to it using its configured SCG ID." ::= { upsSyncCtrlGroupConfig 1 } upsSCGActiveMembershipStatus OBJECT-TYPE SYNTAX INTEGER { enabledSCG (1), disabledSCG (2) } ACCESS read-write STATUS mandatory DESCRIPTION "Membership in the configured SCG can be enabled and disabled. If an NMC is configured for an SCG, but has its membership disabled, all synchronized control commands received will be ignored." ::= { upsSyncCtrlGroupConfig 2 } upsSCGPowerSynchronizationDelayTime OBJECT-TYPE SYNTAX INTEGER ACCESS read-write STATUS mandatory DESCRIPTION "The Power Synchronization Delay Time (PSD) setting is the maximum number of seconds an SCG Initiator will wait for all SCG members to recover utility power before completing the reboot sequence of a reboot or sleep command. If all SCG members are ready to proceed, no additional delay is introduced." ::= { upsSyncCtrlGroupConfig 3 } upsSCGReturnBatteryCapacityOffset OBJECT-TYPE SYNTAX INTEGER ACCESS read-write STATUS mandatory DESCRIPTION "A reboot command uses the Initiators Return battery Capacity (RBC) to control when the SCG completes this operation. In a Normal Control Operation (NCC) the UPS will only complete the reboot if RBC is reached. Due to normal battery charge rate variations it may be desirable for the Followers to complete the reboot if they are within some range of the Initiators RBC when the Initiator is prepared (charged to RBC) to complete the reboot. The Return Battery Capacity Offset (RBCO) defines a percent battery capacity subtracted from an RBC above which a Followers battery must be charged for it to complete a reboot. For example, if the Initiators RBC is 50% and the Initiators RBCO is 5% then a Followers battery capacity is within range if it is greater or equal to 45% (50% - 5%) at the time when the Initiator tries to complete the reboot command. The default RBCO is 10%. " ::= { upsSyncCtrlGroupConfig 4 } upsSCGMultiCastIP OBJECT-TYPE SYNTAX IpAddress ACCESS read-write STATUS mandatory DESCRIPTION "The MultiCast IP address of the SCG Group." ::= { upsSyncCtrlGroupConfig 5 } -- the upsSyncCtrlGroupStatus group upsSCGNumOfGroupMembers OBJECT-TYPE SYNTAX INTEGER ACCESS read-only STATUS mandatory DESCRIPTION "The number of active, communicating members in the Sync Control Group (SCG). This variable indicates the number of rows in the SCG Status Table." ::= { upsSyncCtrlGroupStatus 1 } -- Sync Control Group Status Table upsSCGStatusTable OBJECT-TYPE SYNTAX SEQUENCE OF UpsSCGStatusEntry ACCESS not-accessible STATUS mandatory DESCRIPTION "A list of SCG status table entries. The number of entries is given by the value of upsSCGNumOfGroupMembers." ::= { upsSyncCtrlGroupStatus 2 } upsSCGStatusEntry OBJECT-TYPE SYNTAX UpsSCGStatusEntry ACCESS not-accessible STATUS mandatory DESCRIPTION "An entry containing information applicable to a particular SCG Member." INDEX { upsSCGStatusTableIndex } ::= { upsSCGStatusTable 1 } UpsSCGStatusEntry ::= SEQUENCE { upsSCGStatusTableIndex INTEGER, upsSCGMemberIP IpAddress, upsSCGACInputStatus INTEGER, upsSCGACOutputStatus INTEGER } upsSCGStatusTableIndex OBJECT-TYPE SYNTAX INTEGER ACCESS read-only STATUS mandatory DESCRIPTION "The index of a status entry for an active, communicating SCG member." ::= { upsSCGStatusEntry 1 } upsSCGMemberIP OBJECT-TYPE SYNTAX IpAddress ACCESS read-only STATUS mandatory DESCRIPTION "The IP address of an active, communicating SCG Member." ::= { upsSCGStatusEntry 2 } upsSCGACInputStatus OBJECT-TYPE SYNTAX INTEGER { acInGood(1), acInBad(2) } ACCESS read-only STATUS mandatory DESCRIPTION "This OID indicates the AC Input Status of the SCG Member. acInGood(1) indicates the AC Input is within tolerance. acInBad(2) indicates the AC Input is not within tolerance." ::= { upsSCGStatusEntry 3 } upsSCGACOutputStatus OBJECT-TYPE SYNTAX INTEGER { acOutOn(1), acOutOff(2) } ACCESS read-only STATUS mandatory DESCRIPTION "This OID indicates the AC Output Status of the SCG Member. acOutOn(1) indicates the UPS output is providing power to the load. acOutOff(2) indicates the UPS output is not providing power to the load. " ::= { upsSCGStatusEntry 4 } -- the upsBasicState group upsBasicStateOutputState OBJECT-TYPE SYNTAX DisplayString ACCESS read-only STATUS mandatory DESCRIPTION "An ASCII string containing the 64 flags representing the current state(s) of the UPS. If the Network Card is unable to determine the state of the UPS, this variable is set to UNKNOWN. The flags are numbered 1 to 64, read from left to right. The flags are defined as follows: Flag 1: Abnormal Condition Present Flag 2: On Battery Flag 3: Low Battery Flag 4: On Line Flag 5: Replace Battery Flag 6: Serial Communication Established Flag 7: AVR Boost Active* Flag 8: AVR Trim Active* Flag 9: Overload Flag 10: Runtime Calibration Flag 11: Batteries Discharged Flag 12: Manual Bypass Flag 13: Software Bypass Flag 14: In Bypass due to Internal Fault Flag 15: In Bypass due to Supply Failure* Flag 16: In Bypass due to Fan Failure* Flag 17: Sleeping on a Timer Flag 18: Sleeping until Utility Power Returns Flag 19: On Flag 20: Rebooting Flag 21: Battery Communication Lost* Flag 22: Graceful Shutdown Initiated Flag 23: Smart Boost or Smart Trim Fault* Flag 24: Bad Output Voltage* Flag 25: Battery Charger Failure* Flag 26: High Battery Temperature Flag 27: Self Test In Progress Flag 28: Low Battery / On Battery Flag 29: Graceful Shutdown Issued by Upstream Device Flag 30: Graceful Shutdown Issued by Downstream Device Flag 31: No Batteries Attached* Flag 32: Synchronized command is in progress Flag 33: Flag 34: Flag 35: Flag 36: Flag 37: Flag 38: Flag 39: Flag 40: Flag 41: Flag 42: Flag 43: Flag 44: Flag 45: Flag 46: Flag 47: Flag 48: Flag 49: Flag 50: Flag 51: Flag 52: Flag 53: Flag 54: Flag 55: Flag 56: Flag 57: Flag 58: Flag 59: Flag 60: Flag 61: Flag 62: Flag 63: Flag 64: " ::= { upsBasicState 1 } -- the upsAdvState group upsAdvStateAbnormalConditions OBJECT-TYPE SYNTAX DisplayString ACCESS read-only STATUS mandatory DESCRIPTION "An ASCII string containing the 32 flags representing the current active UPS faults. If the Network Card is unable to determine the values of the flags, this variable is set to UNKNOWN. If this variable is not supported by the connected UPS, this variable is set to NOT SUPPORTED. The flags are numbered from 1 to 32, and read from left to right. The flags are defined as follows: Flag 1: Power Module Failure Flag 2: Main Intelligence Module Failure Flag 3: Redundant Intelligence Module Failure Flag 4: Battery Failure Flag 5: Load(kVA) Alarm Threshold Violation Flag 6: Redundancy Lost Flag 7: Redundancy Below Alarm Threshold Flag 8: Bypass notin Range; Either Frequency or Voltage Flag 9: Bypass Contactor Stuck in Bypass Condition Flag 10: Bypass Contactor Stuck in On-Line Condition Flag 11: In Bypass due to an Internal Fault Flag 12: In Bypass due to an Overload Flag 13: In Maintanence Bypass Flag 14: Input Circuit Braker Tripped Open Flag 15: System Level Fan Failure Flag 16: Redundant Intelligent Module in Control Flag 17: IIC Inter-Module Communication Failure Flag 18: No Working Power Modules Flag 19: Load Shutdown From Bypass; Input Frequency Flag 20: Runtime Below Alarm Threshold Flag 21: Extended Run Frame Fault Flag 22: Output Voltage out of Range Flag 23: UPS Not Synchronized Flag 24: No Batteries Installed Flag 25: Battery Voltage High Flag 26: UPS Specific Fault Detected Flag 27: Site Wiring Fault Flag 28: Backfeed Protection Relay Opened Flag 29: Flag 30: Flag 31: Flag 32: " ::= { upsAdvState 1 } upsAdvStateSymmetra3PhaseSpecificFaults OBJECT-TYPE SYNTAX DisplayString ACCESS read-only STATUS mandatory DESCRIPTION "An ASCII string containing the 64 flags representing the current active UPS specific faults for the Symmetra 3-Phase UPS models. If the Network Card is unable to determine the values of the flags, this variable is set to UNKNOWN. If the connected UPS does not use this variable, it is set to NOT SUPPORTED. The flags are numbered from 1 to 64, and read from left to right. The bits are defined as follows: Flag 1: External Switch Gear Failure Flag 2: External Transformer Over Temperature Flag 3: External DC Circuit Breaker Tripped Flag 4: System Power Supply Failure Flag 5: Battery Monitor Card Failure Flag 6: Battery Monitor Card Removed Flag 7: XR Communication Card Failure Flag 8: XR Communication Card Removed Flag 9: External Switch Gear Monitoring Card Failure Flag 10: External Switch Gear Monitoring Card Removed Flag 11: Internal DC Circiut Breaker Tripped Flag 12: Static Bypass Switch Failure Flag 13: System EEPROM Removed Flag 14: System EEPROM Failure Flag 15: UPS in Forced Bypass Flag 16: Flag 17: Flag 18: Flag 19: Flag 20: Flag 21: Flag 22: Flag 23: Flag 24: Flag 25: Flag 26: Flag 27: Flag 28: Flag 29: Flag 30: Flag 31: Flag 32: Flag 33: Flag 34: Flag 35: Flag 36: Flag 37: Flag 38: Flag 39: Flag 40: Flag 41: Flag 42: Flag 43: Flag 44: Flag 45: Flag 46: Flag 47: Flag 48: Flag 49: Flag 50: Flag 51: Flag 52: Flag 53: Flag 54: Flag 55: Flag 56: Flag 57: Flag 58: Flag 59: Flag 60: Flag 61: Flag 62: Flag 63: Flag 64: " ::= { upsAdvState 2 } upsAdvStateDP300ESpecificFaults OBJECT-TYPE SYNTAX DisplayString ACCESS read-only STATUS mandatory DESCRIPTION "An ASCII string containing the 64 flags representing the current active UPS specific faults for the Silcon DP300E UPS models. If the Network Card is unable to determine the values of the flags, this variable is set to UNKNOWN. If the connected UPS does not use this variable, it is set to NOT SUPPORTED. The flags are numbered from 1 to 64, and read from left to right. The bits are defined as follows: Flag 1: Peak Current Limiter Avtive Flag 2: Bypass Power Supply Fault Flag 3: Delta Current LImiter Active Flag 4: Fan Fault Flag 5: High DC warning Flag 6: Inverter Voltage Error Flag 7: Parallel Synchronization Error Flag 8: Second Power Supply Fault Flag 9: Internal Power Supply Fault Flag 10: Flag 11: Flag 12: Flag 13: Flag 14: Bypass Static Switch High Temperature Flag 15: High Battery Temperature Flag 16: Battery Weak Flag 17: Flag 18: System Locked in Operation Mode Flag 19: RAM1 Memory Write Error Flag 20: Memory Write Error Flag 21: Communication to VQ Bypass Lost Flag 22: Communication to VQ Output Lost Flag 23: Communication to DMU Lost Flag 24: Communication to Controller Lost Flag 25: Communication to Parallel IF Lost Flag 26: External Shutdown Accepted Flag 27: DC Capacitor Charge Error Flag 28: Communication to VQ Mains Lost Flag 29: Bypass Synchronization Error Flag 30: Charge Error Flag 31: Flag 32: Flag 33: Flag 34: Flag 35: Flag 36: Flag 37: Flag 38: Flag 39: Flag 40: Flag 41: Flag 42: Flag 43: Flag 44: Flag 45: Flag 46: Flag 47: Flag 48: Flag 49: Flag 50: Flag 51: Flag 52: Flag 53: Flag 54: Flag 55: Flag 56: Flag 57: Flag 58: Flag 59: Flag 60: Flag 61: Flag 62: Flag 63: Flag 64: " ::= { upsAdvState 3 } -- the upsBasicControl group upsBasicControlConserveBattery OBJECT-TYPE SYNTAX INTEGER { noTurnOffUps(1), turnOffUpsToConserveBattery(2) } ACCESS read-write STATUS mandatory DESCRIPTION "Setting this variable to turnUpsOffToConserveBattery(2) causes a UPS on battery to be put into 'sleep' mode. The UPS will turn back on when utility power is restored. Attempting to turn off a UPS that is not on battery will result in a badValue error. Setting this value to noTurnOffUps(1) has no effect. The value noTurnOffUps(1) will always be returned when the variable is read." ::= { upsBasicControl 1 } -- the upsAdvControl group upsAdvControlUpsOff OBJECT-TYPE SYNTAX INTEGER { noTurnUpsOff(1), turnUpsOff(2), turnUpsOffGracefully(3), turnUpsSyncGroupOff(4), turnUpsSyncGroupOffAfterDelay(5), turnUpsSyncGroupOffGracefully(6) } ACCESS read-write STATUS mandatory DESCRIPTION "Setting this variable to turnUpsOff(2) causes the UPS to shut off. When in this state, the UPS will not provide output power regardless of the input line state. Setting this variable to turnUpsOffGracefully(3) causes the UPS to shut off after a delay period. This allows the host to shut down in a graceful manner. When in this state, the UPS will not provide output power regardless of the input line state. If this UPS is an active member of a Synchronized Control Group (SCG) the turnUpsSyncGroupOff(4) command will perform a Synchronized Turn Off of all active Group members regardless of their current AC output status. If this UPS is an active member of a Synchronized Control Group (SCG) the turnUpsSyncGroupOffAfterDelay(5) command will perform a Synchronized Turn Off After Delay of all active Group members regardless of their current AC output status. This unit's Shutdown Delay will be used to execute the Turn Off After Delay command. If this UPS is an active member of an SCG, the turnUpsSyncGroupOffGracefully(6) command will perform a Synchronized Turn Off Gracefully of all active Group members regardless of their current AC output status. This unit's Maximum Shutdown Time and Shutdown Delay will be used to execute the Turn Off Gracefully command. Setting this value to noTurnUpsOff(1) has no effect. The value noTurnUpsOff(1) will always be returned when the variable is read." ::= { upsAdvControl 1 } upsAdvControlRebootUps OBJECT-TYPE SYNTAX INTEGER { noRebootUps(1), rebootUps(2), rebootUpsGracefully(3), rebootSyncGroupUps(4), rebootSyncGroupUpsGracefully(5) } ACCESS read-write STATUS mandatory DESCRIPTION "Setting this variable to rebootUps(2) causes the UPS to shut off and turn back on. Setting this variable to rebootUpsGracefully(3) causes the UPS to shut off and turn back on after a delay period. This allows the host to shut down in a graceful manner. If this UPS is an active member of a Synchronized Control Group (SCG) the rebootSyncGroupUps(4) command will perform a Synchronized Reboot of all active Group members regardless of their current AC output status. This unit's Power Synchronization Delay, Shutdown Delay, Return Delay, Return Battery Capacity, and Return Battery Capacity Offset will be used to execute the Reboot command. If this UPS is an active member of a SCG the rebootSyncGroupUpsGracefully(5) command will perform a Synchronized Reboot of all active Group members regardless of their current AC output status. This unit's Power Synchronization Delay, Maximum Shutdown Time, Shutdown Delay, Return Delay, Return Battery Capacity, and Return Battery Capacity Offset will be used to execute the Reboot command. Setting this value to noRebootUps(1) has no effect. The value noRebootUps(1) will always be returned when the variable is read." ::= { upsAdvControl 2 } upsAdvControlUpsSleep OBJECT-TYPE SYNTAX INTEGER { noPutUpsToSleep(1), putUpsToSleep(2), putUpsToSleepGracefully(3), putUpsSyncGroupToSleep(4), putUpsSyncGroupToSleepGracefully(5) } ACCESS read-write STATUS mandatory DESCRIPTION "Setting this variable to putUpsToSleep(2) causes the UPS to go to sleep for the time specified by upsAdvConfigUpsSleepTime. Setting this variable to putUpsToSleepGracefully(3) causes the UPS to go to sleep for the time specified by upsAdvConfigUpsSleepTime after a delay period. This allows the host to shut down in a graceful manner. If this UPS is an active member of a Synchronized Control Group (SCG), the putUpsSyncGroupToSleep(4) command will perform a Synchronized Sleep of all active Group members regardless of their current AC output status. This unit's Power Synchronization Delay, Shutdown Delay, Sleep Time, and Return Delay will be used to execute the sleep command. If this UPS is an active member of a SCG the putUpsSyncGroupToSleepGracefully(5) command will perform a Synchronized Sleep Gracefully of all active Group members regardless of their current AC output status. This unit's Power Synchronization Delay, Maximum Shutdown Time, Shutdown Delay, Sleep Time, and Return Delay to execute the sleep command. When in sleep mode, the UPS will not provide output power regardless of the input line state. Once the specified time has elapsed, output power will be restored. Setting this value to noPutUpsToSleep(1) has no effect. The value noPutUpsToSleep(1) will always be returned when the variable is read." ::= { upsAdvControl 3 } upsAdvControlSimulatePowerFail OBJECT-TYPE SYNTAX INTEGER { noSimulatePowerFailure(1), simulatePowerFailure(2) } ACCESS read-write STATUS mandatory DESCRIPTION "Setting this variable to simulatePowerFailure(2) causes the UPS switch to battery power. Setting this value to noSimulatePowerFailure(1) has no effect. The value noSimulatePowerFailure(1) will always be returned when the variable is read." ::= { upsAdvControl 4 } upsAdvControlFlashAndBeep OBJECT-TYPE SYNTAX INTEGER { noFlashAndBeep(1), flashAndBeep(2), flashAndBeepSyncGroup(3) } ACCESS read-write STATUS mandatory DESCRIPTION "Setting this variable to flashAndBeep(2) causes the UPS to beep and simultaneously turn on the UPS front panel lights (Smart-UPS only). If this UPS is an active member of a Synchronized Control Group (SCG), the flashAndBeepSyncGroup(3) command will Flash and Beep all active Group members regardless of current AC output status. Setting this value to noFlashAndBeep(1) has no effect. The value noFlashAndBeep(1) will always be returned when the variable is read." ::= { upsAdvControl 5 } upsAdvControlTurnOnUPS OBJECT-TYPE SYNTAX INTEGER { noTurnOnUPS(1), turnOnUPS(2), turnOnUPSSyncGroup(3) } ACCESS read-write STATUS mandatory DESCRIPTION "Setting this variable to turnOnUPS(2) causes the UPS to be turned on immediately. If this UPS is an active member of a Synchronized Control Group (SCG), the turnOnUPSSyncGroup(3) command will perform a Synchronized Turn On of all active Group members regardless of their current AC output status. Setting this value to noTurnOnUPS(1) has no effect. The value noTurnOnUPS(1) will always be returned when the variable is read." ::= { upsAdvControl 6 } upsAdvControlBypassSwitch OBJECT-TYPE SYNTAX INTEGER { noBypassSwitch (1), switchToBypass (2), switchOutOfBypass(3) } ACCESS read-write STATUS mandatory DESCRIPTION "This switch puts the UPS in or out of bypass mode." ::= { upsAdvControl 7 } -- the upsTest group -- the upsBasicTest group -- the upsAdvTest group upsAdvTestDiagnosticSchedule OBJECT-TYPE SYNTAX INTEGER { unknown(1), biweekly(2), weekly(3), atTurnOn(4), never(5) } ACCESS read-write STATUS mandatory DESCRIPTION "The UPS system's automatic battery test schedule." ::= { upsAdvTest 1 } upsAdvTestDiagnostics OBJECT-TYPE SYNTAX INTEGER { noTestDiagnostics(1), testDiagnostics(2) } ACCESS read-write STATUS mandatory DESCRIPTION "Setting this variable to testDiagnostics(2) causes the UPS to perform a diagnostic self test. Setting this value to noTestDiagnostics(1) has no effect. The value noTestDiagnostics(1) will always be returned when the variable is read." ::= { upsAdvTest 2 } upsAdvTestDiagnosticsResults OBJECT-TYPE SYNTAX INTEGER { ok(1), failed(2), invalidTest(3), testInProgress(4) } ACCESS read-only STATUS mandatory DESCRIPTION "The results of the last UPS diagnostics test performed." ::= { upsAdvTest 3 } upsAdvTestLastDiagnosticsDate OBJECT-TYPE SYNTAX DisplayString ACCESS read-only STATUS mandatory DESCRIPTION "The date the last UPS diagnostics test was performed in mm/dd/yy format." ::= { upsAdvTest 4 } upsAdvTestRuntimeCalibration OBJECT-TYPE SYNTAX INTEGER { noPerformCalibration(1), performCalibration(2), cancelCurrentCalibration(3) } ACCESS read-write STATUS mandatory DESCRIPTION "Setting this variable to performCalibration(2) causes the UPS to discharge to calibrate the UPS. The test will only start if the battery capacity is 100%. The test runs until capacity is less than 25%. Setting this variable to cancelCurrentCalibration(3) after setting performCalibration(2) will cancel the current discharge. Setting this variable to noPerformCalibration(1) will have no effect. The value noPerformCalibration(1) will always be returned when the variable is read. The result of the calibration will be saved in upsAdvTestCalibrationResult." ::= { upsAdvTest 5 } upsAdvTestCalibrationResults OBJECT-TYPE SYNTAX INTEGER { ok(1), invalidCalibration(2), calibrationInProgress(3) } ACCESS read-only STATUS mandatory DESCRIPTION "The results of the last runtime calibration. Value ok(1) means a successful runtime calibration. Value invalidCalibration(2) indicates last calibration did not take place since the battery capacity was below 100%. Value calibrationInProgress(3) means a calibration is occurring now. " ::= { upsAdvTest 6 } upsAdvTestCalibrationDate OBJECT-TYPE SYNTAX DisplayString ACCESS read-only STATUS mandatory DESCRIPTION "The date the last UPS runtime calibration was performed in mm/dd/yy format." ::= { upsAdvTest 7 } -- the upsComm group upsCommStatus OBJECT-TYPE SYNTAX INTEGER { ok(1), noComm(2) } ACCESS read-only STATUS mandatory DESCRIPTION "The status of agent's communication with UPS. " ::= { upsComm 1 } -- the measureUps group -- the Environ group mUpsEnvironAmbientTemperature OBJECT-TYPE SYNTAX Gauge ACCESS read-only STATUS mandatory DESCRIPTION "The ambient temperature in Celsius for Probe 1." ::= { mUpsEnviron 1 } mUpsEnvironRelativeHumidity OBJECT-TYPE SYNTAX Gauge ACCESS read-only STATUS mandatory DESCRIPTION "The relative humidity as a percentage for Probe 1." ::= { mUpsEnviron 2 } mUpsEnvironAmbientTemperature2 OBJECT-TYPE SYNTAX Gauge ACCESS read-only STATUS mandatory DESCRIPTION "The ambient temperature in Celsius for Probe 2." ::= { mUpsEnviron 3 } mUpsEnvironRelativeHumidity2 OBJECT-TYPE SYNTAX Gauge ACCESS read-only STATUS mandatory DESCRIPTION "The relative humidity as a percentage for Probe 2." ::= { mUpsEnviron 4 } -- the mUpsContact group mUpsContactNumContacts OBJECT-TYPE SYNTAX INTEGER ACCESS read-only STATUS mandatory DESCRIPTION "The number of contacts supported by the Measure-UPS." ::= { mUpsContact 1 } mUpsContactTable OBJECT-TYPE SYNTAX SEQUENCE OF ContactEntry ACCESS not-accessible STATUS mandatory DESCRIPTION "A list of contacts supported by the Measure-UPS." ::= { mUpsContact 2 } mUpsContactEntry OBJECT-TYPE SYNTAX ContactEntry ACCESS not-accessible STATUS mandatory DESCRIPTION "A contact entry containing information for a given contact." INDEX { contactNumber } ::= { mUpsContactTable 1 } ContactEntry ::= SEQUENCE { contactNumber INTEGER, normalState INTEGER, description DisplayString, monitoringStatus INTEGER, currentStatus INTEGER } contactNumber OBJECT-TYPE SYNTAX INTEGER ACCESS read-only STATUS mandatory DESCRIPTION "An index identifying the contact on the Measure-UPS." ::= { mUpsContactEntry 1 } normalState OBJECT-TYPE SYNTAX INTEGER { unknown(1), open(2), closed(3) } ACCESS read-write STATUS mandatory DESCRIPTION "The normal operating position of the contact. If the normal operating position cannot be set then it is controlled via the dip switch on the Measure-UPS and is therefore read-only." ::= { mUpsContactEntry 2 } description OBJECT-TYPE SYNTAX DisplayString ACCESS read-write STATUS mandatory DESCRIPTION "The description of the purpose/use of the contact." ::= { mUpsContactEntry 3 } monitoringStatus OBJECT-TYPE SYNTAX INTEGER { unknown(1), enabled(2), disabled(3) } ACCESS read-write STATUS mandatory DESCRIPTION "A flag indicating whether this contact is monitored, or not." ::= { mUpsContactEntry 4 } currentStatus OBJECT-TYPE SYNTAX INTEGER { unknown(1), noFault(2), fault(3) } ACCESS read-only STATUS mandatory DESCRIPTION "This value indicates the current state of the contact. If the contact is not in its normal state. This value is set to fault(2)." ::= { mUpsContactEntry 5 } -- Three Phase Group -- -- Reset Max/Min Values Group -- upsPhaseResetMaxMinValues OBJECT-TYPE SYNTAX INTEGER { none (1), reset (2) } ACCESS read-write STATUS mandatory DESCRIPTION "Reset the maximum and minimum UPS values: upsPhaseInputMaxVoltage, upsPhaseInputMinVoltage, upsPhaseInputMaxCurrent, upsPhaseInputMinCurrent, upsPhaseInputMaxPower, upsPhaseInputMinPower, upsPhaseOutputMaxCurrent, upsPhaseOutputMinCurrent, upsPhaseOutputMaxLoad, upsPhaseOutputMinLoad, upsPhaseOutputMaxPercentLoad, upsPhaseOutputMinPercentLoad, upsPhaseOutputMaxPower, upsPhaseOutputMinPower, upsPhaseOutputMaxPercentPower, upsPhaseOutputMinPercentPower." ::= { upsPhaseResetValues 1 } -- -- Input Group -- -- Number of Inputs upsPhaseNumInputs OBJECT-TYPE SYNTAX INTEGER ACCESS read-only STATUS mandatory DESCRIPTION "The number of input feeds to this device. This variable indicates the number of rows in the input table." ::= { upsPhaseInput 1 } -- Input Table upsPhaseInputTable OBJECT-TYPE SYNTAX SEQUENCE OF UpsPhaseInputEntry ACCESS not-accessible STATUS mandatory DESCRIPTION "A list of input table entries. The number of entries is given by the value of upsPhaseNumInputs." ::= { upsPhaseInput 2 } upsPhaseInputEntry OBJECT-TYPE SYNTAX UpsPhaseInputEntry ACCESS not-accessible STATUS mandatory DESCRIPTION "An entry containing information applicable to a particular input." INDEX { upsPhaseInputTableIndex } ::= { upsPhaseInputTable 1 } UpsPhaseInputEntry ::= SEQUENCE { upsPhaseInputTableIndex INTEGER, upsPhaseNumInputPhases INTEGER, upsPhaseInputVoltageOrientation INTEGER, upsPhaseInputFrequency INTEGER, upsPhaseInputType INTEGER, upsPhaseInputName DisplayString } upsPhaseInputTableIndex OBJECT-TYPE SYNTAX INTEGER ACCESS read-only STATUS mandatory DESCRIPTION "The input identifier." ::= { upsPhaseInputEntry 1 } upsPhaseNumInputPhases OBJECT-TYPE SYNTAX INTEGER ACCESS read-only STATUS mandatory DESCRIPTION "The number of input phases utilized in this device. The sum of all the upsPhaseNumInputPhases variable indicates the number of rows in the input phase table." ::= { upsPhaseInputEntry 2 } upsPhaseInputVoltageOrientation OBJECT-TYPE SYNTAX INTEGER { unknown(1), singlePhase(2), splitPhase(3), threePhasePhaseToNeutral(4), threePhasePhaseToPhase(5) } ACCESS read-only STATUS mandatory DESCRIPTION "The input voltage orientation: 1: unknown for this UPS 2: singlePhase - phase 1 voltage is between Phase 1 and Neutral. 3: splitPhase - phase 1 voltage is between Phase 1 and Neutral; phase 2 voltage is between Phase 2 and Neutral; phase 3 voltage is between Phase 1 and Phase2. 4: threePhasePhaseToNeutral - phase 1 voltage is between Phase 1 and Neutral; phase 2 voltage is between Phase 2 and Neutral; phase 3 voltage is between Phase3 and Neutral. 5: threePhasePhaseToPhase - phase 1 voltage is between Phase 1 and Phase 2; phase 2 voltage is between Phase 2 and Phase 3; phase 3 voltage is between Phase 3 and Phase 1." ::= { upsPhaseInputEntry 3 } upsPhaseInputFrequency OBJECT-TYPE SYNTAX INTEGER ACCESS read-only STATUS mandatory DESCRIPTION "The input frequency in 0.1 Hertz, or -1 if it's unsupported by this UPS." ::= { upsPhaseInputEntry 4 } upsPhaseInputType OBJECT-TYPE SYNTAX INTEGER { unknown(1), main(2), bypass(3) } ACCESS read-only STATUS mandatory DESCRIPTION "The input type." ::= { upsPhaseInputEntry 5 } upsPhaseInputName OBJECT-TYPE SYNTAX DisplayString ACCESS read-write STATUS mandatory DESCRIPTION "A name given to a particular input." ::= { upsPhaseInputEntry 6 } -- Input Phase Table upsPhaseInputPhaseTable OBJECT-TYPE SYNTAX SEQUENCE OF UpsPhaseInputPhaseEntry ACCESS not-accessible STATUS mandatory DESCRIPTION "A list of input table entries. The number of entries is given by the sum of the upsPhaseNumInputPhases." ::= { upsPhaseInput 3 } upsPhaseInputPhaseEntry OBJECT-TYPE SYNTAX UpsPhaseInputPhaseEntry ACCESS not-accessible STATUS mandatory DESCRIPTION "An entry containing information applicable to a particular input phase." INDEX { upsPhaseInputPhaseTableIndex, upsPhaseInputPhaseIndex } ::= { upsPhaseInputPhaseTable 1 } UpsPhaseInputPhaseEntry ::= SEQUENCE { upsPhaseInputPhaseTableIndex INTEGER, upsPhaseInputPhaseIndex INTEGER, upsPhaseInputVoltage INTEGER, upsPhaseInputMaxVoltage INTEGER, upsPhaseInputMinVoltage INTEGER, upsPhaseInputCurrent INTEGER, upsPhaseInputMaxCurrent INTEGER, upsPhaseInputMinCurrent INTEGER, upsPhaseInputPower INTEGER, upsPhaseInputMaxPower INTEGER, upsPhaseInputMinPower INTEGER } upsPhaseInputPhaseTableIndex OBJECT-TYPE SYNTAX INTEGER ACCESS read-only STATUS mandatory DESCRIPTION "The input identifier." ::= { upsPhaseInputPhaseEntry 1 } upsPhaseInputPhaseIndex OBJECT-TYPE SYNTAX INTEGER ACCESS read-only STATUS mandatory DESCRIPTION "The input phase identifier." ::= { upsPhaseInputPhaseEntry 2 } upsPhaseInputVoltage OBJECT-TYPE SYNTAX INTEGER ACCESS read-only STATUS mandatory DESCRIPTION "The input voltage in VAC, or -1 if it's unsupported by this UPS." ::= { upsPhaseInputPhaseEntry 3 } upsPhaseInputMaxVoltage OBJECT-TYPE SYNTAX INTEGER ACCESS read-only STATUS mandatory DESCRIPTION "The maximum input voltage in VAC measured since the last reset (upsPhaseResetMaxMinValues), or -1 if it's unsupported by this UPS. Sampled every 30 seconds." ::= { upsPhaseInputPhaseEntry 4 } upsPhaseInputMinVoltage OBJECT-TYPE SYNTAX INTEGER ACCESS read-only STATUS mandatory DESCRIPTION "The minimum input voltage in VAC measured since the last reset (upsPhaseResetMaxMinValues), or -1 if it's unsupported by this UPS. Sampled every 30 seconds." ::= { upsPhaseInputPhaseEntry 5 } upsPhaseInputCurrent OBJECT-TYPE SYNTAX INTEGER ACCESS read-only STATUS mandatory DESCRIPTION "The input current in 0.1 amperes, or -1 if it's unsupported by this UPS." ::= { upsPhaseInputPhaseEntry 6 } upsPhaseInputMaxCurrent OBJECT-TYPE SYNTAX INTEGER ACCESS read-only STATUS mandatory DESCRIPTION "The maximum input current in 0.1 amperes measured since the last reset (upsPhaseResetMaxMinValues), or -1 if it's unsupported by this UPS. Sampled every 30 seconds." ::= { upsPhaseInputPhaseEntry 7 } upsPhaseInputMinCurrent OBJECT-TYPE SYNTAX INTEGER ACCESS read-only STATUS mandatory DESCRIPTION "The minimum input current in 0.1 amperes measured since the last reset (upsPhaseResetMaxMinValues), or -1 if it's unsupported by this UPS. Sampled every 30 seconds." ::= { upsPhaseInputPhaseEntry 8 } upsPhaseInputPower OBJECT-TYPE SYNTAX INTEGER ACCESS read-only STATUS mandatory DESCRIPTION "The input power in Watts, or -1 if it's unsupported by this UPS." ::= { upsPhaseInputPhaseEntry 9 } upsPhaseInputMaxPower OBJECT-TYPE SYNTAX INTEGER ACCESS read-only STATUS mandatory DESCRIPTION "The maximum input power in Watts measured since the last reset (upsPhaseResetMaxMinValues), or -1 if it's unsupported by this UPS. Sampled every 30 seconds." ::= { upsPhaseInputPhaseEntry 10 } upsPhaseInputMinPower OBJECT-TYPE SYNTAX INTEGER ACCESS read-only STATUS mandatory DESCRIPTION "The minimum input power in Watts measured since the last reset (upsPhaseResetMaxMinValues), or -1 if it's unsupported by this UPS. Sampled every 30 seconds." ::= { upsPhaseInputPhaseEntry 11 } -- -- The Output group. -- -- Number of Outputs upsPhaseNumOutputs OBJECT-TYPE SYNTAX INTEGER ACCESS read-only STATUS mandatory DESCRIPTION "The number of output feeds to this device. This variable indicates the number of rows in the output table." ::= { upsPhaseOutput 1 } -- Output Table upsPhaseOutputTable OBJECT-TYPE SYNTAX SEQUENCE OF UpsPhaseOutputEntry ACCESS not-accessible STATUS mandatory DESCRIPTION "A list of output table entries. The number of entries is given by the value of upsOutputNumPhases." ::= { upsPhaseOutput 2 } upsPhaseOutputEntry OBJECT-TYPE SYNTAX UpsPhaseOutputEntry ACCESS not-accessible STATUS mandatory DESCRIPTION "An entry containing information applicable to a particular output." INDEX { upsPhaseOutputTableIndex } ::= { upsPhaseOutputTable 1 } UpsPhaseOutputEntry ::= SEQUENCE { upsPhaseOutputTableIndex INTEGER, upsPhaseNumOutputPhases INTEGER, upsPhaseOutputVoltageOrientation INTEGER, upsPhaseOutputFrequency INTEGER } upsPhaseOutputTableIndex OBJECT-TYPE SYNTAX INTEGER ACCESS read-only STATUS mandatory DESCRIPTION "The output identifier." ::= { upsPhaseOutputEntry 1 } upsPhaseNumOutputPhases OBJECT-TYPE SYNTAX INTEGER ACCESS read-only STATUS mandatory DESCRIPTION "The number of output phases utilized in this device. The sum of all the upsPhaseNumOutputPhases variable indicates the number of rows in the output phase table." ::= { upsPhaseOutputEntry 2 } upsPhaseOutputVoltageOrientation OBJECT-TYPE SYNTAX INTEGER { unknown(1), singlePhase(2), splitPhase(3), threePhasePhaseToNeutral(4), threePhasePhaseToPhase(5) } ACCESS read-only STATUS mandatory DESCRIPTION "The output voltage orientation: 1: unknown for this UPS 2: singlePhase - phase 1 voltage is between Phase 1 and Neutral. 3: splitPhase - phase 1 voltage is between Phase 1 and Neutral; phase 2 voltage is between Phase 2 and Neutral; phase 3 voltage is between Phase 1 and Phase2. 4: threePhasePhaseToNeutral - phase 1 voltage is between Phase 1 and Neutral; phase 2 voltage is between Phase 2 and Neutral; phase 3 voltage is between Phase3 and Neutral. 5: threePhasePhaseToPhase - phase 1 voltage is between Phase 1 and Phase 2; phase 2 voltage is between Phase 2 and Phase 3; phase 3 voltage is between Phase 3 and Phase 1." ::= { upsPhaseOutputEntry 3 } upsPhaseOutputFrequency OBJECT-TYPE SYNTAX INTEGER ACCESS read-only STATUS mandatory DESCRIPTION "The output frequency in 0.1 Hertz, or -1 if it's unsupported by this UPS." ::= { upsPhaseOutputEntry 4 } -- Output Phase Table upsPhaseOutputPhaseTable OBJECT-TYPE SYNTAX SEQUENCE OF UpsPhaseOutputPhaseEntry ACCESS not-accessible STATUS mandatory DESCRIPTION "A list of output table entries. The number of entries is given by the sum of the upsPhaseNumOutputPhases." ::= { upsPhaseOutput 3 } upsPhaseOutputPhaseEntry OBJECT-TYPE SYNTAX UpsPhaseOutputPhaseEntry ACCESS not-accessible STATUS mandatory DESCRIPTION "An entry containing information applicable to a particular output phase." INDEX { upsPhaseOutputPhaseTableIndex, upsPhaseOutputPhaseIndex } ::= { upsPhaseOutputPhaseTable 1 } UpsPhaseOutputPhaseEntry ::= SEQUENCE { upsPhaseOutputPhaseTableIndex INTEGER, upsPhaseOutputPhaseIndex INTEGER, upsPhaseOutputVoltage INTEGER, upsPhaseOutputCurrent INTEGER, upsPhaseOutputMaxCurrent INTEGER, upsPhaseOutputMinCurrent INTEGER, upsPhaseOutputLoad INTEGER, upsPhaseOutputMaxLoad INTEGER, upsPhaseOutputMinLoad INTEGER, upsPhaseOutputPercentLoad INTEGER, upsPhaseOutputMaxPercentLoad INTEGER, upsPhaseOutputMinPercentLoad INTEGER, upsPhaseOutputPower INTEGER, upsPhaseOutputMaxPower INTEGER, upsPhaseOutputMinPower INTEGER, upsPhaseOutputPercentPower INTEGER, upsPhaseOutputMaxPercentPower INTEGER, upsPhaseOutputMinPercentPower INTEGER } upsPhaseOutputPhaseTableIndex OBJECT-TYPE SYNTAX INTEGER ACCESS read-only STATUS mandatory DESCRIPTION "The output identifier." ::= { upsPhaseOutputPhaseEntry 1 } upsPhaseOutputPhaseIndex OBJECT-TYPE SYNTAX INTEGER ACCESS read-only STATUS mandatory DESCRIPTION "The output phase identifier." ::= { upsPhaseOutputPhaseEntry 2 } upsPhaseOutputVoltage OBJECT-TYPE SYNTAX INTEGER ACCESS read-only STATUS mandatory DESCRIPTION "The output voltage in VAC, or -1 if it's unsupported by this UPS." ::= { upsPhaseOutputPhaseEntry 3 } upsPhaseOutputCurrent OBJECT-TYPE SYNTAX INTEGER ACCESS read-only STATUS mandatory DESCRIPTION "The output current in 0.1 amperes drawn by the load on the UPS, or -1 if it's unsupported by this UPS." ::= { upsPhaseOutputPhaseEntry 4 } upsPhaseOutputMaxCurrent OBJECT-TYPE SYNTAX INTEGER ACCESS read-only STATUS mandatory DESCRIPTION "The maximum output current in 0.1 amperes measured since the last reset (upsPhaseResetMaxMinValues), or -1 if it's unsupported by this UPS. Sampled every 30 seconds." ::= { upsPhaseOutputPhaseEntry 5 } upsPhaseOutputMinCurrent OBJECT-TYPE SYNTAX INTEGER ACCESS read-only STATUS mandatory DESCRIPTION "The minimum output current in 0.1 amperes measured since the last reset (upsPhaseResetMaxMinValues), or -1 if it's unsupported by this UPS. Sampled every 30 seconds." ::= { upsPhaseOutputPhaseEntry 6 } upsPhaseOutputLoad OBJECT-TYPE SYNTAX INTEGER ACCESS read-only STATUS mandatory DESCRIPTION "The output load in VA, or -1 if it's unsupported by this UPS." ::= { upsPhaseOutputPhaseEntry 7 } upsPhaseOutputMaxLoad OBJECT-TYPE SYNTAX INTEGER ACCESS read-only STATUS mandatory DESCRIPTION "The maximum output load in VA measured since the last reset (upsPhaseResetMaxMinValues), or -1 if it's unsupported by this UPS. Sampled every 30 seconds." ::= { upsPhaseOutputPhaseEntry 8 } upsPhaseOutputMinLoad OBJECT-TYPE SYNTAX INTEGER ACCESS read-only STATUS mandatory DESCRIPTION "The minimum output load in VA measured since the last reset (upsPhaseResetMaxMinValues), or -1 if it's unsupported by this UPS. Sampled every 30 seconds." ::= { upsPhaseOutputPhaseEntry 9 } upsPhaseOutputPercentLoad OBJECT-TYPE SYNTAX INTEGER ACCESS read-only STATUS mandatory DESCRIPTION "The percentage of the UPS load capacity in VA at redundancy @ (n + x) presently being used on this output phase, or -1 if it's unsupported by this UPS." ::= { upsPhaseOutputPhaseEntry 10 } upsPhaseOutputMaxPercentLoad OBJECT-TYPE SYNTAX INTEGER ACCESS read-only STATUS mandatory DESCRIPTION "The maximum percentage of the UPS load capacity in VA measured at redundancy @ (n + x) presently being used on this output phase since the last reset (upsPhaseResetMaxMinValues), or -1 if it's unsupported by this UPS. Sampled every 30 seconds." ::= { upsPhaseOutputPhaseEntry 11 } upsPhaseOutputMinPercentLoad OBJECT-TYPE SYNTAX INTEGER ACCESS read-only STATUS mandatory DESCRIPTION "The minimum percentage of the UPS load capacity in VA measured at redundancy @ (n + x) presently being used on this output phase since the last reset (upsPhaseResetMaxMinValues), or -1 if it's unsupported by this UPS. Sampled every 30 seconds." ::= { upsPhaseOutputPhaseEntry 12 } upsPhaseOutputPower OBJECT-TYPE SYNTAX INTEGER ACCESS read-only STATUS mandatory DESCRIPTION "The output power in Watts, or -1 if it's unsupported by this UPS." ::= { upsPhaseOutputPhaseEntry 13 } upsPhaseOutputMaxPower OBJECT-TYPE SYNTAX INTEGER ACCESS read-only STATUS mandatory DESCRIPTION "The maximum output power in Watts measured since the last reset (upsPhaseResetMaxMinValues), or -1 if it's unsupported by this UPS. Sampled every 30 seconds." ::= { upsPhaseOutputPhaseEntry 14 } upsPhaseOutputMinPower OBJECT-TYPE SYNTAX INTEGER ACCESS read-only STATUS mandatory DESCRIPTION "The minimum output power in Watts measured since the last reset (upsPhaseResetMaxMinValues), or -1 if it's unsupported by this UPS. Sampled every 30 seconds." ::= { upsPhaseOutputPhaseEntry 15 } upsPhaseOutputPercentPower OBJECT-TYPE SYNTAX INTEGER ACCESS read-only STATUS mandatory DESCRIPTION "The percentage of the UPS power capacity in Watts at redundancy @ (n + x) presently being used on this output phase, or -1 if it's unsupported by this UPS." ::= { upsPhaseOutputPhaseEntry 16 } upsPhaseOutputMaxPercentPower OBJECT-TYPE SYNTAX INTEGER ACCESS read-only STATUS mandatory DESCRIPTION "The maximum percentage of the UPS power capacity in Watts measured at redundancy @ (n + x) presently being used on this output phase since the last reset (upsPhaseResetMaxMinValues), or -1 if it's unsupported by this UPS. Sampled every 30 seconds." ::= { upsPhaseOutputPhaseEntry 17 } upsPhaseOutputMinPercentPower OBJECT-TYPE SYNTAX INTEGER ACCESS read-only STATUS mandatory DESCRIPTION "The maximum percentage of the UPS power capacity in Watts measured at redundancy @ (n + x) presently being used on this output phase since the last reset (upsPhaseResetMaxMinValues), or -1 if it's unsupported by this UPS. Sampled every 30 seconds." ::= { upsPhaseOutputPhaseEntry 18 } -- the upsOutletGroupStatus group upsOutletGroupStatusTableSize OBJECT-TYPE SYNTAX INTEGER ACCESS read-only STATUS mandatory DESCRIPTION "The number of outlet groups for the UPS." ::= { upsOutletGroupStatus 1 } upsOutletGroupStatusTable OBJECT-TYPE SYNTAX SEQUENCE OF UpsOutletGroupStatusEntry ACCESS not-accessible STATUS mandatory DESCRIPTION "Allows for getting status of the outlet groups. The number of entries is contained in the upsOutletGroupStatusTableSize OID." ::= { upsOutletGroupStatus 2 } upsOutletGroupStatusEntry OBJECT-TYPE SYNTAX UpsOutletGroupStatusEntry ACCESS not-accessible STATUS mandatory DESCRIPTION "The outlet group status to get." INDEX { upsOutletGroupStatusIndex} ::= { upsOutletGroupStatusTable 1 } UpsOutletGroupStatusEntry ::= SEQUENCE { upsOutletGroupStatusIndex INTEGER, upsOutletGroupStatusName DisplayString, upsOutletGroupStatusGroupState INTEGER, upsOutletGroupStatusCommandPending INTEGER } upsOutletGroupStatusIndex OBJECT-TYPE SYNTAX INTEGER ACCESS read-only STATUS mandatory DESCRIPTION "The index to the outlet group entry." ::= { upsOutletGroupStatusEntry 1 } upsOutletGroupStatusName OBJECT-TYPE SYNTAX DisplayString ACCESS read-only STATUS mandatory DESCRIPTION "The name of the outlet group. This OID is provided for informational purposes only. This value is set by the upsOutletGroupConfigName OID." ::= { upsOutletGroupStatusEntry 2 } upsOutletGroupStatusGroupState OBJECT-TYPE SYNTAX INTEGER { upsOutletGroupStatusOn (1), upsOutletGroupStatusOff (2), upsOutletGroupStatusUnknown (3) } ACCESS read-only STATUS mandatory DESCRIPTION "Getting this variable will return the outlet group state. If the outlet group is on, the upsOutletGroupStatusOn (1) value will be returned. If the outlet group is off, the upsOutletGroupStatusOff (2) value will be returned. If the state of the outlet group cannot be determined, the upsOutletGroupStatusUnknown (3) value will be returned." ::= { upsOutletGroupStatusEntry 3 } upsOutletGroupStatusCommandPending OBJECT-TYPE SYNTAX INTEGER { upsOutletGroupCommandPending (1), upsOutletGroupNoCommandPending (2) } ACCESS read-only STATUS mandatory DESCRIPTION "Getting this variable will return the command pending state of the outlet group. If a command is pending on the outlet group, the upsOutletGroupCommandPending (1) value will be returned. If there is not a command pending on the outlet group, the upsOutletGroupNoCommandPending (2) will be returned." ::= { upsOutletGroupStatusEntry 4 } -- the upsOutletGroupConfig group upsOutletGroupConfigTableSize OBJECT-TYPE SYNTAX INTEGER ACCESS read-only STATUS mandatory DESCRIPTION "The number of outlet groups for the UPS." ::= { upsOutletGroupConfig 1 } upsOutletGroupConfigTable OBJECT-TYPE SYNTAX SEQUENCE OF UpsOutletGroupConfigEntry ACCESS not-accessible STATUS mandatory DESCRIPTION "The list of outlet groups to configure. The number of entries is defined by the upsOutletGroupConfigTableSize OID." ::= { upsOutletGroupConfig 2 } upsOutletGroupConfigEntry OBJECT-TYPE SYNTAX UpsOutletGroupConfigEntry ACCESS not-accessible STATUS mandatory DESCRIPTION "The outlet groups to configure." INDEX { upsOutletGroupConfigIndex} ::= { upsOutletGroupConfigTable 1 } UpsOutletGroupConfigEntry ::= SEQUENCE { upsOutletGroupConfigIndex INTEGER, upsOutletGroupConfigName DisplayString, upsOutletGroupConfigPowerOnDelay INTEGER, upsOutletGroupConfigPowerOffDelay INTEGER, upsOutletGroupConfigRebootDuration INTEGER } upsOutletGroupConfigIndex OBJECT-TYPE SYNTAX INTEGER ACCESS read-only STATUS mandatory DESCRIPTION "The index to the outlet group entry." ::= { upsOutletGroupConfigEntry 1 } upsOutletGroupConfigName OBJECT-TYPE SYNTAX DisplayString ACCESS read-write STATUS mandatory DESCRIPTION "The name of the outlet group." ::= { upsOutletGroupConfigEntry 2 } upsOutletGroupConfigPowerOnDelay OBJECT-TYPE SYNTAX INTEGER ACCESS read-write STATUS mandatory DESCRIPTION "The amount of time (in seconds) the outlet group will delay powering on when the delayed on or reboot command is applied. Allowed values are -1 (for Never) or 0 to 600 seconds." ::= { upsOutletGroupConfigEntry 3 } upsOutletGroupConfigPowerOffDelay OBJECT-TYPE SYNTAX INTEGER ACCESS read-write STATUS mandatory DESCRIPTION "The amount of time (in seconds) the outlet group will delay powering off when the delayed off command is applied. Allowed values are 0 to 600 seconds." ::= { upsOutletGroupConfigEntry 4 } upsOutletGroupConfigRebootDuration OBJECT-TYPE SYNTAX INTEGER ACCESS read-write STATUS mandatory DESCRIPTION "During a reboot sequence, power is turned off and then back on. This OID defines the amount of time to wait, in seconds, after turning the power off, at the start of the sequence, before initiating the power on sequence. Allowed values are 0 to 600 seconds." ::= { upsOutletGroupConfigEntry 5 } -- the upsOutletGroupControl group upsOutletGroupControlTableSize OBJECT-TYPE SYNTAX INTEGER ACCESS read-only STATUS mandatory DESCRIPTION "The number of outlet groups for the UPS." ::= { upsOutletGroupControl 1 } upsOutletGroupControlTable OBJECT-TYPE SYNTAX SEQUENCE OF UpsOutletGroupControlEntry ACCESS not-accessible STATUS mandatory DESCRIPTION "Allows for control of individual outlet groups. The number of entries is contained in the upsOutletGroupControlTableSize OID." ::= { upsOutletGroupControl 2 } upsOutletGroupControlEntry OBJECT-TYPE SYNTAX UpsOutletGroupControlEntry ACCESS not-accessible STATUS mandatory DESCRIPTION "The outlet group to control." INDEX { upsOutletGroupControlIndex} ::= { upsOutletGroupControlTable 1 } UpsOutletGroupControlEntry ::= SEQUENCE { upsOutletGroupControlIndex INTEGER, upsOutletGroupControlName DisplayString, upsOutletGroupControlCommand INTEGER } upsOutletGroupControlIndex OBJECT-TYPE SYNTAX INTEGER ACCESS read-only STATUS mandatory DESCRIPTION "The index to the outlet group entry." ::= { upsOutletGroupControlEntry 1 } upsOutletGroupControlName OBJECT-TYPE SYNTAX DisplayString ACCESS read-only STATUS mandatory DESCRIPTION "The name of the outlet group. This OID is provided for informational purposes only. This value is set by the upsOutletGroupConfigName OID." ::= { upsOutletGroupControlEntry 2 } upsOutletGroupControlCommand OBJECT-TYPE SYNTAX INTEGER { upsOutletGroupImmediateOn (1), upsOutletGroupImmediateOff (2), upsOutletGroupImmediateReboot (3), upsOutletGroupDelayedOn (4), upsOutletGroupDelayedOff (5), upsOutletGroupDelayedReboot (6), upsOutletGroupCancelPendingCommand (7), upsOutletGroupControlUnknown (8) } ACCESS read-write STATUS mandatory DESCRIPTION "Getting this variable will return the outlet group state. If the outlet group is on, the upsOutletGroupImmediateOn (1) value will be returned. If the outlet group is off, the upsOutletGroupImmediateOff (2) value will be returned. If the state of the outlet group cannot be determined, the upsOutletGroupControlUnknown (8) value will be returned. Setting this variable to upsOutletGroupImmediateOn (1) will turn the outlet group on. Setting this variable to upsOutletGroupImmediateOff (2) will turn the outlet group off. Setting this variable to upsOutletGroupImmediateReboot (3) will turn the outlet group off, wait the upsOutletGroupConfigRebootDuration OID time, wait the upsOutletGroupConfigPowerOnDelay OID, and then turn the outlet group on. Setting this variable to upsOutletGroupDelayedOn (4) will turn the outlet group on after the upsOutletGroupConfigPowerOnDelay OID has elapsed. Setting this variable to upsOutletGroupDelayedOff (5) will turn the outlet group off after the upsOutletGroupConfigPowerOffDelay OID has elapsed. Setting this variable to upsOutletGroupDelayedReboot (6) will turn the outlet group off after the upsOutletGroupConfigPowerOffDelay OID has elapsed, wait the upsOutletGroupConfigRebootDuration OID time, wait the upsOutletGroupConfigPowerOnDelay OID, and then turn the outlet group on. Setting this variable to upsOutletGroupCancelPendingCommand (7) will cause any pending command to this outlet group to be canceled." ::= { upsOutletGroupControlEntry 3 } -- the upsDiagnosticIM group upsDiagIMTableSize OBJECT-TYPE SYNTAX INTEGER ACCESS read-only STATUS mandatory DESCRIPTION "The number of Intelligence Modules in or attached to the UPS." ::= { upsDiagnosticIM 1 } upsDiagIMTable OBJECT-TYPE SYNTAX SEQUENCE OF UpsDiagIMEntry ACCESS not-accessible STATUS mandatory DESCRIPTION "Allows for diagnostics of individual Intelligence Modules. The number of entries is contained in the upsDiagIMTableSize OID." ::= { upsDiagnosticIM 2 } upsDiagIMEntry OBJECT-TYPE SYNTAX UpsDiagIMEntry ACCESS not-accessible STATUS mandatory DESCRIPTION "The diagnostics and information of an Intelligence Module." INDEX { upsDiagIMIndex} ::= { upsDiagIMTable 1 } UpsDiagIMEntry ::= SEQUENCE { upsDiagIMIndex INTEGER, upsDiagIMType INTEGER, upsDiagIMStatus INTEGER, upsDiagIMFirmwareRev DisplayString, upsDiagIMSlaveFirmwareRev DisplayString, upsDiagIMHardwareRev DisplayString, upsDiagIMSerialNum DisplayString, upsDiagIMManufactureDate DisplayString } upsDiagIMIndex OBJECT-TYPE SYNTAX INTEGER ACCESS read-only STATUS mandatory DESCRIPTION "The index to the Intelligence Module entry." ::= { upsDiagIMEntry 1 } upsDiagIMType OBJECT-TYPE SYNTAX INTEGER { imUnknown (1), imMIM (2), imRIM (3) } ACCESS read-only STATUS mandatory DESCRIPTION "The type of the Intelligence Module. imUnknown(1) indicates the IM type is unknown. imMIM(2) indicates the IM type is a Main Intelligence Module. imRIM(3) indicates the IM type is Redundant Intelligence Module." ::= { upsDiagIMEntry 2 } upsDiagIMStatus OBJECT-TYPE SYNTAX INTEGER { unknown (1), notInstalled (2), offOk (3), onOk (4), offFail (5), onFail (6), lostComm (7) } ACCESS read-only STATUS mandatory DESCRIPTION "The status of the Intelligence Module. unknown(1) indicates the device status is unknown. notInstalled(2) indicates the device is not installed. offOk(3) indicates the device status is off and OK. onOk(4) indicates the device status is on and OK. offFail(5) indicates the device status is off and failed. onFail(6) indicates the device status is on and failed. lostComm(7) indicates the device has lost communication." ::= { upsDiagIMEntry 3 } upsDiagIMFirmwareRev OBJECT-TYPE SYNTAX DisplayString ACCESS read-only STATUS mandatory DESCRIPTION "The firmware revision of the Intelligence Module." ::= { upsDiagIMEntry 4 } upsDiagIMSlaveFirmwareRev OBJECT-TYPE SYNTAX DisplayString ACCESS read-only STATUS mandatory DESCRIPTION "The slave firmware revision of the Intelligence Module." ::= { upsDiagIMEntry 5 } upsDiagIMHardwareRev OBJECT-TYPE SYNTAX DisplayString ACCESS read-only STATUS mandatory DESCRIPTION "The hardware revision of the Intelligence Module." ::= { upsDiagIMEntry 6 } upsDiagIMSerialNum OBJECT-TYPE SYNTAX DisplayString ACCESS read-only STATUS mandatory DESCRIPTION "The serial number of the Intelligence Module." ::= { upsDiagIMEntry 7 } upsDiagIMManufactureDate OBJECT-TYPE SYNTAX DisplayString ACCESS read-only STATUS mandatory DESCRIPTION "The manufacture date of the Intelligence Module." ::= { upsDiagIMEntry 8 } -- the upsDiagnosticPowerModules group upsDiagPMTableSize OBJECT-TYPE SYNTAX INTEGER ACCESS read-only STATUS mandatory DESCRIPTION "The number of Power Modules in or attached to the UPS." ::= { upsDiagnosticPowerModules 1 } upsDiagPMTable OBJECT-TYPE SYNTAX SEQUENCE OF UpsDiagPMEntry ACCESS not-accessible STATUS mandatory DESCRIPTION "Allows for diagnostics of Individual Power modules. The number of entries is contained in the upsDiagPMTableSize OID." ::= { upsDiagnosticPowerModules 2 } upsDiagPMEntry OBJECT-TYPE SYNTAX UpsDiagPMEntry ACCESS not-accessible STATUS mandatory DESCRIPTION "The diagnostics of an Power Module." INDEX { upsDiagPMIndex} ::= { upsDiagPMTable 1 } UpsDiagPMEntry ::= SEQUENCE { upsDiagPMIndex INTEGER, upsDiagPMStatus INTEGER, upsDiagPMFirmwareRev DisplayString, upsDiagPMHardwareRev DisplayString, upsDiagPMSerialNum DisplayString, upsDiagPMManufactureDate DisplayString } upsDiagPMIndex OBJECT-TYPE SYNTAX INTEGER ACCESS read-only STATUS mandatory DESCRIPTION "The index to the Power Module entry." ::= { upsDiagPMEntry 1 } upsDiagPMStatus OBJECT-TYPE SYNTAX INTEGER { unknown (1), notInstalled (2), offOk (3), onOk (4), offFail (5), onFail (6), lostComm (7) } ACCESS read-only STATUS mandatory DESCRIPTION "The status of the Power Module. unknown(1) indicates the device status is unknown. notInstalled(2) indicates the device is not installed. offOk(3) indicates the device status is off and OK. onOk(4) indicates the device status is on and OK. offFail(5) indicates the device status is off and failed. onFail(6) indicates the device status is on and failed. lostComm(7) indicates the device has lost communication." ::= { upsDiagPMEntry 2 } upsDiagPMFirmwareRev OBJECT-TYPE SYNTAX DisplayString ACCESS read-only STATUS mandatory DESCRIPTION "The firmware revision of the Power Module." ::= { upsDiagPMEntry 3 } upsDiagPMHardwareRev OBJECT-TYPE SYNTAX DisplayString ACCESS read-only STATUS mandatory DESCRIPTION "The hardware revision of the Power Module." ::= { upsDiagPMEntry 4 } upsDiagPMSerialNum OBJECT-TYPE SYNTAX DisplayString ACCESS read-only STATUS mandatory DESCRIPTION "The serial number of the Power Module." ::= { upsDiagPMEntry 5 } upsDiagPMManufactureDate OBJECT-TYPE SYNTAX DisplayString ACCESS read-only STATUS mandatory DESCRIPTION "The manufacture date of the Power Module." ::= { upsDiagPMEntry 6 } -- the upsDiagnosticBatteries group upsDiagBatteryTableSize OBJECT-TYPE SYNTAX INTEGER ACCESS read-only STATUS mandatory DESCRIPTION "The number of batteries in or attached to the UPS." ::= { upsDiagnosticBatteries 1 } upsDiagBatteryTable OBJECT-TYPE SYNTAX SEQUENCE OF UpsDiagBatteryEntry ACCESS not-accessible STATUS mandatory DESCRIPTION "Allows for diagnostics of individual batteries. The number of entries is contained in the upsDiagBattTableSize OID." ::= { upsDiagnosticBatteries 2 } upsDiagBatteryEntry OBJECT-TYPE SYNTAX UpsDiagBatteryEntry ACCESS not-accessible STATUS mandatory DESCRIPTION "The diagnostics of a battery." INDEX { upsDiagBatteryIndex} ::= { upsDiagBatteryTable 1 } UpsDiagBatteryEntry ::= SEQUENCE { upsDiagBatteryFrameIndex INTEGER, upsDiagBatteryIndex INTEGER, upsDiagBatteryStatus INTEGER, upsDiagBatterySerialNumber DisplayString, upsDiagBatteryFirmwareRev DisplayString, upsDiagBatteryManufactureDate DisplayString, upsDiagBatteryType DisplayString } upsDiagBatteryFrameIndex OBJECT-TYPE SYNTAX INTEGER ACCESS read-only STATUS mandatory DESCRIPTION "The index to the battery frame entry. Frame 0 indicates the Main frame. Extended Run (XR) frames start from index 1." ::= { upsDiagBatteryEntry 1 } upsDiagBatteryIndex OBJECT-TYPE SYNTAX INTEGER ACCESS read-only STATUS mandatory DESCRIPTION "The index to the battery entry." ::= { upsDiagBatteryEntry 2 } upsDiagBatteryStatus OBJECT-TYPE SYNTAX INTEGER { unknown (1), notInstalled (2), ok (3), failed (4), highTemperature (5), replaceImmediately (6), lowCapacity (7) } ACCESS read-only STATUS mandatory DESCRIPTION "The status of the battery. unknown(1) indicates the device status is unknown. notInstalled(2) indicates the device is not installed. ok(3) indicates the battery status is OK. failed(4) indicates the battery status is failed. highTemperature(5) indicates the battery has a high temperature condition. replaceImmediately(6) indicates the battery must be replaced immediately. lowCapacity(7) indicates the battery has a low capacity." ::= { upsDiagBatteryEntry 3 } upsDiagBatterySerialNumber OBJECT-TYPE SYNTAX DisplayString ACCESS read-only STATUS mandatory DESCRIPTION "The serial number of the battery." ::= { upsDiagBatteryEntry 4 } upsDiagBatteryFirmwareRev OBJECT-TYPE SYNTAX DisplayString ACCESS read-only STATUS mandatory DESCRIPTION "The firmware revision of the battery." ::= { upsDiagBatteryEntry 5 } upsDiagBatteryManufactureDate OBJECT-TYPE SYNTAX DisplayString ACCESS read-only STATUS mandatory DESCRIPTION "The manufacture date of the battery." ::= { upsDiagBatteryEntry 6 } upsDiagBatteryType OBJECT-TYPE SYNTAX DisplayString ACCESS read-only STATUS mandatory DESCRIPTION "The battery type or rating for the battery." ::= { upsDiagBatteryEntry 7 } -- the upsDiagnosticSubsystem group upsDiagSubSysFrameTableSize OBJECT-TYPE SYNTAX INTEGER ACCESS read-only STATUS mandatory DESCRIPTION "The number of frames attached to the UPS including the Main frame." ::= { upsDiagnosticSubsystem 1 } upsDiagSubSysFrameTable OBJECT-TYPE SYNTAX SEQUENCE OF UpsDiagSubSysFrameEntry ACCESS not-accessible STATUS mandatory DESCRIPTION "Allows for diagnostics of individual XR Frames." ::= { upsDiagnosticSubsystem 2 } upsDiagSubSysFrameEntry OBJECT-TYPE SYNTAX UpsDiagSubSysFrameEntry ACCESS not-accessible STATUS mandatory DESCRIPTION "The diagnostics of an XR Frame." INDEX { upsDiagSubSysFrameIndex} ::= { upsDiagSubSysFrameTable 1 } UpsDiagSubSysFrameEntry ::= SEQUENCE { upsDiagSubSysFrameIndex INTEGER, upsDiagSubSysFrameType INTEGER, upsDiagSubSysFrameFirmwareRev DisplayString, upsDiagSubSysFrameHardwareRev DisplayString, upsDiagSubSysFrameSerialNum DisplayString, upsDiagSubSysFrameManufactureDate DisplayString } upsDiagSubSysFrameIndex OBJECT-TYPE SYNTAX INTEGER ACCESS read-only STATUS mandatory DESCRIPTION "The frame index entry." ::= { upsDiagSubSysFrameEntry 1 } upsDiagSubSysFrameType OBJECT-TYPE SYNTAX INTEGER { unknown (1), notInstalled (2), frameTypeMain (3), frameTypeXR (4), frameTypeLXR (5) } ACCESS read-only STATUS mandatory DESCRIPTION "The type of Frame. unknown(1) indicates the device status is unknown. notInstalled(2) indicates the device is not installed. frameTypeMain(3) indicates the the frame type is the Main Frame. frameTypeXR(4) indicates the frame type is an XR Frame. frameTypeLXR(5) indicates the frame type is an LXR Frame." ::= { upsDiagSubSysFrameEntry 2 } upsDiagSubSysFrameFirmwareRev OBJECT-TYPE SYNTAX DisplayString ACCESS read-only STATUS mandatory DESCRIPTION "The firmware revision of the frame." ::= { upsDiagSubSysFrameEntry 3 } upsDiagSubSysFrameHardwareRev OBJECT-TYPE SYNTAX DisplayString ACCESS read-only STATUS mandatory DESCRIPTION "The hardware revision of the frame." ::= { upsDiagSubSysFrameEntry 4 } upsDiagSubSysFrameSerialNum OBJECT-TYPE SYNTAX DisplayString ACCESS read-only STATUS mandatory DESCRIPTION "The serial number of the frame." ::= { upsDiagSubSysFrameEntry 5 } upsDiagSubSysFrameManufactureDate OBJECT-TYPE SYNTAX DisplayString ACCESS read-only STATUS mandatory DESCRIPTION "The manufacture date of the frame." ::= { upsDiagSubSysFrameEntry 6 } upsDiagSubSysIntBypSwitchTableSize OBJECT-TYPE SYNTAX INTEGER ACCESS read-only STATUS mandatory DESCRIPTION "The number of Internal Bypass switches attached to the UPS." ::= { upsDiagnosticSubsystem 3 } upsDiagSubSysIntBypSwitchTable OBJECT-TYPE SYNTAX SEQUENCE OF UpsDiagSubSysIntBypSwitchEntry ACCESS not-accessible STATUS mandatory DESCRIPTION "Allows for diagnostics of the Internal Bypass Switch." ::= { upsDiagnosticSubsystem 4 } upsDiagSubSysIntBypSwitchEntry OBJECT-TYPE SYNTAX UpsDiagSubSysIntBypSwitchEntry ACCESS not-accessible STATUS mandatory DESCRIPTION "The diagnostics of the Internal Bypass Switch." INDEX { upsDiagSubSysIntBypSwitchIndex} ::= { upsDiagSubSysIntBypSwitchTable 1 } UpsDiagSubSysIntBypSwitchEntry ::= SEQUENCE { upsDiagSubSysIntBypSwitchFrameIndex INTEGER, upsDiagSubSysIntBypSwitchIndex INTEGER, upsDiagSubSysIntBypSwitchStatus INTEGER, upsDiagSubSysIntBypSwitchFirmwareRev DisplayString, upsDiagSubSysIntBypSwitchHardwareRev DisplayString, upsDiagSubSysIntBypSwitchSerialNum DisplayString, upsDiagSubSysIntBypSwitchManufactureDate DisplayString } upsDiagSubSysIntBypSwitchFrameIndex OBJECT-TYPE SYNTAX INTEGER ACCESS read-only STATUS mandatory DESCRIPTION "The frame index entry." ::= { upsDiagSubSysIntBypSwitchEntry 1 } upsDiagSubSysIntBypSwitchIndex OBJECT-TYPE SYNTAX INTEGER ACCESS read-only STATUS mandatory DESCRIPTION "The Internal Bypass Switch index entry." ::= { upsDiagSubSysIntBypSwitchEntry 2 } upsDiagSubSysIntBypSwitchStatus OBJECT-TYPE SYNTAX INTEGER { unknown (1), notInstalled (2), offOk (3), onOk (4), offFail (5), onFail (6), lostComm (7) } ACCESS read-only STATUS mandatory DESCRIPTION "The Internal Bypass Switch status. unknown(1) indicates the device status is unknown. notInstalled(2) indicates the device is not installed. offOk(3) indicates the device status is off and OK. onOk(4) indicates the device status is on and OK. offFail(5) indicates the device status is off and failed. onFail(6) indicates the device status is on and failed. lostComm(7) indicates the device has lost communication." ::= { upsDiagSubSysIntBypSwitchEntry 3 } upsDiagSubSysIntBypSwitchFirmwareRev OBJECT-TYPE SYNTAX DisplayString ACCESS read-only STATUS mandatory DESCRIPTION "The firmware revision of the Internal Bypass Switch." ::= { upsDiagSubSysIntBypSwitchEntry 4 } upsDiagSubSysIntBypSwitchHardwareRev OBJECT-TYPE SYNTAX DisplayString ACCESS read-only STATUS mandatory DESCRIPTION "The hardware revision of the Internal Bypass Switch." ::= { upsDiagSubSysIntBypSwitchEntry 5 } upsDiagSubSysIntBypSwitchSerialNum OBJECT-TYPE SYNTAX DisplayString ACCESS read-only STATUS mandatory DESCRIPTION "The serial number of the Internal Bypass Switch." ::= { upsDiagSubSysIntBypSwitchEntry 6 } upsDiagSubSysIntBypSwitchManufactureDate OBJECT-TYPE SYNTAX DisplayString ACCESS read-only STATUS mandatory DESCRIPTION "The manufacture date of the Internal Bypass Switch." ::= { upsDiagSubSysIntBypSwitchEntry 7 } upsDiagSubSysBattMonitorTableSize OBJECT-TYPE SYNTAX INTEGER ACCESS read-only STATUS mandatory DESCRIPTION "The number of Battery Monitor Boards attached to the UPS." ::= { upsDiagnosticSubsystem 5 } upsDiagSubSysBattMonitorTable OBJECT-TYPE SYNTAX SEQUENCE OF UpsDiagSubSysBattMonitorEntry ACCESS not-accessible STATUS mandatory DESCRIPTION "Allows for diagnostics of the Battery Monitor Board." ::= { upsDiagnosticSubsystem 6 } upsDiagSubSysBattMonitorEntry OBJECT-TYPE SYNTAX UpsDiagSubSysBattMonitorEntry ACCESS not-accessible STATUS mandatory DESCRIPTION "The diagnostics of the Battery Monitor Board." INDEX { upsDiagSubSysBattMonitorIndex} ::= { upsDiagSubSysBattMonitorTable 1 } UpsDiagSubSysBattMonitorEntry ::= SEQUENCE { upsDiagSubSysBattMonitorFrameIndex INTEGER, upsDiagSubSysBattMonitorIndex INTEGER, upsDiagSubSysBattMonitorStatus INTEGER, upsDiagSubSysBattMonitorFirmwareRev DisplayString, upsDiagSubSysBattMonitorHardwareRev DisplayString, upsDiagSubSysBattMonitorSerialNum DisplayString, upsDiagSubSysBattMonitorManufactureDate DisplayString } upsDiagSubSysBattMonitorFrameIndex OBJECT-TYPE SYNTAX INTEGER ACCESS read-only STATUS mandatory DESCRIPTION "The frame index entry." ::= { upsDiagSubSysBattMonitorEntry 1 } upsDiagSubSysBattMonitorIndex OBJECT-TYPE SYNTAX INTEGER ACCESS read-only STATUS mandatory DESCRIPTION "The index of the Battery Monitor Board." ::= { upsDiagSubSysBattMonitorEntry 2 } upsDiagSubSysBattMonitorStatus OBJECT-TYPE SYNTAX INTEGER { unknown (1), notInstalled (2), offOk (3), onOk (4), offFail (5), onFail (6), lostComm (7) } ACCESS read-only STATUS mandatory DESCRIPTION "The status of the Battery Monitor Board. unknown(1) indicates the device status is unknown. notInstalled(2) indicates the device is not installed. offOk(3) indicates the device status is off and OK. onOk(4) indicates the device status is on and OK. offFail(5) indicates the device status is off and failed. onFail(6) indicates the device status is on and failed. lostComm(7) indicates the device has lost communication." ::= { upsDiagSubSysBattMonitorEntry 3 } upsDiagSubSysBattMonitorFirmwareRev OBJECT-TYPE SYNTAX DisplayString ACCESS read-only STATUS mandatory DESCRIPTION "The firmware revision of the Battery Monitor Board." ::= { upsDiagSubSysBattMonitorEntry 4 } upsDiagSubSysBattMonitorHardwareRev OBJECT-TYPE SYNTAX DisplayString ACCESS read-only STATUS mandatory DESCRIPTION "The hardware revision of the Battery Monitor Board." ::= { upsDiagSubSysBattMonitorEntry 5 } upsDiagSubSysBattMonitorSerialNum OBJECT-TYPE SYNTAX DisplayString ACCESS read-only STATUS mandatory DESCRIPTION "The serial number of the Battery Monitor Board." ::= { upsDiagSubSysBattMonitorEntry 6 } upsDiagSubSysBattMonitorManufactureDate OBJECT-TYPE SYNTAX DisplayString ACCESS read-only STATUS mandatory DESCRIPTION "The date of the manufacture for the Battery Monitor Board." ::= { upsDiagSubSysBattMonitorEntry 7 } upsDiagSubSysExternalSwitchGearTableSize OBJECT-TYPE SYNTAX INTEGER ACCESS read-only STATUS mandatory DESCRIPTION "The number of External Switch Gears attached to the UPS." ::= { upsDiagnosticSubsystem 7 } upsDiagSubSysExternalSwitchGearTable OBJECT-TYPE SYNTAX SEQUENCE OF UpsDiagSubSysExternalSwitchGearEntry ACCESS not-accessible STATUS mandatory DESCRIPTION "Allows for diagnostics of the individual External Switch Gear." ::= { upsDiagnosticSubsystem 8 } upsDiagSubSysExternalSwitchGearEntry OBJECT-TYPE SYNTAX UpsDiagSubSysExternalSwitchGearEntry ACCESS not-accessible STATUS mandatory DESCRIPTION "The diagnostics of an individual External Switch Gear." INDEX { upsDiagSubSysExternalSwitchGearIndex} ::= { upsDiagSubSysExternalSwitchGearTable 1 } UpsDiagSubSysExternalSwitchGearEntry ::= SEQUENCE { upsDiagSubSysExternalSwitchGearFrameIndex INTEGER, upsDiagSubSysExternalSwitchGearIndex INTEGER, upsDiagSubSysExternalSwitchGearStatus INTEGER, upsDiagSubSysExternalSwitchGearFirmwareRev DisplayString, upsDiagSubSysExternalSwitchGearHardwareRev DisplayString, upsDiagSubSysExternalSwitchGearSerialNum DisplayString, upsDiagSubSysExternalSwitchGearManufactureDate DisplayString } upsDiagSubSysExternalSwitchGearFrameIndex OBJECT-TYPE SYNTAX INTEGER ACCESS read-only STATUS mandatory DESCRIPTION "The frame index entry." ::= { upsDiagSubSysExternalSwitchGearEntry 1 } upsDiagSubSysExternalSwitchGearIndex OBJECT-TYPE SYNTAX INTEGER ACCESS read-only STATUS mandatory DESCRIPTION "The index of the External Switch Gear." ::= { upsDiagSubSysExternalSwitchGearEntry 2 } upsDiagSubSysExternalSwitchGearStatus OBJECT-TYPE SYNTAX INTEGER { unknown (1), notInstalled (2), offOk (3), onOk (4), offFail (5), onFail (6), lostComm (7) } ACCESS read-only STATUS mandatory DESCRIPTION "The status of the External Switch Gear. unknown(1) indicates the device status is unknown. notInstalled(2) indicates the device is not installed. offOk(3) indicates the device status is off and OK. onOk(4) indicates the device status is on and OK. offFail(5) indicates the device status is off and failed. onFail(6) indicates the device status is on and failed. lostComm(7) indicates the device has lost communication." ::= { upsDiagSubSysExternalSwitchGearEntry 3 } upsDiagSubSysExternalSwitchGearFirmwareRev OBJECT-TYPE SYNTAX DisplayString ACCESS read-only STATUS mandatory DESCRIPTION "The firmware revision of the External Switch Gear monitor card." ::= { upsDiagSubSysExternalSwitchGearEntry 4 } upsDiagSubSysExternalSwitchGearHardwareRev OBJECT-TYPE SYNTAX DisplayString ACCESS read-only STATUS mandatory DESCRIPTION "The hardware revision of the External Switch Gear monitor card." ::= { upsDiagSubSysExternalSwitchGearEntry 5 } upsDiagSubSysExternalSwitchGearSerialNum OBJECT-TYPE SYNTAX DisplayString ACCESS read-only STATUS mandatory DESCRIPTION "The serial number of the External Switch Gear monitor card." ::= { upsDiagSubSysExternalSwitchGearEntry 6 } upsDiagSubSysExternalSwitchGearManufactureDate OBJECT-TYPE SYNTAX DisplayString ACCESS read-only STATUS mandatory DESCRIPTION "The date of the manufacture for the External Switch Gear monitor card." ::= { upsDiagSubSysExternalSwitchGearEntry 7 } upsDiagSubSysDisplayInterfaceCardTableSize OBJECT-TYPE SYNTAX INTEGER ACCESS read-only STATUS mandatory DESCRIPTION "The number of Display Interface Cards attached to the UPS." ::= { upsDiagnosticSubsystem 9 } upsDiagSubSysDisplayInterfaceCardTable OBJECT-TYPE SYNTAX SEQUENCE OF UpsDiagSubSysDisplayInterfaceCardEntry ACCESS not-accessible STATUS mandatory DESCRIPTION "Allows for diagnostics of individual Display Interface Cards." ::= { upsDiagnosticSubsystem 10 } upsDiagSubSysDisplayInterfaceCardEntry OBJECT-TYPE SYNTAX UpsDiagSubSysDisplayInterfaceCardEntry ACCESS not-accessible STATUS mandatory DESCRIPTION "The diagnostics of a Display Interface Card." INDEX { upsDiagSubSysDisplayInterfaceCardIndex} ::= { upsDiagSubSysDisplayInterfaceCardTable 1 } UpsDiagSubSysDisplayInterfaceCardEntry ::= SEQUENCE { upsDiagSubSysDisplayInterfaceCardFrameIndex INTEGER, upsDiagSubSysDisplayInterfaceCardIndex INTEGER, upsDiagSubSysDisplayInterfaceCardStatus INTEGER } upsDiagSubSysDisplayInterfaceCardFrameIndex OBJECT-TYPE SYNTAX INTEGER ACCESS read-only STATUS mandatory DESCRIPTION "The frame index entry." ::= { upsDiagSubSysDisplayInterfaceCardEntry 1 } upsDiagSubSysDisplayInterfaceCardIndex OBJECT-TYPE SYNTAX INTEGER ACCESS read-only STATUS mandatory DESCRIPTION "The index of the Display Interface Card." ::= { upsDiagSubSysDisplayInterfaceCardEntry 2 } upsDiagSubSysDisplayInterfaceCardStatus OBJECT-TYPE SYNTAX INTEGER { unknown (1), notInstalled (2), offOk (3), onOk (4), offFail (5), onFail (6), lostComm (7) } ACCESS read-only STATUS mandatory DESCRIPTION "The status of the Display Interface Card. unknown(1) indicates the device status is unknown. notInstalled(2) indicates the device is not installed. offOk(3) indicates the device status is off and OK. onOk(4) indicates the device status is on and OK. offFail(5) indicates the device status is off and failed. onFail(6) indicates the device status is on and failed. lostComm(7) indicates the device has lost communication." ::= { upsDiagSubSysDisplayInterfaceCardEntry 3 } upsDiagSubSysDCCircuitBreakerTableSize OBJECT-TYPE SYNTAX INTEGER ACCESS read-only STATUS mandatory DESCRIPTION "The number of DC Circuit Breakers attached to the UPS." ::= { upsDiagnosticSubsystem 11 } upsDiagSubSysDCCircuitBreakerTable OBJECT-TYPE SYNTAX SEQUENCE OF UpsDiagSubSysDCCircuitBreakerEntry ACCESS not-accessible STATUS mandatory DESCRIPTION "Allows for diagnostics of individual DC Circuit Breakers." ::= { upsDiagnosticSubsystem 12 } upsDiagSubSysDCCircuitBreakerEntry OBJECT-TYPE SYNTAX UpsDiagSubSysDCCircuitBreakerEntry ACCESS not-accessible STATUS mandatory DESCRIPTION "The diagnostics of a DC Circuit Breaker." INDEX { upsDiagSubSysDCCircuitBreakerIndex} ::= { upsDiagSubSysDCCircuitBreakerTable 1 } UpsDiagSubSysDCCircuitBreakerEntry ::= SEQUENCE { upsDiagSubSysDCCircuitBreakerFrameIndex INTEGER, upsDiagSubSysDCCircuitBreakerIndex INTEGER, upsDiagSubSysDCCircuitBreakerStatus INTEGER } upsDiagSubSysDCCircuitBreakerFrameIndex OBJECT-TYPE SYNTAX INTEGER ACCESS read-only STATUS mandatory DESCRIPTION "The frame index entry." ::= { upsDiagSubSysDCCircuitBreakerEntry 1 } upsDiagSubSysDCCircuitBreakerIndex OBJECT-TYPE SYNTAX INTEGER ACCESS read-only STATUS mandatory DESCRIPTION "The index of the DC Circuit Breaker." ::= { upsDiagSubSysDCCircuitBreakerEntry 2 } upsDiagSubSysDCCircuitBreakerStatus OBJECT-TYPE SYNTAX INTEGER { unknown (1), notInstalled (2), opened (3), closed (4) } ACCESS read-only STATUS mandatory DESCRIPTION "The status of the DC Circuit Breaker. unknown(1) indicates the circuit breaker status is unknown. notInstalled(2) indicates the circuit breaker is not installed. opened(3) indicates the circuit breaker is opened. closed(4) indicates the circuit breaker is closed." ::= { upsDiagSubSysDCCircuitBreakerEntry 3 } upsDiagSubSysSystemPowerSupplyTableSize OBJECT-TYPE SYNTAX INTEGER ACCESS read-only STATUS mandatory DESCRIPTION "The number of System Power Supplies attached to the UPS." ::= { upsDiagnosticSubsystem 13 } upsDiagSubSysSystemPowerSupplyTable OBJECT-TYPE SYNTAX SEQUENCE OF UpsDiagSubSysSystemPowerSupplyEntry ACCESS not-accessible STATUS mandatory DESCRIPTION "Allows for diagnostics of individual System Power Supplies." ::= { upsDiagnosticSubsystem 14 } upsDiagSubSysSystemPowerSupplyEntry OBJECT-TYPE SYNTAX UpsDiagSubSysSystemPowerSupplyEntry ACCESS not-accessible STATUS mandatory DESCRIPTION "The diagnostics of a System Power Supply." INDEX { upsDiagSubSysSystemPowerSupplyIndex} ::= { upsDiagSubSysSystemPowerSupplyTable 1 } UpsDiagSubSysSystemPowerSupplyEntry ::= SEQUENCE { upsDiagSubSysSystemPowerSupplyFrameIndex INTEGER, upsDiagSubSysSystemPowerSupplyIndex INTEGER, upsDiagSubSysSystemPowerSupplyStatus INTEGER } upsDiagSubSysSystemPowerSupplyFrameIndex OBJECT-TYPE SYNTAX INTEGER ACCESS read-only STATUS mandatory DESCRIPTION "The frame index entry." ::= { upsDiagSubSysSystemPowerSupplyEntry 1 } upsDiagSubSysSystemPowerSupplyIndex OBJECT-TYPE SYNTAX INTEGER ACCESS read-only STATUS mandatory DESCRIPTION "The index of a System Power Supply." ::= { upsDiagSubSysSystemPowerSupplyEntry 2 } upsDiagSubSysSystemPowerSupplyStatus OBJECT-TYPE SYNTAX INTEGER { unknown (1), notInstalled (2), offOk (3), onOk (4), offFail (5), onFail (6), lostComm (7) } ACCESS read-only STATUS mandatory DESCRIPTION "The status of the System Power Supply. unknown(1) indicates the device status is unknown. notInstalled(2) indicates the device is not installed. offOk(3) indicates the device status is off and OK. onOk(4) indicates the device status is on and OK. offFail(5) indicates the device status is off and failed. onFail(6) indicates the device status is on and failed. lostComm(7) indicates the device has lost communication." ::= { upsDiagSubSysSystemPowerSupplyEntry 3 } upsDiagSubSysXRCommunicationCardTableSize OBJECT-TYPE SYNTAX INTEGER ACCESS read-only STATUS mandatory DESCRIPTION "The number of XR Communication Cards attached to the UPS." ::= { upsDiagnosticSubsystem 15 } upsDiagSubSysXRCommunicationCardTable OBJECT-TYPE SYNTAX SEQUENCE OF UpsDiagSubSysXRCommunicationCardEntry ACCESS not-accessible STATUS mandatory DESCRIPTION "Allows for diagnostics of individual XR Communication Cards." ::= { upsDiagnosticSubsystem 16 } upsDiagSubSysXRCommunicationCardEntry OBJECT-TYPE SYNTAX UpsDiagSubSysXRCommunicationCardEntry ACCESS not-accessible STATUS mandatory DESCRIPTION "The diagnostics of an XR Communication Card." INDEX { upsDiagSubSysXRCommunicationCardIndex} ::= { upsDiagSubSysXRCommunicationCardTable 1 } UpsDiagSubSysXRCommunicationCardEntry ::= SEQUENCE { upsDiagSubSysXRCommunicationCardFrameIndex INTEGER, upsDiagSubSysXRCommunicationCardIndex INTEGER, upsDiagSubSysXRCommunicationCardStatus INTEGER } upsDiagSubSysXRCommunicationCardFrameIndex OBJECT-TYPE SYNTAX INTEGER ACCESS read-only STATUS mandatory DESCRIPTION "The frame index entry." ::= { upsDiagSubSysXRCommunicationCardEntry 1 } upsDiagSubSysXRCommunicationCardIndex OBJECT-TYPE SYNTAX INTEGER ACCESS read-only STATUS mandatory DESCRIPTION "The index of an XR Communication Card." ::= { upsDiagSubSysXRCommunicationCardEntry 2 } upsDiagSubSysXRCommunicationCardStatus OBJECT-TYPE SYNTAX INTEGER { unknown (1), notInstalled (2), offOk (3), onOk (4), offFail (5), onFail (6), lostComm (7) } ACCESS read-only STATUS mandatory DESCRIPTION "The status of the XR Communication Card. unknown(1) indicates the device status is unknown. notInstalled(2) indicates the device is not installed. offOk(3) indicates the device status is off and OK. onOk(4) indicates the device status is on and OK. offFail(5) indicates the device status is off and failed. onFail(6) indicates the device status is on and failed. lostComm(7) indicates the device has lost communication." ::= { upsDiagSubSysXRCommunicationCardEntry 3 } upsDiagSubSysExternalPowerFrameBoardTableSize OBJECT-TYPE SYNTAX INTEGER ACCESS read-only STATUS mandatory DESCRIPTION "The number of External Power Frame Boards attached to the UPS." ::= { upsDiagnosticSubsystem 17 } upsDiagSubSysExternalPowerFrameBoardTable OBJECT-TYPE SYNTAX SEQUENCE OF UpsDiagSubSysExternalPowerFrameBoardEntry ACCESS not-accessible STATUS mandatory DESCRIPTION "Allows for diagnostics of individual External Power Frame Boards." ::= { upsDiagnosticSubsystem 18 } upsDiagSubSysExternalPowerFrameBoardEntry OBJECT-TYPE SYNTAX UpsDiagSubSysExternalPowerFrameBoardEntry ACCESS not-accessible STATUS mandatory DESCRIPTION "The diagnostics of an External Power Frame Board." INDEX { upsDiagSubSysExternalPowerFrameBoardIndex} ::= { upsDiagSubSysExternalPowerFrameBoardTable 1 } UpsDiagSubSysExternalPowerFrameBoardEntry ::= SEQUENCE { upsDiagSubSysExternalPowerFrameBoardFrameIndex INTEGER, upsDiagSubSysExternalPowerFrameBoardIndex INTEGER, upsDiagSubSysExternalPowerFrameBoardStatus INTEGER } upsDiagSubSysExternalPowerFrameBoardFrameIndex OBJECT-TYPE SYNTAX INTEGER ACCESS read-only STATUS mandatory DESCRIPTION "The frame index entry." ::= { upsDiagSubSysExternalPowerFrameBoardEntry 1 } upsDiagSubSysExternalPowerFrameBoardIndex OBJECT-TYPE SYNTAX INTEGER ACCESS read-only STATUS mandatory DESCRIPTION "The index of an External Power Frame Board." ::= { upsDiagSubSysExternalPowerFrameBoardEntry 2 } upsDiagSubSysExternalPowerFrameBoardStatus OBJECT-TYPE SYNTAX INTEGER { unknown (1), notInstalled (2), offOk (3), onOk (4), offFail (5), onFail (6), lostComm (7) } ACCESS read-only STATUS mandatory DESCRIPTION "The status of the External Power Frame Board. unknown(1) indicates the device status is unknown. notInstalled(2) indicates the device is not installed. offOk(3) indicates the device status is off and OK. onOk(4) indicates the device status is on and OK. offFail(5) indicates the device status is off and failed. onFail(6) indicates the device status is on and failed. lostComm(7) indicates the device has lost communication." ::= { upsDiagSubSysExternalPowerFrameBoardEntry 3 } upsDiagSubSysChargerTableSize OBJECT-TYPE SYNTAX INTEGER ACCESS read-only STATUS mandatory DESCRIPTION "The number of Chargers attached to the UPS." ::= { upsDiagnosticSubsystem 19 } upsDiagSubSysChargerTable OBJECT-TYPE SYNTAX SEQUENCE OF UpsDiagSubSysChargerEntry ACCESS not-accessible STATUS mandatory DESCRIPTION "Allows for diagnostics of individual chargers." ::= { upsDiagnosticSubsystem 20 } upsDiagSubSysChargerEntry OBJECT-TYPE SYNTAX UpsDiagSubSysChargerEntry ACCESS not-accessible STATUS mandatory DESCRIPTION "The diagnostics of a charger." INDEX { upsDiagSubSysChargerIndex} ::= { upsDiagSubSysChargerTable 1 } UpsDiagSubSysChargerEntry ::= SEQUENCE { upsDiagSubSysChargerFrameIndex INTEGER, upsDiagSubSysChargerIndex INTEGER, upsDiagSubSysChargerStatus INTEGER } upsDiagSubSysChargerFrameIndex OBJECT-TYPE SYNTAX INTEGER ACCESS read-only STATUS mandatory DESCRIPTION "The frame index entry." ::= { upsDiagSubSysChargerEntry 1 } upsDiagSubSysChargerIndex OBJECT-TYPE SYNTAX INTEGER ACCESS read-only STATUS mandatory DESCRIPTION "The index of a charger." ::= { upsDiagSubSysChargerEntry 2 } upsDiagSubSysChargerStatus OBJECT-TYPE SYNTAX INTEGER { unknown (1), notInstalled (2), offOk (3), onOk (4), offFail (5), onFail (6), lostComm (7) } ACCESS read-only STATUS mandatory DESCRIPTION "The status of the Charger. unknown(1) indicates the device status is unknown. notInstalled(2) indicates the device is not installed. offOk(3) indicates the device status is off and OK. onOk(4) indicates the device status is on and OK. offFail(5) indicates the device status is off and failed. onFail(6) indicates the device status is on and failed. lostComm(7) indicates the device has lost communication." ::= { upsDiagSubSysChargerEntry 3 } -- the upsDiagnosticExternalDevices group upsDiagSwitchGearStatus OBJECT-TYPE SYNTAX INTEGER { unknown (1), notInstalled (2), ok (3), fail (4), lostComm (5), overtemp (6) } ACCESS read-only STATUS mandatory DESCRIPTION "The status of the Switch Gear. unknown(1) indicates the device status is unknown. notInstalled(2) indicates the device is not installed. ok(3) indicates the device status is OK. fail(4) indicates the device status has failed. lostComm(5) indicates the device has lost communication. overtemp(6) indicates the device has an over temperature condition." ::= { upsDiagSwitchGear 1 } upsDiagSwitchGearInputSwitchStatus OBJECT-TYPE SYNTAX INTEGER { unknown (1), notInstalled (2), opened (3), closed (4) } ACCESS read-only STATUS mandatory DESCRIPTION "The status of the Switch Gear Input Switch. unknown(1) indicates the switch status is unknown. notInstalled(2) indicates the switch is not installed. opened(3) indicates the switch is opened. closed(4) indicates the switch is closed." ::= { upsDiagSwitchGear 2 } upsDiagSwitchGearOutputSwitchStatus OBJECT-TYPE SYNTAX INTEGER { unknown (1), notInstalled (2), opened (3), closed (4) } ACCESS read-only STATUS mandatory DESCRIPTION "The status of the Switch Gear Output Switch. unknown(1) indicates the switch status is unknown. notInstalled(2) indicates the switch is not installed. opened(3) indicates the switch is opened. closed(4) indicates the switch is closed." ::= { upsDiagSwitchGear 3 } upsDiagSwitchGearBypassSwitchStatus OBJECT-TYPE SYNTAX INTEGER { unknown (1), notInstalled (2), opened (3), closed (4) } ACCESS read-only STATUS mandatory DESCRIPTION "The status of the Switch Gear Bypass Switch. unknown(1) indicates the switch status is unknown. notInstalled(2) indicates the switch is not installed. opened(3) indicates the switch is opened. closed(4) indicates the switch is closed." ::= { upsDiagSwitchGear 4 } upsDiagMCCBBoxStatus OBJECT-TYPE SYNTAX INTEGER { unknown (1), notInstalled (2), opened (3), closed (4) } ACCESS read-only STATUS mandatory DESCRIPTION "The status of the MCCB Box (Molded Case Circuit Breaker Box) external device. unknown(1) indicates the device status is unknown. notInstalled(2) indicates the device is not installed. opened(3) indicates the circuit is opened. closed(4) indicates the circuit is closed." ::= { upsDiagMCCBBox 1 } upsDiagTransformerStatus OBJECT-TYPE SYNTAX INTEGER { unknown (1), notInstalled (2), ok (3), fail (4), lostComm (5), overtemp (6), opened (7), closed (8) } ACCESS read-only STATUS mandatory DESCRIPTION "The status of the External Transformer. unknown(1) indicates the device status is unknown. notInstalled(2) indicates the device is not installed. ok(3) indicates the device status is OK. fail(4) indicates the device status has failed. lostComm(5) indicates the device has lost communication. overtemp(6) indicates the device has an over temperature condition. opened(7) indicates the circuit is opened. closed(8) indicates the circuit is closed." ::= { upsDiagTransformer 1 } -- the upsDiagnosticComBus group upsDiagComBusInternalMIMStatus OBJECT-TYPE SYNTAX INTEGER { unknown (1), notInstalled (2), ok (3), lostComm (4), rxFailure (5), txFailure (6) } ACCESS read-only STATUS mandatory DESCRIPTION "The status of the internal MIM communication bus. unknown(1) indicates the device status is unknown. notInstalled(2) indicates the device is not installed. ok(3) indicates the device status is OK. lostComm(4) indicates the device has lost communication. rxFailure(5) indicates the device has a receive failure. txFailure(6) indicates the device has a transmit failure." ::= { upsDiagnosticComBus 1 } upsDiagComBusInternalRIMStatus OBJECT-TYPE SYNTAX INTEGER { unknown (1), notInstalled (2), ok (3), lostComm (4), rxFailure (5), txFailure (6) } ACCESS read-only STATUS mandatory DESCRIPTION "The status of the internal RIM communication bus. unknown(1) indicates the device status is unknown. notInstalled(2) indicates the device is not installed. ok(3) indicates the device status is OK. lostComm(4) indicates the device has lost communication. rxFailure(5) indicates the device has a receive failure. txFailure(6) indicates the device has a transmit failure." ::= { upsDiagnosticComBus 2 } upsDiagComBusMIMtoRIMStatus OBJECT-TYPE SYNTAX INTEGER { unknown (1), notInstalled (2), ok (3), lostComm (4), rxFailure (5), txFailure (6) } ACCESS read-only STATUS mandatory DESCRIPTION "The status of the MIM to RIM communication bus. unknown(1) indicates the device status is unknown. notInstalled(2) indicates the device is not installed. ok(3) indicates the device status is OK. lostComm(4) indicates the device has lost communication. rxFailure(5) indicates the device has a receive failure. txFailure(6) indicates the device has a transmit failure." ::= { upsDiagnosticComBus 3 } upsDiagComBusExternalMIMStatus OBJECT-TYPE SYNTAX INTEGER { unknown (1), notInstalled (2), ok (3), lostComm (4), rxFailure (5), txFailure (6) } ACCESS read-only STATUS mandatory DESCRIPTION "The status of the external MIM communication bus. unknown(1) indicates the device status is unknown. notInstalled(2) indicates the device is not installed. ok(3) indicates the device status is OK. lostComm(4) indicates the device has lost communication. rxFailure(5) indicates the device has a receive failure. txFailure(6) indicates the device has a transmit failure." ::= { upsDiagnosticComBus 4 } upsDiagComBusExternalRIMStatus OBJECT-TYPE SYNTAX INTEGER { unknown (1), notInstalled (2), ok (3), lostComm (4), rxFailure (5), txFailure (6) } ACCESS read-only STATUS mandatory DESCRIPTION "The status of the external RIM communication bus. unknown(1) indicates the device status is unknown. notInstalled(2) indicates the device is not installed. ok(3) indicates the device status is OK. lostComm(4) indicates the device has lost communication. rxFailure(5) indicates the device has a receive failure. txFailure(6) indicates the device has a transmit failure." ::= { upsDiagnosticComBus 5 } -- the serialPort2Config group serialPort2Mode OBJECT-TYPE SYNTAX INTEGER { localConsole(1), passthrough(2) } ACCESS read-write STATUS obsolete DESCRIPTION "Setting this variable to passthrough will enable mini's port2 behave like a UPS port. Choosing localConsole will enable the port to be used as local console." ::= { serialPort2Config 1 } -- the serialPort2Control group setPulseOnTXD OBJECT-TYPE SYNTAX INTEGER { noSetPulseOnTXD(1), setPulseOnTXD(2), setTXDLow(3), setTXDHigh(4) } ACCESS read-write STATUS obsolete DESCRIPTION "Setting this variable to setPulseOnTXD(2) causes adapter to generate a PULSE on TXD pin of serial port 2. The duration in the prototype implementation will be 1 second. Setting this value to noSetPulseOnTXD(1) has no effect. The value noSetPulseOnTXD(1) will always be returned when the variable is read. Setting this value to setTXDLow(3), or setTXDHigh(4) will keep TXD always low or high respectively." ::= { serialPort2Control 1 } -- the sPDUIdent group sPDUIdentHardwareRev OBJECT-TYPE SYNTAX DisplayString ACCESS read-only STATUS mandatory DESCRIPTION "The hardware revision of the PDU. This value is set at the factory." ::= { sPDUIdent 1 } sPDUIdentFirmwareRev OBJECT-TYPE SYNTAX DisplayString ACCESS read-only STATUS mandatory DESCRIPTION "An 8 byte ID string identifying the PDU firmware revision. This value is set at the factory." ::= { sPDUIdent 2 } sPDUIdentDateOfManufacture OBJECT-TYPE SYNTAX DisplayString ACCESS read-only STATUS mandatory DESCRIPTION "The date when the PDU was manufactured in mm/dd/yy format. This value is set at the factory. The year 2000 will be represented by 00." ::= { sPDUIdent 3 } sPDUIdentModelNumber OBJECT-TYPE SYNTAX DisplayString ACCESS read-only STATUS mandatory DESCRIPTION "A 10-character string identifying the model number of the PDU internal. This value is set at the factory." ::= { sPDUIdent 4 } sPDUIdentSerialNumber OBJECT-TYPE SYNTAX DisplayString ACCESS read-only STATUS mandatory DESCRIPTION "A 12-character string identifying the serial number of the PDU internal microprocessor. This value is set at the factory." ::= { sPDUIdent 5 } -- the sPDUMasterControl group sPDUMasterControlSwitch OBJECT-TYPE SYNTAX INTEGER { turnAllOnNow (1), turnAllOnSequence (2), turnAllOffNow (3), rebootAllNow (4), rebootAllSequence (5), noCommand (6), turnAllOffSequence (7) } ACCESS read-write STATUS mandatory DESCRIPTION "Setting this OID to turnAllOnNow (1) will turn all outlets on immediately. Setting this OID to turnAllOnSequence (2) will turn all outlets on as defined by each outlet's sPDUOutletPowerOnTime OID value. Setting this OID to turnAllOff (3) will turn all outlets off immediately. Setting this OID to rebootAllNow (4) will reboot all outlets immediately. For MasterSwitch firmware version 1.X, setting this OID to rebootAllSequence (5) reboots all outlets, with power returned to the outlets in the sequence defined by each outlet's sPDUOutletPowerOnTime OID value. For MasterSwitch firmware version 2.X, setting this OID to rebootAllSequence (5) will cause a turnAllOffSequence to be performed. Once all outlets are off, the MasterSwitch will then delay the sPDUMasterConfigReboot OID time, and then perform a turnAllOnSequence. For MasterSwitch firmware version 2.X, setting this OID to turnAllOffSequence (7) will turn all outlets off as defined by each outlet's sPDUOutletPowerOffTime OID value. For MasterSwitch firmware version 1.X, setting this OID to turnAllOffSequence (7) will have no effect. Getting this OID will return the noCommand (6) value." ::= { sPDUMasterControl 1 } sPDUMasterState OBJECT-TYPE SYNTAX DisplayString ACCESS read-only STATUS mandatory DESCRIPTION "Getting this OID will cause the status of all outlets to be returned. This OID is provided for informational purposes only. To change the outlet state, the user should use the sPDUOutletCtl OID in the sPDUOutletControlTable. The format of the data returned is a character string consisting of the word 'On' if the outlet is on or 'Off' if the outlet is off. At least one space will delimit each outlet entry in the string. If the outlet states are unknown, the character string 'Unknown' will be returned. This signifies that there is an inconsistancy in the PDU. In the rare case that this should happen, the user is advised to shut down all equipment powered by the PDU and then cycle the PDU's power. This will put the PDU in a consistent state." ::= { sPDUMasterControl 2 } sPDUMasterPending OBJECT-TYPE SYNTAX DisplayString ACCESS read-only STATUS mandatory DESCRIPTION "Getting this OID will cause the command pending status of all outlets to be returned. The format of the data returned is a character string consisting of the word 'Yes' if a command is pending for the outlet or 'No' if there is no command pending for the outlet. At least one space will delimit each outlet entry in the string. If the pending states are unknown, the character string 'Unknown' will be returned. This signifies that there is an inconsistancy in the PDU. In the rare case that this should happen, the user is advised to shut down all equipment powered by the PDU and then cycle the PDU's power. This will put the PDU in a consistent state." ::= { sPDUMasterControl 3 } -- the sPDUMasterConfig group sPDUMasterConfigPowerOn OBJECT-TYPE SYNTAX INTEGER ACCESS read-write STATUS mandatory DESCRIPTION " The amount of delay, in seconds, between when power is provided to the PDU and when the PDU provides basic master power to the outlets. Allowed values are: -1 never apply power automatically. 0 apply power immediately. 15 apply power in 15 seconds. 30 apply power in 30 seconds. 45 apply power in 45 seconds. 60 apply power in 60 seconds (1 minute). 120 apply power in 120 seconds (2 minutes). 300 apply power in 300 seconds (5 minutes). If a value other than a supported value is provided in a set request, the PDU interprets it as the next lower acceptable value. If the provided value is lower than the lowest acceptable value, the lowest acceptable value is used." ::= { sPDUMasterConfig 1 } sPDUMasterConfigReboot OBJECT-TYPE SYNTAX INTEGER ACCESS read-write STATUS mandatory DESCRIPTION "During a reboot sequence, power is turned off and then back on. This OID defines the amount of time to wait, in seconds, after turning the power off, at the start of the sequence, before turning power back on, at the end of the reboot sequence. Allowed values are: 5 wait 5 seconds between off/on. 10 wait 10 seconds between off/on. 15 wait 15 seconds between off/on. 20 wait 20 seconds between off/on. 30 wait 30 seconds between off/on. 45 wait 45 seconds between off/on. 60 wait 60 seconds (1 minute) between off/on. If a value other than a supported value is provided in a set request, the PDU interprets it as the next lower acceptable value. If the provided value is lower than the lowest acceptable value, the lowest acceptable value is used. This OID is read-only for the MasterSwitch version 2.X and is the maximum sPDUOutletRebootDuration OID of the individual outlets." ::= { sPDUMasterConfig 2 } sPDUMasterConfigPDUName OBJECT-TYPE SYNTAX DisplayString ACCESS read-write STATUS mandatory DESCRIPTION "The name of the PDU. The maximum value is 20 characters." ::= { sPDUMasterConfig 3 } -- the sPDUOutletControl group sPDUOutletControlTableSize OBJECT-TYPE SYNTAX INTEGER ACCESS read-only STATUS mandatory DESCRIPTION "The number of outlets for the PDU." ::= { sPDUOutletControl 1 } sPDUOutletControlTable OBJECT-TYPE SYNTAX SEQUENCE OF OutletControlEntry ACCESS not-accessible STATUS mandatory DESCRIPTION "Allows for control of individual outlet switches. The number of entries is contained in the sPDUOutletControlTableSize OID." ::= { sPDUOutletControl 2 } sPDUOutletControlEntry OBJECT-TYPE SYNTAX OutletControlEntry ACCESS not-accessible STATUS mandatory DESCRIPTION "The outlets to control." INDEX { sPDUOutletControlIndex} ::= { sPDUOutletControlTable 1 } OutletControlEntry ::= SEQUENCE { sPDUOutletControlIndex INTEGER, sPDUOutletPending INTEGER, sPDUOutletCtl INTEGER, sPDUOutletCtlName DisplayString } sPDUOutletControlIndex OBJECT-TYPE SYNTAX INTEGER ACCESS read-only STATUS mandatory DESCRIPTION "The index to the outlet entry." ::= { sPDUOutletControlEntry 1 } sPDUOutletPending OBJECT-TYPE SYNTAX INTEGER{ commandPending (1), noCommandPending (2), commandPendingUnknown (3) } ACCESS read-only STATUS mandatory DESCRIPTION "Reports whether the current outlet has a pending command. If the commandPendingUnknown (3) value is returned, all devices powered by the PDU should be shut down. The PDU's power should then be cycled to clear this condition." ::= { sPDUOutletControlEntry 2 } sPDUOutletCtl OBJECT-TYPE SYNTAX INTEGER { outletOn (1), outletOff (2), outletReboot (3), outletUnknown (4), outletOnWithDelay (5), outletOffWithDelay (6), outletRebootWithDelay (7) } ACCESS read-write STATUS mandatory DESCRIPTION "Getting this variable will return the outlet state. If the outlet is on, the outletOn (1) value will be returned. If the outlet is off, the outletOff (2) value will be returned. If the state of the outlet cannot be determined, the outletUnknown (4) value will be returned. If the outletUnknown condition should occur, all devices powered by the PDU should be shut down. The PDU's power should then be cycled to clear this condition. Setting this variable to outletOn (1) will turn the outlet on. Setting this variable to outletOff (2) will turn the outlet off. Setting this variable to outletReboot (3) will reboot the outlet. Setting this variable to outletOnWithDelay (5) will turn the outlet on after the sPDUOutletPowerOnTime OID has elapsed. This option is not valid for MasterSwitch firmware version 1.X. Setting this variable to outletOffWithDelay (6) will turn the outlet off after the sPDUOutletPowerOffTime OID has elapsed. This option is not valid for MasterSwitch firmware version 1.X. Setting this variable to outletRebootWithDelay (7) will turn the outlet off after the sPDUOutletPowerOffTime OID has elapsed, wait the sPDUOutletRebootDuration OID time, then turn the outlet back on. This option is not valid for MasterSwitch firmware version 1.X." ::= { sPDUOutletControlEntry 3 } sPDUOutletCtlName OBJECT-TYPE SYNTAX DisplayString ACCESS read-only STATUS mandatory DESCRIPTION "The name of the outlet. Maximum size is 20 characters. This OID is provided for informational purposes only. This value is set by the sPDUOutletName OID." ::= { sPDUOutletControlEntry 4 } -- the sPDUOutletConfig group sPDUOutletConfigTableSize OBJECT-TYPE SYNTAX INTEGER ACCESS read-only STATUS mandatory DESCRIPTION "The number of outlets for the PDU." ::= { sPDUOutletConfig 1 } sPDUOutletConfigTable OBJECT-TYPE SYNTAX SEQUENCE OF SPDUOutletConfigEntry ACCESS not-accessible STATUS mandatory DESCRIPTION "The list of outlets to configure. The number of entries is defined by the sPDUOutletConfigTableSize OID." ::= { sPDUOutletConfig 2 } sPDUOutletConfigEntry OBJECT-TYPE SYNTAX SPDUOutletConfigEntry ACCESS not-accessible STATUS mandatory DESCRIPTION "The outlets to control." INDEX { sPDUOutletConfigIndex} ::= { sPDUOutletConfigTable 1 } SPDUOutletConfigEntry ::= SEQUENCE { sPDUOutletConfigIndex INTEGER, sPDUOutletPowerOnTime INTEGER, sPDUOutletName DisplayString, sPDUOutletPowerOffTime INTEGER, sPDUOutletRebootDuration INTEGER } sPDUOutletConfigIndex OBJECT-TYPE SYNTAX INTEGER ACCESS read-only STATUS mandatory DESCRIPTION "The index to the outlet entry." ::= { sPDUOutletConfigEntry 1 } sPDUOutletPowerOnTime OBJECT-TYPE SYNTAX INTEGER ACCESS read-write STATUS mandatory DESCRIPTION "The amount of time (in seconds) the outlet will delay powering on when the MasterSwitch is powered on. Allowed values are: -1 never power on automatically. 0 power on with the Master Switch. 15 power on 15 seconds after the MasterSwitch has power applied. 30 power on 30 seconds after the MasterSwitch has power applied. 45 power on 45 seconds after the MasterSwitch has power applied. 60 power on 60 seconds (1 minute) after the MasterSwitch has power applied. 120 power on 120 seconds (2 minutes) after the MasterSwitch has power applied. 300 power on 300 seconds (5 minutes) after the MasterSwitch has power applied. If a value other than a supported value is provided in a set request, the PDU interprets it as the next lower acceptable value. If the provided value is lower than the lowest acceptable value, the lowest acceptable value is used." ::= { sPDUOutletConfigEntry 2 } sPDUOutletName OBJECT-TYPE SYNTAX DisplayString ACCESS read-write STATUS mandatory DESCRIPTION "The name of the outlet. Maximum size is 20 characters." ::= { sPDUOutletConfigEntry 3 } sPDUOutletPowerOffTime OBJECT-TYPE SYNTAX INTEGER ACCESS read-write STATUS mandatory DESCRIPTION "The amount of time (in seconds) the outlet will delay powering off. Allowed values are: -1 never power off automatically. 0 power off with the MasterSwitch. 15 power off 15 seconds after being commanded. 30 power off 30 seconds after being commanded. 45 power off 45 seconds after being commanded. 60 power off 60 seconds (1 minute) after being commanded. 120 power off 120 seconds (2 minutes) after being commanded. 300 power off 300 seconds (5 minutes) after being commanded. If a value other than a supported value is provided in a set request, the PDU interprets it as the next lower acceptable value. If the provided value is lower than the lowest acceptable value, the lowest acceptable value is used. This OID is not available for MasterSwitch firmware version 1.X." ::= { sPDUOutletConfigEntry 4 } sPDUOutletRebootDuration OBJECT-TYPE SYNTAX INTEGER ACCESS read-write STATUS mandatory DESCRIPTION "During a reboot sequence, power is turned off and then back on. This OID defines the amount of time to wait, in seconds, after turning the power off, at the start of the sequence, before turning power back on, at the end of the reboot sequence. Allowed values are: 5 wait 5 seconds between off/on. 10 wait 10 seconds between off/on. 15 wait 15 seconds between off/on. 20 wait 20 seconds between off/on. 30 wait 30 seconds between off/on. 45 wait 45 seconds between off/on. 60 wait 60 seconds (1 minute) between off/on. If a value other than a supported value is provided in a set request, the PDU interprets it as the next lower acceptable value. If the provided value is lower than the lowest acceptable value, the lowest acceptable value is used. This OID is not available for MasterSwitch firmware version 1.X." ::= { sPDUOutletConfigEntry 5 } -- the sPDUIdentVM group sPDUIdentVMTableSize OBJECT-TYPE SYNTAX INTEGER ACCESS read-only STATUS mandatory DESCRIPTION "The number of MasterSwitch VMs controllable by this IP address." ::= { sPDUIdentVM 1 } sPDUIdentVMTable OBJECT-TYPE SYNTAX SEQUENCE OF IdentVMEntry ACCESS not-accessible STATUS mandatory DESCRIPTION "Allows for query of the individual MasterSwitch VMs. The number of entries is contained in the sPDUIdentVMTableSize OID." ::= { sPDUIdentVM 2 } sPDUIdentVMEntry OBJECT-TYPE SYNTAX IdentVMEntry ACCESS not-accessible STATUS mandatory DESCRIPTION "The MasterSwitch VMs to query." INDEX { sPDUIdentVMIndex} ::= { sPDUIdentVMTable 1 } IdentVMEntry ::= SEQUENCE { sPDUIdentVMIndex INTEGER, sPDUIdentNameVM DisplayString, sPDUIdentHardwareRevVM DisplayString, sPDUIdentFirmwareRevVM DisplayString, sPDUIdentDateOfManufactureVM DisplayString, sPDUIdentModelNumberVM DisplayString, sPDUIdentSerialNumberVM DisplayString } sPDUIdentVMIndex OBJECT-TYPE SYNTAX INTEGER ACCESS read-only STATUS mandatory DESCRIPTION "The index to the MasterSwitch VM entry." ::= { sPDUIdentVMEntry 1 } sPDUIdentNameVM OBJECT-TYPE SYNTAX DisplayString ACCESS read-only STATUS mandatory DESCRIPTION "A 23-character string identifying the MasterSwitch VM. " ::= { sPDUIdentVMEntry 2 } sPDUIdentHardwareRevVM OBJECT-TYPE SYNTAX DisplayString ACCESS read-only STATUS mandatory DESCRIPTION "The hardware version of the MasterSwitch VM. This value is set at the factory." ::= { sPDUIdentVMEntry 3 } sPDUIdentFirmwareRevVM OBJECT-TYPE SYNTAX DisplayString ACCESS read-only STATUS mandatory DESCRIPTION "An 6-character ID string identifying the MasterSwitch VM firmware version. This value is set at the factory." ::= { sPDUIdentVMEntry 4 } sPDUIdentDateOfManufactureVM OBJECT-TYPE SYNTAX DisplayString ACCESS read-only STATUS mandatory DESCRIPTION "The date when the MasterSwitch VM was manufactured in mm/dd/yyyy format. This value is set at the factory. " ::= { sPDUIdentVMEntry 5 } sPDUIdentModelNumberVM OBJECT-TYPE SYNTAX DisplayString ACCESS read-only STATUS mandatory DESCRIPTION "A 17-character string identifying the model number of the MasterSwitch VM. This value is set at the factory." ::= { sPDUIdentVMEntry 6 } sPDUIdentSerialNumberVM OBJECT-TYPE SYNTAX DisplayString ACCESS read-only STATUS mandatory DESCRIPTION "A 17-character string identifying the serial number of the MasterSwitch VM. This value is set at the factory." ::= { sPDUIdentVMEntry 7 } -- the sPDUMasterControlVM group sPDUMasterControlVMTableSize OBJECT-TYPE SYNTAX INTEGER ACCESS read-only STATUS mandatory DESCRIPTION "The number of MasterSwitch VMs controllable by this IP address." ::= { sPDUMasterControlVM 1 } sPDUMasterControlVMTable OBJECT-TYPE SYNTAX SEQUENCE OF MasterControlVMEntry ACCESS not-accessible STATUS mandatory DESCRIPTION "Allows for control of the individual MasterSwitch VMs. The number of entries is contained in the sPDUMasterControlVMTableSize OID." ::= { sPDUMasterControlVM 2 } sPDUMasterControlVMEntry OBJECT-TYPE SYNTAX MasterControlVMEntry ACCESS not-accessible STATUS mandatory DESCRIPTION "The MasterSwitch VMs to control." INDEX { sPDUMasterControlVMIndex} ::= { sPDUMasterControlVMTable 1 } MasterControlVMEntry ::= SEQUENCE { sPDUMasterControlVMIndex INTEGER, sPDUMasterControlVMName DisplayString, sPDUMasterControlVMCommand INTEGER } sPDUMasterControlVMIndex OBJECT-TYPE SYNTAX INTEGER ACCESS read-only STATUS mandatory DESCRIPTION "The index to the MasterSwitch VM entry." ::= { sPDUMasterControlVMEntry 1 } sPDUMasterControlVMName OBJECT-TYPE SYNTAX DisplayString ACCESS read-only STATUS mandatory DESCRIPTION "The name of the MasterSwitch VM. The maximum value is 23 characters. The name is set by using the sPDUMasterConfigVMName OID." ::= { sPDUMasterControlVMEntry 2 } sPDUMasterControlVMCommand OBJECT-TYPE SYNTAX INTEGER { noCommandAllVM (1), immediateAllOnVM (2), immediateAllOffVM (3), immediateAllRebootVM (4), delayedAllOnVM (5), delayedAllOffVM (6), sequencedAllRebootVM (7), delayedAllRebootVM (8), delayedSequenceAllRebootVM (9), cancelAllPendingCommandsVM (10), audioAlarmMute (11) } ACCESS read-write STATUS mandatory DESCRIPTION "Setting this OID to immediateAllOnVM (2) will turn all outlets on immediately. Setting this OID to immediateAllOffVM (3) will turn all outlets off immediately. Setting this OID to immediateAllRebootVM (4) will reboot all outlets immediately. Setting this OID to delayedAllOnVM (5) will turn all outlets on as defined by each outlet's sPDUOutletConfigVMPowerOnTime OID value. Setting this OID to delayedAllOffVM (6) will turn all outlets off as defined by each outlet's sPDUOutletConfigVMPowerOffTime OID value. Setting this OID to sequencedAllRebootVM (7) will cause a immediateAllOffVM command to be performed. The MasterSwitch VM will then delay the sPDUMasterStatusVMRebootDuration OID time, and then perform a delayedAllOnVM command. Setting this OID to delayedAllRebootVM (8) will cause a delayedAllOffVM command to be performed. Each outlet will then wait its sPDUOutletConfigVMRebootDuration before returning power to the outlet. Setting this OID to delayedSequenceAllRebootVM (9) will cause a delayedAllOffVM command to be performed. Once all outlets are off, the MasterSwitch VM will then delay the sPDUMasterStatusVMRebootDuration OID time, and then perform a delayedAllOnVM command. Setting this OID to cancelAllPendingCommandsVM (10) will cause all pending commands on the MasterSwitch VM to be canceled. Setting this OID to audioAlarmMute (11) will temporarily silence the audible alarm for the duration of the current overload condition. The audible alarm will be activated on subsequent overload alarms. Getting this OID will return the noCommandAllVM (1) value." ::= { sPDUMasterControlVMEntry 3 } -- the sPDUMasterConfigVM group sPDUMasterConfigVMTableSize OBJECT-TYPE SYNTAX INTEGER ACCESS read-only STATUS mandatory DESCRIPTION "The number of MasterSwitch VMs configurable by this IP address." ::= { sPDUMasterConfigVM 1 } sPDUMasterConfigVMTable OBJECT-TYPE SYNTAX SEQUENCE OF MasterConfigVMEntry ACCESS not-accessible STATUS mandatory DESCRIPTION "Allows for configuration of the individual MasterSwitch VMs. The number of entries is contained in the sPDUMasterConfigVMTableSize OID." ::= { sPDUMasterConfigVM 2 } sPDUMasterConfigVMEntry OBJECT-TYPE SYNTAX MasterConfigVMEntry ACCESS not-accessible STATUS mandatory DESCRIPTION "The MasterSwitch VMs to configure." INDEX { sPDUMasterConfigVMIndex} ::= { sPDUMasterConfigVMTable 1 } MasterConfigVMEntry ::= SEQUENCE { sPDUMasterConfigVMIndex INTEGER, sPDUMasterConfigVMName DisplayString, sPDUMasterConfigVMColdstartDelay INTEGER, sPDUMasterConfigVMAudioAlarmActivated INTEGER, sPDUMasterConfigVMHighLoadWarningThreshold INTEGER, sPDUMasterConfigVMLowLoadWarningThreshold INTEGER, sPDUMasterConfigVMOverloadRestriction INTEGER } sPDUMasterConfigVMIndex OBJECT-TYPE SYNTAX INTEGER ACCESS read-only STATUS mandatory DESCRIPTION "The index to the MasterSwitch VM entry." ::= { sPDUMasterConfigVMEntry 1 } sPDUMasterConfigVMName OBJECT-TYPE SYNTAX DisplayString ACCESS read-write STATUS mandatory DESCRIPTION "The name of the MasterSwitch VM. Maximum size is 23 characters." ::= { sPDUMasterConfigVMEntry 2 } sPDUMasterConfigVMColdstartDelay OBJECT-TYPE SYNTAX INTEGER ACCESS read-write STATUS mandatory DESCRIPTION " The amount of delay, in seconds, between when power is provided to the MasterSwitch VM and when the MasterSwitch VM provides basic master power to the outlets. Allowed values are: -1 never apply power automatically. 0 apply power immediately. 15 apply power in 15 seconds. 30 apply power in 30 seconds. 45 apply power in 45 seconds. 60 apply power in 60 seconds (1 minute). 120 apply power in 120 seconds (2 minutes). 300 apply power in 300 seconds (5 minutes). If a value other than a supported value is provided in a set request, the MasterSwitch VM interprets it as the next lower acceptable value. If the provided value is lower than the lowest acceptable value, the lowest acceptable value is used." ::= { sPDUMasterConfigVMEntry 3 } sPDUMasterConfigVMAudioAlarmActivated OBJECT-TYPE SYNTAX INTEGER { audioAlarmActiveNever (1), audioAlarmActiveOnOverload (2), audioAlarmActiveOnOverloadImminent (3) } ACCESS read-write STATUS mandatory DESCRIPTION "Setting this OID to audioAlarmActiveNever (1) will disable the audio alarm on the MasterSwitch VM. Setting this OID to audioAlarmActiveOnOverload (2) will activate the audio alarm on the MasterSwitch VM when an overload condition is present. Setting this OID to audioAlarmActiveOnOverloadImminent (3) will activate the audio alarm on the MasterSwitch VM when the load on the MasterSwitch VM has surpassed the sPDUMasterConfigVMHighLoadWarningThreshold OID value." ::= { sPDUMasterConfigVMEntry 4 } sPDUMasterConfigVMHighLoadWarningThreshold OBJECT-TYPE SYNTAX INTEGER (0..100) ACCESS read-write STATUS mandatory DESCRIPTION "A threshold that indicates the power consumption of the load is nearing an overload condition. It is represented as a percentage of full load." ::= { sPDUMasterConfigVMEntry 5 } sPDUMasterConfigVMLowLoadWarningThreshold OBJECT-TYPE SYNTAX INTEGER (0..100) ACCESS read-write STATUS mandatory DESCRIPTION "A threshold that indicates the power consumption of the load is nearing a low consumption condition. It is represented as a percentage of full load." ::= { sPDUMasterConfigVMEntry 6 } sPDUMasterConfigVMOverloadRestriction OBJECT-TYPE SYNTAX INTEGER { alwaysAllowTurnON (1), restrictOnWarning (2), restrictOnOverload (3) } ACCESS read-write STATUS mandatory DESCRIPTION "This OID controls the behavior of the MasterSwitch VM when an overload condition is possible and additional outlets are requested to be turned on. Setting this OID to alwaysAllowTurnON (1) will always allow the outlets to turn on. Setting this OID to restrictOnWarning (2) will not allow outlets to turn on if the sPDUMasterConfigVMHighLoadWarningThreshold OID is exceeded. Setting this OID to restrictOnOverload (3) will not allow outlets to turn on if the MasterSwitch Vm is in an overload condition." ::= { sPDUMasterConfigVMEntry 7 } -- the sPDUMasterStatusVM group sPDUMasterStatusVMTableSize OBJECT-TYPE SYNTAX INTEGER ACCESS read-only STATUS mandatory DESCRIPTION "The number of MasterSwitch VMs at this IP address." ::= { sPDUMasterStatusVM 1 } sPDUMasterStatusVMTable OBJECT-TYPE SYNTAX SEQUENCE OF MasterStatusVMEntry ACCESS not-accessible STATUS mandatory DESCRIPTION "Allows for gathering of status from the individual MasterSwitch VMs. The number of entries is contained in the sPDUMasterStatusVMTableSize OID." ::= { sPDUMasterStatusVM 2 } sPDUMasterStatusVMEntry OBJECT-TYPE SYNTAX MasterStatusVMEntry ACCESS not-accessible STATUS mandatory DESCRIPTION "The MasterSwitch VMs to gather status from." INDEX { sPDUMasterStatusVMIndex} ::= { sPDUMasterStatusVMTable 1 } MasterStatusVMEntry ::= SEQUENCE { sPDUMasterStatusVMIndex INTEGER, sPDUMasterStatusVMName DisplayString, sPDUMasterStatusVMCommandPending INTEGER, sPDUMasterStatusVMOverloadCondition INTEGER, sPDUMasterStatusVMLowLoadCondition INTEGER, sPDUMasterStatusVMCurrentLoad INTEGER, sPDUMasterStatusVMMaxLoad INTEGER, sPDUMasterStatusVMOutletCount INTEGER, sPDUMasterStatusVMRebootDuration INTEGER } sPDUMasterStatusVMIndex OBJECT-TYPE SYNTAX INTEGER ACCESS read-only STATUS mandatory DESCRIPTION "The index to the MasterSwitch VM entry." ::= { sPDUMasterStatusVMEntry 1 } sPDUMasterStatusVMName OBJECT-TYPE SYNTAX DisplayString ACCESS read-only STATUS mandatory DESCRIPTION "The name of the MasterSwitch VM. Maximum size is 23 characters." ::= { sPDUMasterStatusVMEntry 2 } sPDUMasterStatusVMCommandPending OBJECT-TYPE SYNTAX INTEGER { commandPendingMasterTrueVM (1), commandPendingMasterFalseVM (2) } ACCESS read-only STATUS mandatory DESCRIPTION "Getting this OID will return commandPendingMasterTrueVM (1) if the MasterSwitch VM has a pending command on any of its outlets. commandPendingMasterFalseVM (2) will be returned if there are no pending commands." ::= { sPDUMasterStatusVMEntry 3 } sPDUMasterStatusVMOverloadCondition OBJECT-TYPE SYNTAX INTEGER { overloadConditionTrueVM (1), overloadConditionFalseVM (2) } ACCESS read-only STATUS mandatory DESCRIPTION "Getting this OID will return overloadConditionTrueVM (1) if the sPDUMasterConfigVMHighLoadWarningThreshold OID is violated. overloadConditionFalseVM (2) will be returned if the sPDUMasterConfigVMHighLoadWarningThreshold OID is not violated." ::= { sPDUMasterStatusVMEntry 4 } sPDUMasterStatusVMLowLoadCondition OBJECT-TYPE SYNTAX INTEGER { lowLoadConditionTrueVM (1), lowLoadConditionFalseVM (2) } ACCESS read-only STATUS mandatory DESCRIPTION "Getting this OID will return lowLoadConditionTrueVM (1) if the sPDUMasterConfigVMLowLoadWarningThreshold OID is violated. lowLoadConditionFalseVM (2) will be returned if the sPDUMasterConfigVMHighLoadWarningThreshold OID is not violated. " ::= { sPDUMasterStatusVMEntry 5 } sPDUMasterStatusVMCurrentLoad OBJECT-TYPE SYNTAX INTEGER ACCESS read-only STATUS mandatory DESCRIPTION "Getting this OID will return the total amount of power being consumed by the load. It is represented as a percentage of full load." ::= { sPDUMasterStatusVMEntry 6 } sPDUMasterStatusVMMaxLoad OBJECT-TYPE SYNTAX INTEGER ACCESS read-only STATUS mandatory DESCRIPTION "Getting this OID will return the total amount of power that this MasterSwitch VM can provide. It is represented in Amps." ::= { sPDUMasterStatusVMEntry 7 } sPDUMasterStatusVMOutletCount OBJECT-TYPE SYNTAX INTEGER ACCESS read-only STATUS mandatory DESCRIPTION "Getting this OID will return the number of controllable outlets for this MasterSwitch VM." ::= { sPDUMasterStatusVMEntry 8 } sPDUMasterStatusVMRebootDuration OBJECT-TYPE SYNTAX INTEGER ACCESS read-only STATUS mandatory DESCRIPTION "Getting this OID will return the largest sPDUOutletConfigVMRebootDuration OID time for this MasterSwitch VM." ::= { sPDUMasterStatusVMEntry 9 } -- the sPDUOutletControlVM group sPDUOutletControlVMTable OBJECT-TYPE SYNTAX SEQUENCE OF OutletControlVMEntry ACCESS not-accessible STATUS mandatory DESCRIPTION "Allows for control of individual outlet switches. The number of entries is contained in the sPDUMasterStatusOutletCount OID." ::= { sPDUOutletControlVM 1 } sPDUOutletControlVMEntry OBJECT-TYPE SYNTAX OutletControlVMEntry ACCESS not-accessible STATUS mandatory DESCRIPTION "The outlets to control." INDEX { sPDUOutletControlVMIndex, sPDUOutletControlVMOutletIndex } ::= { sPDUOutletControlVMTable 1 } OutletControlVMEntry ::= SEQUENCE { sPDUOutletControlVMIndex INTEGER, sPDUOutletControlVMName DisplayString, sPDUOutletControlVMOutletIndex INTEGER, sPDUOutletControlVMOutletName DisplayString, sPDUOutletControlVMOutletCommand INTEGER } sPDUOutletControlVMIndex OBJECT-TYPE SYNTAX INTEGER ACCESS read-only STATUS mandatory DESCRIPTION "The index to the MasterSwitch VM." ::= { sPDUOutletControlVMEntry 1 } sPDUOutletControlVMName OBJECT-TYPE SYNTAX DisplayString ACCESS read-only STATUS mandatory DESCRIPTION "The name of the MasterSwitch VM. Maximum size is 23 characters. This OID is provided for informational purposes only." ::= { sPDUOutletControlVMEntry 2 } sPDUOutletControlVMOutletIndex OBJECT-TYPE SYNTAX INTEGER ACCESS read-only STATUS mandatory DESCRIPTION "The index to the outlet entry." ::= { sPDUOutletControlVMEntry 3 } sPDUOutletControlVMOutletName OBJECT-TYPE SYNTAX DisplayString ACCESS read-only STATUS mandatory DESCRIPTION "The name of the outlet. Maximum size is 23 characters. This OID is provided for informational purposes only." ::= { sPDUOutletControlVMEntry 4 } sPDUOutletControlVMOutletCommand OBJECT-TYPE SYNTAX INTEGER { immediateOnVM (1), immediateOffVM (2), immediateRebootVM (3), delayedOnVM (4), delayedOffVM (5), delayedRebootVM (6), cancelPendingCommandVM (7) } ACCESS read-write STATUS mandatory DESCRIPTION "Getting this variable will return the outlet state. If the outlet is on, the immediateOnVM (1) value will be returned. If the outlet is off, the immediateOffVM (2) value will be returned. Setting this variable to immediateOnVM (1) will immediately turn the outlet on. Setting this variable to immediateOffVM (2) will immediately turn the outlet off. Setting this variable to immediateRebootVM (3) will immediately reboot the outlet. Setting this variable to delayedOnVM (4) will turn the outlet on after the sPDUOutletConfigVMPowerOnTime OID time has elapsed. Setting this variable to delayedOffVM (5) will turn the outlet off after the sPDUOutletConfigVMPowerOffTime OID time has elapsed. Setting this variable to delayedRebootVM (6) will cause the MasterSwitch VM to perform a delayedOffVM command, wait the sPDUOutletConfigVMRebootDuration OID time, and then perform the immediateOnVM command. Setting this variable to cancelPendingCommandVM (7) will cause any pending command to this outlet to be canceled." ::= { sPDUOutletControlVMEntry 5 } -- the sPDUOutletConfigVM group sPDUOutletConfigVMTable OBJECT-TYPE SYNTAX SEQUENCE OF OutletConfigVMEntry ACCESS not-accessible STATUS mandatory DESCRIPTION "Allows for configuration of individual outlets. The number of entries is contained in the sPDUMasterStatusOutletCount OID." ::= { sPDUOutletConfigVM 1 } sPDUOutletConfigVMEntry OBJECT-TYPE SYNTAX OutletConfigVMEntry ACCESS not-accessible STATUS mandatory DESCRIPTION "The outlets to configure." INDEX { sPDUOutletConfigVMIndex, sPDUOutletConfigVMOutletIndex } ::= { sPDUOutletConfigVMTable 1 } OutletConfigVMEntry ::= SEQUENCE { sPDUOutletConfigVMIndex INTEGER, sPDUOutletConfigVMName DisplayString, sPDUOutletConfigVMOutletIndex INTEGER, sPDUOutletConfigVMOutletName DisplayString, sPDUOutletConfigVMPowerOnTime INTEGER, sPDUOutletConfigVMPowerOffTime INTEGER, sPDUOutletConfigVMRebootDuration INTEGER } sPDUOutletConfigVMIndex OBJECT-TYPE SYNTAX INTEGER ACCESS read-only STATUS mandatory DESCRIPTION "The index to the MasterSwitch VM." ::= { sPDUOutletConfigVMEntry 1 } sPDUOutletConfigVMName OBJECT-TYPE SYNTAX DisplayString ACCESS read-only STATUS mandatory DESCRIPTION "The name of the MasterSwitch VM. Maximum size is 23 characters." ::= { sPDUOutletConfigVMEntry 2 } sPDUOutletConfigVMOutletIndex OBJECT-TYPE SYNTAX INTEGER ACCESS read-only STATUS mandatory DESCRIPTION "The index to the outlet entry." ::= { sPDUOutletConfigVMEntry 3 } sPDUOutletConfigVMOutletName OBJECT-TYPE SYNTAX DisplayString ACCESS read-write STATUS mandatory DESCRIPTION "The name of the outlet. Maximum size is 23 characters." ::= { sPDUOutletConfigVMEntry 4 } sPDUOutletConfigVMPowerOnTime OBJECT-TYPE SYNTAX INTEGER ACCESS read-write STATUS mandatory DESCRIPTION "The amount of time (in seconds) the outlet will delay powering on at coldstart or when a command that requires a turn-on delay is issued. Allowed values are: -1 never power on. 0 power on immediately. 15 power on 15 seconds after being commanded. 30 power on 30 seconds after being commanded. 45 power on 45 seconds after being commanded. 60 power on 60 seconds (1 minute) after being commanded. 120 power on 120 seconds (2 minutes) after being commanded. 300 power on 300 seconds (5 minutes) after being commanded. If a value other than a supported value is provided in a set request, the MasterSwitch VM interprets it as the next lower acceptable value. If the provided value is lower than the lowest acceptable value, the lowest acceptable value is used." ::= { sPDUOutletConfigVMEntry 5 } sPDUOutletConfigVMPowerOffTime OBJECT-TYPE SYNTAX INTEGER ACCESS read-write STATUS mandatory DESCRIPTION "The amount of time (in seconds) the outlet will delay powering off when a command that requires a turn-off delay is issued. Allowed values are: -1 never power off automatically. 0 power off immediately. 15 power off 15 seconds after being commanded. 30 power off 30 seconds after being commanded. 45 power off 45 seconds after being commanded. 60 power off 60 seconds (1 minute) after being commanded. 120 power off 120 seconds (2 minutes) after being commanded. 300 power off 300 seconds (5 minutes) after being commanded. If a value other than a supported value is provided in a set request, the MasterSwitch VM interprets it as the next lower acceptable value. If the provided value is lower than the lowest acceptable value, the lowest acceptable value is used." ::= { sPDUOutletConfigVMEntry 6 } sPDUOutletConfigVMRebootDuration OBJECT-TYPE SYNTAX INTEGER ACCESS read-write STATUS mandatory DESCRIPTION "During a reboot sequence, power is turned off and then back on. This OID defines the amount of time to wait, in seconds, after turning the power off, at the start of the sequence, before turning power back on, at the end of the reboot sequence. Allowed values are: 5 wait 5 seconds between off/on. 10 wait 10 seconds between off/on. 15 wait 15 seconds between off/on. 20 wait 20 seconds between off/on. 30 wait 30 seconds between off/on. 45 wait 45 seconds between off/on. 60 wait 60 seconds (1 minute) between off/on. If a value other than a supported value is provided in a set request, the MasterSwitch VM interprets it as the next lower acceptable value. If the provided value is lower than the lowest acceptable value, the lowest acceptable value is used." ::= { sPDUOutletConfigVMEntry 7 } -- the sPDUOutletStatusVM group sPDUOutletStatusVMTable OBJECT-TYPE SYNTAX SEQUENCE OF OutletStatusVMEntry ACCESS not-accessible STATUS mandatory DESCRIPTION "Allows for getting of status of individual outlets. The number of entries is contained in the sPDUMasterStatusOutletCount OID." ::= { sPDUOutletStatusVM 1 } sPDUOutletStatusVMEntry OBJECT-TYPE SYNTAX OutletStatusVMEntry ACCESS not-accessible STATUS mandatory DESCRIPTION "The outlets to gather status from." INDEX { sPDUOutletStatusVMIndex, sPDUOutletStatusVMOutletIndex } ::= { sPDUOutletStatusVMTable 1 } OutletStatusVMEntry ::= SEQUENCE { sPDUOutletStatusVMIndex INTEGER, sPDUOutletStatusVMName DisplayString, sPDUOutletStatusVMOutletIndex INTEGER, sPDUOutletStatusVMOutletName DisplayString, sPDUOutletStatusVMOutletState INTEGER, sPDUOutletStatusVMCommandPending INTEGER } sPDUOutletStatusVMIndex OBJECT-TYPE SYNTAX INTEGER ACCESS read-only STATUS mandatory DESCRIPTION "The index to the MasterSwitch VM." ::= { sPDUOutletStatusVMEntry 1 } sPDUOutletStatusVMName OBJECT-TYPE SYNTAX DisplayString ACCESS read-only STATUS mandatory DESCRIPTION "The name of the MasterSwitch VM. Maximum size is 23 characters." ::= { sPDUOutletStatusVMEntry 2 } sPDUOutletStatusVMOutletIndex OBJECT-TYPE SYNTAX INTEGER ACCESS read-only STATUS mandatory DESCRIPTION "The index to the outlet entry." ::= { sPDUOutletStatusVMEntry 3 } sPDUOutletStatusVMOutletName OBJECT-TYPE SYNTAX DisplayString ACCESS read-only STATUS mandatory DESCRIPTION "The name of the outlet. Maximum size is 23 characters." ::= { sPDUOutletStatusVMEntry 4 } sPDUOutletStatusVMOutletState OBJECT-TYPE SYNTAX INTEGER { outletStatusVMOn (1), outletStatusVMOff (2) } ACCESS read-only STATUS mandatory DESCRIPTION "Getting this variable will return the outlet state. If the outlet is on, the outletStatusOnVM (1) value will be returned. If the outlet is off, the outletStatusOffVM (2) value will be returned. " ::= { sPDUOutletStatusVMEntry 5 } sPDUOutletStatusVMCommandPending OBJECT-TYPE SYNTAX INTEGER { outletStatusVMCommandPending (1), outletStatusVMNoCommandPending (2) } ACCESS read-only STATUS mandatory DESCRIPTION "Getting this variable will return the command pending state of the outlet. If a command is pending on the outlet, the outletStatusVMCommandPending (1) value will be returned. If there is not a command pending on the outlet, the outletStatusVMNoCommandPending (2) will be returned." ::= { sPDUOutletStatusVMEntry 6 } -- the sPDUIdentMSP group sPDUIdentMSPTableSize OBJECT-TYPE SYNTAX INTEGER ACCESS read-only STATUS mandatory DESCRIPTION "The number of MasterSwitch pluses controllable by this IP address." ::= { sPDUIdentMSP 1 } sPDUIdentMSPTable OBJECT-TYPE SYNTAX SEQUENCE OF IdentMSPEntry ACCESS not-accessible STATUS mandatory DESCRIPTION "Allows for query of the individual MasterSwitch pluses. The number of entries is contained in the sPDUIdentMSPTableSize OID." ::= { sPDUIdentMSP 2 } sPDUIdentMSPEntry OBJECT-TYPE SYNTAX IdentMSPEntry ACCESS not-accessible STATUS mandatory DESCRIPTION "The MasterSwitch pluses to query." INDEX { sPDUIdentMSPIndex} ::= { sPDUIdentMSPTable 1 } IdentMSPEntry ::= SEQUENCE { sPDUIdentMSPIndex INTEGER, sPDUIdentNameMSP DisplayString, sPDUIdentHardwareRevMSP DisplayString, sPDUIdentFirmwareRevMSP DisplayString, sPDUIdentDateOfManufactureMSP DisplayString, sPDUIdentModelNumberMSP DisplayString, sPDUIdentSerialNumberMSP DisplayString } sPDUIdentMSPIndex OBJECT-TYPE SYNTAX INTEGER ACCESS read-only STATUS mandatory DESCRIPTION "The index to the MasterSwitch plus entry." ::= { sPDUIdentMSPEntry 1 } sPDUIdentNameMSP OBJECT-TYPE SYNTAX DisplayString ACCESS read-only STATUS mandatory DESCRIPTION "The name of the MasterSwitch plus. The maximum value is 23 characters. The name is set by using the sPDUMasterConfigMSPName OID." ::= { sPDUIdentMSPEntry 2 } sPDUIdentHardwareRevMSP OBJECT-TYPE SYNTAX DisplayString ACCESS read-only STATUS mandatory DESCRIPTION "The hardware version of the MasterSwitch plus. This value is set at the factory." ::= { sPDUIdentMSPEntry 3 } sPDUIdentFirmwareRevMSP OBJECT-TYPE SYNTAX DisplayString ACCESS read-only STATUS mandatory DESCRIPTION "An 6-character ID string identifying the MasterSwitch plus firmware version. This value is set at the factory." ::= { sPDUIdentMSPEntry 4 } sPDUIdentDateOfManufactureMSP OBJECT-TYPE SYNTAX DisplayString ACCESS read-only STATUS mandatory DESCRIPTION "The date when the MasterSwitch plus was manufactured in mm/dd/yyyy format. This value is set at the factory. " ::= { sPDUIdentMSPEntry 5 } sPDUIdentModelNumberMSP OBJECT-TYPE SYNTAX DisplayString ACCESS read-only STATUS mandatory DESCRIPTION "A 17-character string identifying the model number of the MasterSwitch plus. This value is set at the factory." ::= { sPDUIdentMSPEntry 6 } sPDUIdentSerialNumberMSP OBJECT-TYPE SYNTAX DisplayString ACCESS read-only STATUS mandatory DESCRIPTION "A 17-character string identifying the serial number of the MasterSwitch plus. This value is set at the factory." ::= { sPDUIdentMSPEntry 7 } -- the sPDUMasterControlMSP group sPDUMasterControlMSPTableSize OBJECT-TYPE SYNTAX INTEGER ACCESS read-only STATUS mandatory DESCRIPTION "The number of MasterSwitch pluses controllable by this IP address." ::= { sPDUMasterControlMSP 1 } sPDUMasterControlMSPTable OBJECT-TYPE SYNTAX SEQUENCE OF MasterControlMSPEntry ACCESS not-accessible STATUS mandatory DESCRIPTION "Allows for control of the individual MasterSwitch pluses. The number of entries is contained in the sPDUMasterControlMSPTableSize OID." ::= { sPDUMasterControlMSP 2 } sPDUMasterControlMSPEntry OBJECT-TYPE SYNTAX MasterControlMSPEntry ACCESS not-accessible STATUS mandatory DESCRIPTION "The MasterSwitch pluses to control." INDEX { sPDUMasterControlMSPIndex} ::= { sPDUMasterControlMSPTable 1 } MasterControlMSPEntry ::= SEQUENCE { sPDUMasterControlMSPIndex INTEGER, sPDUMasterControlMSPName DisplayString, sPDUMasterControlMSPCommand INTEGER } sPDUMasterControlMSPIndex OBJECT-TYPE SYNTAX INTEGER ACCESS read-only STATUS mandatory DESCRIPTION "The index to the MasterSwitch plus entry." ::= { sPDUMasterControlMSPEntry 1 } sPDUMasterControlMSPName OBJECT-TYPE SYNTAX DisplayString ACCESS read-only STATUS mandatory DESCRIPTION "The name of the MasterSwitch plus. The maximum value is 23 characters. The name is set by using the sPDUMasterConfigMSPName OID." ::= { sPDUMasterControlMSPEntry 2 } sPDUMasterControlMSPCommand OBJECT-TYPE SYNTAX INTEGER { noCommandAllMSP (1), immediateAllOnMSP (2), sequencedAllOnMSP (3), immediateAllOffMSP (4), gracefulAllRebootMSP (5), immediateAllRebootMSP (6), gracefulAllShutdownMSP (7), overrideAllBatCapThreshMSP (8), cancelAllPendingCommandsMSP (9), restoreFactoryDefaultsMSP (10) } ACCESS read-write STATUS mandatory DESCRIPTION "Setting this OID to immediateAllOnMSP (2) will turn all outlets on immediately. Setting this OID to sequencedAllOnMSP (3) will turn all outlets on as defined by each outlet's sPDUOutletConfigMSPPowerOnDelay OID value. Setting this OID to immediateAllOffMSP (4) will turn all outlets off immediately. Setting this OID to gracefulAllRebootMSP (5) will reboot all outlets (after the device running PowerChute confirms shutdown) as defined by each outlet's sPDUOutletConfigMSPRebootDuration OID time value. Setting this OID to immediateAllRebootMSP (6) will reboot all outlets immediately. Setting this OID to gracefulAllShutdownMSP (7) will shutdown all outlets (after the device running PowerChute confirms shutdown) as defined by each outlet's sPDUOutletConfigMSPPowerOffDelay OID time value. Each outlet will then turn on after the sum of its sPDUOutletConfigMSPRestartDelay and sPDUOutletConfigMSPPowerOnDelay OID values. Setting this OID to overrideAllBatCapThreshMSP (8) will cause the outlet to ignore the Battery Capacity Threshold and proceed turning on the outlets as defined by each outlet's sPDUOutletConfigMSPPowerOnDelay OID value. Setting this OID to cancelAllPendingCommandsMSP (9) will cause all pending commands on the MasterSwitch plus to be canceled. Setting this OID to restoreFactoryDefaultsMSP (10) will cause the settings of the MasterSwitch plus to be restored to the factory defaults. Getting this OID will return the noCommandAllMSP (1) value." ::= { sPDUMasterControlMSPEntry 3 } -- the sPDUMasterConfigMSP group sPDUMasterConfigMSPTableSize OBJECT-TYPE SYNTAX INTEGER ACCESS read-only STATUS mandatory DESCRIPTION "The number of MasterSwitch pluses configurable by this IP address." ::= { sPDUMasterConfigMSP 1 } sPDUMasterConfigMSPTable OBJECT-TYPE SYNTAX SEQUENCE OF MasterConfigMSPEntry ACCESS not-accessible STATUS mandatory DESCRIPTION "Allows for configuration of the individual MasterSwitch pluses. The number of entries is contained in the sPDUMasterConfigMSPTableSize OID." ::= { sPDUMasterConfigMSP 2 } sPDUMasterConfigMSPEntry OBJECT-TYPE SYNTAX MasterConfigMSPEntry ACCESS not-accessible STATUS mandatory DESCRIPTION "The MasterSwitch pluses to configure." INDEX { sPDUMasterConfigMSPIndex} ::= { sPDUMasterConfigMSPTable 1 } MasterConfigMSPEntry ::= SEQUENCE { sPDUMasterConfigMSPIndex INTEGER, sPDUMasterConfigMSPName DisplayString, sPDUMasterConfigMSPPowerOnTimeDelay INTEGER, sPDUMasterConfigMSPManualButton INTEGER } sPDUMasterConfigMSPIndex OBJECT-TYPE SYNTAX INTEGER ACCESS read-only STATUS mandatory DESCRIPTION "The index to the MasterSwitch plus entry." ::= { sPDUMasterConfigMSPEntry 1 } sPDUMasterConfigMSPName OBJECT-TYPE SYNTAX DisplayString ACCESS read-write STATUS mandatory DESCRIPTION "The name of the MasterSwitch plus. Maximum size is 23 characters." ::= { sPDUMasterConfigMSPEntry 2 } sPDUMasterConfigMSPPowerOnTimeDelay OBJECT-TYPE SYNTAX INTEGER (0..9999) ACCESS read-write STATUS mandatory DESCRIPTION " The amount of delay, in seconds, between when power is provided to the MasterSwitch plus and when the MasterSwitch plus provides basic master power to the outlets. Allowed values are: 0 - 9999 seconds (0 - 2hrs, 46 mins, 39 secs). 0 indicates to apply power immediately." ::= { sPDUMasterConfigMSPEntry 3 } sPDUMasterConfigMSPManualButton OBJECT-TYPE SYNTAX INTEGER { manualButtonDisabled (1), manualButtonEnabled (2) } ACCESS read-write STATUS mandatory DESCRIPTION "Setting this OID to manualButtonDisabled (1) will disable the manual button on the MasterSwitch plus. Setting this OID to manualButtonEnabled (2) will enable the manual button on the MasterSwitch plus." ::= { sPDUMasterConfigMSPEntry 4 } -- the sPDUMasterStatusMSP group sPDUMasterStatusMSPTableSize OBJECT-TYPE SYNTAX INTEGER ACCESS read-only STATUS mandatory DESCRIPTION "The number of MasterSwitch pluses at this IP address." ::= { sPDUMasterStatusMSP 1 } sPDUMasterStatusMSPTable OBJECT-TYPE SYNTAX SEQUENCE OF MasterStatusMSPEntry ACCESS not-accessible STATUS mandatory DESCRIPTION "Allows for gathering of status from the individual MasterSwitch pluses. The number of entries is contained in the sPDUMasterStatusMSPTableSize OID." ::= { sPDUMasterStatusMSP 2 } sPDUMasterStatusMSPEntry OBJECT-TYPE SYNTAX MasterStatusMSPEntry ACCESS not-accessible STATUS mandatory DESCRIPTION "The MasterSwitch pluses to gather status from." INDEX { sPDUMasterStatusMSPIndex} ::= { sPDUMasterStatusMSPTable 1 } MasterStatusMSPEntry ::= SEQUENCE { sPDUMasterStatusMSPIndex INTEGER, sPDUMasterStatusMSPName DisplayString, sPDUMasterStatusMSPOutletCount INTEGER } sPDUMasterStatusMSPIndex OBJECT-TYPE SYNTAX INTEGER ACCESS read-only STATUS mandatory DESCRIPTION "The index to the MasterSwitch plus entry." ::= { sPDUMasterStatusMSPEntry 1 } sPDUMasterStatusMSPName OBJECT-TYPE SYNTAX DisplayString ACCESS read-only STATUS mandatory DESCRIPTION "The name of the MasterSwitch plus. The maximum value is 23 characters. The name is set by using the sPDUMasterConfigMSPName OID." ::= { sPDUMasterStatusMSPEntry 2 } sPDUMasterStatusMSPOutletCount OBJECT-TYPE SYNTAX INTEGER ACCESS read-only STATUS mandatory DESCRIPTION "Getting this OID will return the number of controllable outlets for this MasterSwitch plus." ::= { sPDUMasterStatusMSPEntry 3 } -- the sPDUOutletControlMSP group sPDUOutletControlMSPTable OBJECT-TYPE SYNTAX SEQUENCE OF OutletControlMSPEntry ACCESS not-accessible STATUS mandatory DESCRIPTION "Allows for control of individual outlet switches. The number of entries is contained in the sPDUMasterStatusMSPOutletCount OID." ::= { sPDUOutletControlMSP 1 } sPDUOutletControlMSPEntry OBJECT-TYPE SYNTAX OutletControlMSPEntry ACCESS not-accessible STATUS mandatory DESCRIPTION "The outlets to control." INDEX { sPDUOutletControlMSPIndex, sPDUOutletControlMSPOutletIndex } ::= { sPDUOutletControlMSPTable 1 } OutletControlMSPEntry ::= SEQUENCE { sPDUOutletControlMSPIndex INTEGER, sPDUOutletControlMSPName DisplayString, sPDUOutletControlMSPOutletIndex INTEGER, sPDUOutletControlMSPOutletName DisplayString, sPDUOutletControlMSPOutletCommand INTEGER } sPDUOutletControlMSPIndex OBJECT-TYPE SYNTAX INTEGER ACCESS read-only STATUS mandatory DESCRIPTION "The index to the MasterSwitch plus." ::= { sPDUOutletControlMSPEntry 1 } sPDUOutletControlMSPName OBJECT-TYPE SYNTAX DisplayString ACCESS read-only STATUS mandatory DESCRIPTION "The name of the MasterSwitch plus. The maximum value is 23 characters. The name is set by using the sPDUMasterConfigMSPName OID." ::= { sPDUOutletControlMSPEntry 2 } sPDUOutletControlMSPOutletIndex OBJECT-TYPE SYNTAX INTEGER ACCESS read-only STATUS mandatory DESCRIPTION "The index to the outlet entry." ::= { sPDUOutletControlMSPEntry 3 } sPDUOutletControlMSPOutletName OBJECT-TYPE SYNTAX DisplayString ACCESS read-only STATUS mandatory DESCRIPTION "The name of the outlet. The maximum size is 23 characters. The name is set by using the sPDUOutletConfigMSPallOutletName OID. This OID is provided for informational purposes only." ::= { sPDUOutletControlMSPEntry 4 } sPDUOutletControlMSPOutletCommand OBJECT-TYPE SYNTAX INTEGER { immediateOnMSP (1), delayedOnMSP (2), immediateOffMSP (3), gracefulRebootMSP (4), immediateRebootMSP (5), gracefulshutdownMSP (6), overrideBatCapThreshMSP (7), cancelPendingCommandMSP (8) } ACCESS read-write STATUS mandatory DESCRIPTION "Getting this variable will return the outlet state. If the outlet is on, the immediateOnMSP (1) value will be returned. If the outlet is off, the immediateOffMSP (3) value will be returned. Setting this variable to immediateOnMSP (1) will immediately turn the outlet on. Setting this variable to delayedOnMSP (2) will turn the outlet on after the sPDUOutletConfigMSPPowerOnDelay OID time has elapsed. Setting this variable to immediateOffMSP (3) will immediately turn the outlet off. Setting this variable to gracefulRebootMSP (4) will cause the outlet to wait for device confirmation (if applicable) and then turn the outlet off after the sPDUOutletConfigMSPPowerOffDelay OID time has elapsed. The outlet will then turn on after the sPDUOutletConfigMSPRebootDuration OID time has elapsed. Setting this variable to immediateRebootMSP (5) will immediately reboot the outlet. Setting this variable to gracefulshutdownMSP (6) will cause the outlet to wait for device confirmation (if applicable) and then turn the outlet off after the sPDUOutletConfigMSPPowerOffDelay OID time has elapsed. The outlet will then turn on after the sum of the sPDUOutletConfigMSPRestartTime OID time and the sPDUOutletConfigMSPPowerOnDelay OID time has elapsed. Setting this variable to overrideBatCapThreshMSP (7) will cause the outlet to ignore the Battery Capacity Threshold and proceed waiting on the sPDUOutletConfigMSPPowerOnDelay OID time before turning the outlet on. Setting this variable to cancelPendingCommandMSP (8) will cause any pending command to this outlet to be canceled." ::= { sPDUOutletControlMSPEntry 5 } -- the sPDUOutletConfigMSPall group sPDUOutletConfigMSPallTable OBJECT-TYPE SYNTAX SEQUENCE OF OutletConfigMSPallEntry ACCESS not-accessible STATUS mandatory DESCRIPTION "Allows for configuration of individual outlets. The number of entries is contained in the sPDUMasterStatusMSPOutletCount OID." ::= { sPDUOutletConfigMSPall 1 } sPDUOutletConfigMSPallEntry OBJECT-TYPE SYNTAX OutletConfigMSPallEntry ACCESS not-accessible STATUS mandatory DESCRIPTION "The outlets to configure." INDEX { sPDUOutletConfigMSPallIndex, sPDUOutletConfigMSPallOutletIndex } ::= { sPDUOutletConfigMSPallTable 1 } OutletConfigMSPallEntry ::= SEQUENCE { sPDUOutletConfigMSPallIndex INTEGER, sPDUOutletConfigMSPallName DisplayString, sPDUOutletConfigMSPallOutletIndex INTEGER, sPDUOutletConfigMSPallOutletName DisplayString, sPDUOutletConfigMSPallOutletCtrlMode INTEGER } sPDUOutletConfigMSPallIndex OBJECT-TYPE SYNTAX INTEGER ACCESS read-only STATUS mandatory DESCRIPTION "The index to the MasterSwitch plus." ::= { sPDUOutletConfigMSPallEntry 1 } sPDUOutletConfigMSPallName OBJECT-TYPE SYNTAX DisplayString ACCESS read-only STATUS mandatory DESCRIPTION "The name of the MasterSwitch plus. The maximum value is 23 characters. The name is set by using the sPDUMasterConfigMSPName OID." ::= { sPDUOutletConfigMSPallEntry 2 } sPDUOutletConfigMSPallOutletIndex OBJECT-TYPE SYNTAX INTEGER ACCESS read-only STATUS mandatory DESCRIPTION "The index to the outlet entry." ::= { sPDUOutletConfigMSPallEntry 3 } sPDUOutletConfigMSPallOutletName OBJECT-TYPE SYNTAX DisplayString ACCESS read-write STATUS mandatory DESCRIPTION "The name of the outlet. Maximum size is 23 characters." ::= { sPDUOutletConfigMSPallEntry 4 } sPDUOutletConfigMSPallOutletCtrlMode OBJECT-TYPE SYNTAX INTEGER { modeGracefulShutdown (1), modeAnnunciator (2) } ACCESS read-write STATUS mandatory DESCRIPTION "Setting this OID to modeGracefulShutdown (1) will put this outlet into the Graceful Shutdown control mode. Setting this OID to modeAnnunciator (2) will put this outlet into the Annunciator control mode." ::= { sPDUOutletConfigMSPallEntry 5 } -- the sPDUOutConfigMSPgs group sPDUOutletConfigMSPgsTable OBJECT-TYPE SYNTAX SEQUENCE OF OutletConfigMSPgsEntry ACCESS not-accessible STATUS mandatory DESCRIPTION "Allows for configuration of individual outlets. The number of entries is contained in the sPDUMasterStatusMSPOutletCount OID." ::= { sPDUOutletConfigMSPgs 1 } sPDUOutletConfigMSPgsEntry OBJECT-TYPE SYNTAX OutletConfigMSPgsEntry ACCESS not-accessible STATUS mandatory DESCRIPTION "The outlets to configure." INDEX { sPDUOutletConfigMSPgsIndex, sPDUOutletConfigMSPgsOutletIndex } ::= { sPDUOutletConfigMSPgsTable 1 } OutletConfigMSPgsEntry ::= SEQUENCE { sPDUOutletConfigMSPgsIndex INTEGER, sPDUOutletConfigMSPgsName DisplayString, sPDUOutletConfigMSPgsOutletIndex INTEGER, sPDUOutletConfigMSPgsOutletName DisplayString, sPDUOutletConfigMSPgsOutletCtrlMode INTEGER, sPDUOutletConfigMSPgsDeviceConfirm INTEGER, sPDUOutletConfigMSPgsLowBattWarning INTEGER, sPDUOutletConfigMSPgsLowBattMult INTEGER, sPDUOutletConfigMSPgsRestartDelay INTEGER, sPDUOutletConfigMSPgsPowerOnDelay INTEGER, sPDUOutletConfigMSPgsPowerOffDelay INTEGER, sPDUOutletConfigMSPgsBattCapThresh INTEGER, sPDUOutletConfigMSPgsRebootDuration INTEGER } sPDUOutletConfigMSPgsIndex OBJECT-TYPE SYNTAX INTEGER ACCESS read-only STATUS mandatory DESCRIPTION "The index to the MasterSwitch plus." ::= { sPDUOutletConfigMSPgsEntry 1 } sPDUOutletConfigMSPgsName OBJECT-TYPE SYNTAX DisplayString ACCESS read-only STATUS mandatory DESCRIPTION "The name of the MasterSwitch plus. The maximum value is 23 characters. The name is set by using the sPDUMasterConfigMSPName OID." ::= { sPDUOutletConfigMSPgsEntry 2 } sPDUOutletConfigMSPgsOutletIndex OBJECT-TYPE SYNTAX INTEGER ACCESS read-only STATUS mandatory DESCRIPTION "The index to the outlet entry." ::= { sPDUOutletConfigMSPgsEntry 3 } sPDUOutletConfigMSPgsOutletName OBJECT-TYPE SYNTAX DisplayString ACCESS read-only STATUS mandatory DESCRIPTION "The name of the outlet. The maximum size is 23 characters. The name is set by using the sPDUOutletConfigMSPallOutletName OID. This OID is provided for informational purposes only." ::= { sPDUOutletConfigMSPgsEntry 4 } sPDUOutletConfigMSPgsOutletCtrlMode OBJECT-TYPE SYNTAX INTEGER { modeGracefulShutdown (1), modeAnnunciator (2) } ACCESS read-only STATUS mandatory DESCRIPTION "The Control Mode of the outlet. This OID is provided for informational purposes only." ::= { sPDUOutletConfigMSPgsEntry 5 } sPDUOutletConfigMSPgsDeviceConfirm OBJECT-TYPE SYNTAX INTEGER { deviceConfirmNo (1), deviceConfirmYes (2) } ACCESS read-write STATUS mandatory DESCRIPTION "Setting this OID to deviceConfirmNo (1) cause the outlet to NOT wait for device confirmation while performing graceful operations. Setting this OID to deviceConfirmYes (2) cause the outlet to wait for device confirmation while performing graceful operations." ::= { sPDUOutletConfigMSPgsEntry 6 } sPDUOutletConfigMSPgsLowBattWarning OBJECT-TYPE SYNTAX INTEGER (-2..9999) ACCESS read-write STATUS mandatory DESCRIPTION " The amount of delay, in 6 second intervals, between when the UPS goes on battery and the power down sequence for the outlet is initiated. Allowed values are: -2 - Never initiate the power down sequence on low battery warning. -1 - Initiate power down sequence based on remaining runtime. 1 - 9999 six second intervals (6 secs - 16hrs, 39 mins, 54 secs). 0 indicates to immediately initiate power down sequence on low battery warning." ::= { sPDUOutletConfigMSPgsEntry 7 } sPDUOutletConfigMSPgsLowBattMult OBJECT-TYPE SYNTAX INTEGER (1..7) ACCESS read-write STATUS mandatory DESCRIPTION " Only applicable if sPDUOutletConfigMSPgsLowBattWarning OID is set to -1 (On Runtime Remaining). Allows you to set the value to stagger the shutdown sequence of the outlets. 1 provides the longest delay (the outlet to shutoff first), and 7 would provide the shortest delay (the outlet to shut off last). Allowed values are: 1 - 7." ::= { sPDUOutletConfigMSPgsEntry 8 } sPDUOutletConfigMSPgsRestartDelay OBJECT-TYPE SYNTAX INTEGER (-1..9999) ACCESS read-write STATUS mandatory DESCRIPTION " The amount of delay, in 6 minute intervals, between when the outlet is turned off and the outlet is turned back on when performing a Graceful Shutdown. Allowed values are: -1 - Never turn outlet back on after a Graceful shutdown. 0 - 9999 six minute intervals (0 - 999hrs, 54 mins)." ::= { sPDUOutletConfigMSPgsEntry 9 } sPDUOutletConfigMSPgsPowerOnDelay OBJECT-TYPE SYNTAX INTEGER (-1..9999) ACCESS read-write STATUS mandatory DESCRIPTION " The amount of delay, in seconds, between the UPS entering normal (on-line) state and the outlet being powered on. Allowed values are: -1 - Remain Off when the UPS enters the on-line state. 0 - 9999 seconds (0 - 2 hrs, 46 mins, 39 secs)." ::= { sPDUOutletConfigMSPgsEntry 10 } sPDUOutletConfigMSPgsPowerOffDelay OBJECT-TYPE SYNTAX INTEGER (0..9999) ACCESS read-write STATUS mandatory DESCRIPTION " The amount of delay, in seconds, between when the server shuts down and the outlet is powered off. Allowed values are: 0 - 9999 seconds (0 - 2 hrs, 46 mins, 39 secs)." ::= { sPDUOutletConfigMSPgsEntry 11 } sPDUOutletConfigMSPgsBattCapThresh OBJECT-TYPE SYNTAX INTEGER (0..100) ACCESS read-write STATUS mandatory DESCRIPTION " The minimum battery capacity, as a percent (0-100%), required of the UPS before an outlet will be allowed to power on. Allowed values are: 0 - 100 percent." ::= { sPDUOutletConfigMSPgsEntry 12 } sPDUOutletConfigMSPgsRebootDuration OBJECT-TYPE SYNTAX INTEGER (0..9999) ACCESS read-write STATUS mandatory DESCRIPTION " The amount of delay, in seconds, from outlet off until outlet on during a reboot. Allowed values are: 0 - 9999 seconds (0 - 2 hrs, 46 mins, 39 secs)." ::= { sPDUOutletConfigMSPgsEntry 13 } -- the sPDUOutConfigMSPannun group sPDUOutletConfigMSPannunTable OBJECT-TYPE SYNTAX SEQUENCE OF OutletConfigMSPannunEntry ACCESS not-accessible STATUS mandatory DESCRIPTION "Allows for configuration of individual outlets. The number of entries is contained in the sPDUMasterStatusMSPOutletCount OID." ::= { sPDUOutletConfigMSPannun 1 } sPDUOutletConfigMSPannunEntry OBJECT-TYPE SYNTAX OutletConfigMSPannunEntry ACCESS not-accessible STATUS mandatory DESCRIPTION "The outlets to configure." INDEX { sPDUOutletConfigMSPannunIndex, sPDUOutletConfigMSPannunOutletIndex } ::= { sPDUOutletConfigMSPannunTable 1 } OutletConfigMSPannunEntry ::= SEQUENCE { sPDUOutletConfigMSPannunIndex INTEGER, sPDUOutletConfigMSPannunName DisplayString, sPDUOutletConfigMSPannunOutletIndex INTEGER, sPDUOutletConfigMSPannunOutletName DisplayString, sPDUOutletConfigMSPannunOutletCtrlMode INTEGER, sPDUOutletConfigMSPannunInitialState INTEGER, sPDUOutletConfigMSPannunAlarmActionDly INTEGER } sPDUOutletConfigMSPannunIndex OBJECT-TYPE SYNTAX INTEGER ACCESS read-only STATUS mandatory DESCRIPTION "The index to the MasterSwitch plus." ::= { sPDUOutletConfigMSPannunEntry 1 } sPDUOutletConfigMSPannunName OBJECT-TYPE SYNTAX DisplayString ACCESS read-only STATUS mandatory DESCRIPTION "The name of the MasterSwitch plus. The maximum value is 23 characters. The name is set by using the sPDUMasterConfigMSPName OID." ::= { sPDUOutletConfigMSPannunEntry 2 } sPDUOutletConfigMSPannunOutletIndex OBJECT-TYPE SYNTAX INTEGER ACCESS read-only STATUS mandatory DESCRIPTION "The index to the outlet entry." ::= { sPDUOutletConfigMSPannunEntry 3 } sPDUOutletConfigMSPannunOutletName OBJECT-TYPE SYNTAX DisplayString ACCESS read-only STATUS mandatory DESCRIPTION "The name of the outlet. The maximum size is 23 characters. The name is set by using the sPDUOutletConfigMSPallOutletName OID. This OID is provided for informational purposes only." ::= { sPDUOutletConfigMSPannunEntry 4 } sPDUOutletConfigMSPannunOutletCtrlMode OBJECT-TYPE SYNTAX INTEGER { modeGracefulShutdown (1), modeAnnunciator (2) } ACCESS read-only STATUS mandatory DESCRIPTION "The Control Mode of the outlet. This OID is provided for informational purposes only." ::= { sPDUOutletConfigMSPannunEntry 5 } sPDUOutletConfigMSPannunInitialState OBJECT-TYPE SYNTAX INTEGER { initialStateOff (1), initialStateOn (2) } ACCESS read-write STATUS mandatory DESCRIPTION "Setting this OID to initialStateOff (1) causes the outlet to default to off when in the non-alarmed condition. Setting this OID to initialStateOn (2) causes the outlet to default to on when in the non-alarmed condition." ::= { sPDUOutletConfigMSPannunEntry 6 } sPDUOutletConfigMSPannunAlarmActionDly OBJECT-TYPE SYNTAX INTEGER (0..9999) ACCESS read-write STATUS mandatory DESCRIPTION " The amount of time, in seconds, that an enabled Measure-UPS alarm must be asserted before an alarm condition is recognized. Allowed values are: 0 - 9999 seconds (0 - 2 hrs, 46 mins, 39 secs)." ::= { sPDUOutletConfigMSPannunEntry 7 } -- the sPDUOutConfigMSPmups group sPDUOutletConfigMSPmupsTable OBJECT-TYPE SYNTAX SEQUENCE OF OutletConfigMSPmupsEntry ACCESS not-accessible STATUS mandatory DESCRIPTION "Allows for configuration of individual outlets. The number of entries is contained in the sPDUMasterStatusMSPOutletCount OID." ::= { sPDUOutletConfigMSPmups 1 } sPDUOutletConfigMSPmupsEntry OBJECT-TYPE SYNTAX OutletConfigMSPmupsEntry ACCESS not-accessible STATUS mandatory DESCRIPTION "The outlets to configure." INDEX { sPDUOutletConfigMSPmupsIndex, sPDUOutletConfigMSPmupsOutletIndex } ::= { sPDUOutletConfigMSPmupsTable 1 } OutletConfigMSPmupsEntry ::= SEQUENCE { sPDUOutletConfigMSPmupsIndex INTEGER, sPDUOutletConfigMSPmupsName DisplayString, sPDUOutletConfigMSPmupsOutletIndex INTEGER, sPDUOutletConfigMSPmupsOutletName DisplayString, sPDUOutletConfigMSPmupsZone1 INTEGER, sPDUOutletConfigMSPmupsZone2 INTEGER, sPDUOutletConfigMSPmupsZone3 INTEGER, sPDUOutletConfigMSPmupsZone4 INTEGER, sPDUOutletConfigMSPmupsP1LowHum INTEGER, sPDUOutletConfigMSPmupsP1HiHum INTEGER, sPDUOutletConfigMSPmupsP1LowTemp INTEGER, sPDUOutletConfigMSPmupsP1HiTemp INTEGER, sPDUOutletConfigMSPmupsP2LowHum INTEGER, sPDUOutletConfigMSPmupsP2HiHum INTEGER, sPDUOutletConfigMSPmupsP2LowTemp INTEGER, sPDUOutletConfigMSPmupsP2HiTemp INTEGER } sPDUOutletConfigMSPmupsIndex OBJECT-TYPE SYNTAX INTEGER ACCESS read-only STATUS mandatory DESCRIPTION "The index to the MasterSwitch plus." ::= { sPDUOutletConfigMSPmupsEntry 1 } sPDUOutletConfigMSPmupsName OBJECT-TYPE SYNTAX DisplayString ACCESS read-only STATUS mandatory DESCRIPTION "The name of the MasterSwitch plus. The maximum value is 23 characters. The name is set by using the sPDUMasterConfigMSPName OID." ::= { sPDUOutletConfigMSPmupsEntry 2 } sPDUOutletConfigMSPmupsOutletIndex OBJECT-TYPE SYNTAX INTEGER ACCESS read-only STATUS mandatory DESCRIPTION "The index to the outlet entry." ::= { sPDUOutletConfigMSPmupsEntry 3 } sPDUOutletConfigMSPmupsOutletName OBJECT-TYPE SYNTAX DisplayString ACCESS read-only STATUS mandatory DESCRIPTION "The name of the outlet. The maximum size is 23 characters. The name is set by using the sPDUOutletConfigMSPallOutletName OID. This OID is provided for informational purposes only." ::= { sPDUOutletConfigMSPmupsEntry 4 } sPDUOutletConfigMSPmupsZone1 OBJECT-TYPE SYNTAX INTEGER { disableAlarm (1), enableAlarm (2) } ACCESS read-write STATUS mandatory DESCRIPTION "Setting this OID to disableAlarm (1) disables the Zone 1 alarm for this outlet. Setting this OID to enableAlarm (2) enables the Zone 1 alarm for this outlet." ::= { sPDUOutletConfigMSPmupsEntry 5 } sPDUOutletConfigMSPmupsZone2 OBJECT-TYPE SYNTAX INTEGER { disableAlarm (1), enableAlarm (2) } ACCESS read-write STATUS mandatory DESCRIPTION "Setting this OID to disableAlarm (1) disables the Zone 2 alarm for this outlet. Setting this OID to enableAlarm (2) enables the Zone 2 alarm for this outlet." ::= { sPDUOutletConfigMSPmupsEntry 6 } sPDUOutletConfigMSPmupsZone3 OBJECT-TYPE SYNTAX INTEGER { disableAlarm (1), enableAlarm (2) } ACCESS read-write STATUS mandatory DESCRIPTION "Setting this OID to disableAlarm (1) disables the Zone 3 alarm for this outlet. Setting this OID to enableAlarm (2) enables the Zone 3 alarm for this outlet." ::= { sPDUOutletConfigMSPmupsEntry 7 } sPDUOutletConfigMSPmupsZone4 OBJECT-TYPE SYNTAX INTEGER { disableAlarm (1), enableAlarm (2) } ACCESS read-write STATUS mandatory DESCRIPTION "Setting this OID to disableAlarm (1) disables the Zone 4 alarm for this outlet. Setting this OID to enableAlarm (2) enables the Zone 4 alarm for this outlet." ::= { sPDUOutletConfigMSPmupsEntry 8 } sPDUOutletConfigMSPmupsP1LowHum OBJECT-TYPE SYNTAX INTEGER { disableAlarm (1), enableAlarm (2) } ACCESS read-write STATUS mandatory DESCRIPTION "Setting this OID to disableAlarm (1) disables the Probe 1 low humidity alarm for this outlet. Setting this OID to enableAlarm (2) enables the Probe 1 low humidity alarm for this outlet." ::= { sPDUOutletConfigMSPmupsEntry 9 } sPDUOutletConfigMSPmupsP1HiHum OBJECT-TYPE SYNTAX INTEGER { disableAlarm (1), enableAlarm (2) } ACCESS read-write STATUS mandatory DESCRIPTION "Setting this OID to disableAlarm (1) disables the Probe 1 high humidity alarm for this outlet. Setting this OID to enableAlarm (2) enables the Probe 1 high humidity alarm for this outlet." ::= { sPDUOutletConfigMSPmupsEntry 10 } sPDUOutletConfigMSPmupsP1LowTemp OBJECT-TYPE SYNTAX INTEGER { disableAlarm (1), enableAlarm (2) } ACCESS read-write STATUS mandatory DESCRIPTION "Setting this OID to disableAlarm (1) disables the Probe 1 low temperature alarm for this outlet. Setting this OID to enableAlarm (2) enables the Probe 1 low temperature alarm for this outlet." ::= { sPDUOutletConfigMSPmupsEntry 11 } sPDUOutletConfigMSPmupsP1HiTemp OBJECT-TYPE SYNTAX INTEGER { disableAlarm (1), enableAlarm (2) } ACCESS read-write STATUS mandatory DESCRIPTION "Setting this OID to disableAlarm (1) disables the Probe 1 high temperature alarm for this outlet. Setting this OID to enableAlarm (2) enables the Probe 1 high temperature alarm for this outlet." ::= { sPDUOutletConfigMSPmupsEntry 12 } sPDUOutletConfigMSPmupsP2LowHum OBJECT-TYPE SYNTAX INTEGER { disableAlarm (1), enableAlarm (2) } ACCESS read-write STATUS mandatory DESCRIPTION "Setting this OID to disableAlarm (1) disables the Probe 2 low humidity alarm for this outlet. Setting this OID to enableAlarm (2) enables the Probe 2 low humidity alarm for this outlet." ::= { sPDUOutletConfigMSPmupsEntry 13 } sPDUOutletConfigMSPmupsP2HiHum OBJECT-TYPE SYNTAX INTEGER { disableAlarm (1), enableAlarm (2) } ACCESS read-write STATUS mandatory DESCRIPTION "Setting this OID to disableAlarm (1) disables the Probe 2 high humidity alarm for this outlet. Setting this OID to enableAlarm (2) enables the Probe 2 high humidity alarm for this outlet." ::= { sPDUOutletConfigMSPmupsEntry 14 } sPDUOutletConfigMSPmupsP2LowTemp OBJECT-TYPE SYNTAX INTEGER { disableAlarm (1), enableAlarm (2) } ACCESS read-write STATUS mandatory DESCRIPTION "Setting this OID to disableAlarm (1) disables the Probe 2 low temperature alarm for this outlet. Setting this OID to enableAlarm (2) enables the Probe 2 low temperature alarm for this outlet." ::= { sPDUOutletConfigMSPmupsEntry 15 } sPDUOutletConfigMSPmupsP2HiTemp OBJECT-TYPE SYNTAX INTEGER { disableAlarm (1), enableAlarm (2) } ACCESS read-write STATUS mandatory DESCRIPTION "Setting this OID to disableAlarm (1) disables the Probe 2 high temperature alarm for this outlet. Setting this OID to enableAlarm (2) enables the Probe 2 high temperature alarm for this outlet." ::= { sPDUOutletConfigMSPmupsEntry 16 } -- the sPDUOutletStatusMSP group sPDUOutletStatusMSPTable OBJECT-TYPE SYNTAX SEQUENCE OF OutletStatusMSPEntry ACCESS not-accessible STATUS mandatory DESCRIPTION "Allows for getting of status of individual outlets. The number of entries is contained in the sPDUMasterStatusOutletCount OID." ::= { sPDUOutletStatusMSP 1 } sPDUOutletStatusMSPEntry OBJECT-TYPE SYNTAX OutletStatusMSPEntry ACCESS not-accessible STATUS mandatory DESCRIPTION "The outlets to gather status from." INDEX { sPDUOutletStatusMSPIndex, sPDUOutletStatusMSPOutletIndex } ::= { sPDUOutletStatusMSPTable 1 } OutletStatusMSPEntry ::= SEQUENCE { sPDUOutletStatusMSPIndex INTEGER, sPDUOutletStatusMSPName DisplayString, sPDUOutletStatusMSPOutletIndex INTEGER, sPDUOutletStatusMSPOutletName DisplayString, sPDUOutletStatusMSPOutletState INTEGER, sPDUOutletStatusMSPCommandPending INTEGER, sPDUOutletStatusMSPOutletCtrlMode INTEGER } sPDUOutletStatusMSPIndex OBJECT-TYPE SYNTAX INTEGER ACCESS read-only STATUS mandatory DESCRIPTION "The index to the MasterSwitch MSP." ::= { sPDUOutletStatusMSPEntry 1 } sPDUOutletStatusMSPName OBJECT-TYPE SYNTAX DisplayString ACCESS read-only STATUS mandatory DESCRIPTION "The name of the MasterSwitch plus. The maximum value is 23 characters. The name is set by using the sPDUMasterConfigMSPName OID." ::= { sPDUOutletStatusMSPEntry 2 } sPDUOutletStatusMSPOutletIndex OBJECT-TYPE SYNTAX INTEGER ACCESS read-only STATUS mandatory DESCRIPTION "The index to the outlet entry." ::= { sPDUOutletStatusMSPEntry 3 } sPDUOutletStatusMSPOutletName OBJECT-TYPE SYNTAX DisplayString ACCESS read-only STATUS mandatory DESCRIPTION "The name of the outlet. The maximum size is 23 characters. The name is set by using the sPDUOutletConfigMSPallOutletName OID. This OID is provided for informational purposes only." ::= { sPDUOutletStatusMSPEntry 4 } sPDUOutletStatusMSPOutletState OBJECT-TYPE SYNTAX INTEGER { outletStatusMSPOn (1), outletStatusMSPOff (2) } ACCESS read-only STATUS mandatory DESCRIPTION "Getting this variable will return the outlet state. If the outlet is on, the outletStatusMSPOn (1) value will be returned. If the outlet is off, the outletStatusMSPOff (2) value will be returned. " ::= { sPDUOutletStatusMSPEntry 5 } sPDUOutletStatusMSPCommandPending OBJECT-TYPE SYNTAX INTEGER { outletStatusMSPCommandPending (1), outletStatusMSPNoCommandPending (2) } ACCESS read-only STATUS mandatory DESCRIPTION "Getting this variable will return the command pending state of the outlet. If a command is pending on the outlet, the outletStatusMSPCommandPending (1) value will be returned. If there is not a command pending on the outlet, the outletStatusMSPNoCommandPending (2) will be returned." ::= { sPDUOutletStatusMSPEntry 6 } sPDUOutletStatusMSPOutletCtrlMode OBJECT-TYPE SYNTAX INTEGER { modeGracefulShutdown (1), modeAnnunciator (2) } ACCESS read-only STATUS mandatory DESCRIPTION "The Control Mode of the outlet. This OID is provided for informational purposes only." ::= { sPDUOutletStatusMSPEntry 7 } -- the rPDUIdent group rPDUIdentName OBJECT-TYPE SYNTAX DisplayString ACCESS read-write STATUS mandatory DESCRIPTION "The name of the Rack PDU. The maximum string size is device dependent." ::= { rPDUIdent 1 } rPDUIdentHardwareRev OBJECT-TYPE SYNTAX DisplayString ACCESS read-only STATUS mandatory DESCRIPTION "The hardware revision of the Rack PDU. This value is set at the factory." ::= { rPDUIdent 2 } rPDUIdentFirmwareRev OBJECT-TYPE SYNTAX DisplayString ACCESS read-only STATUS mandatory DESCRIPTION "An 8-byte ID string identifying the Rack PDU firmware revision. This value is set at the factory." ::= { rPDUIdent 3 } rPDUIdentDateOfManufacture OBJECT-TYPE SYNTAX DisplayString ACCESS read-only STATUS mandatory DESCRIPTION "The date when the Rack PDU was manufactured in mm/dd/yy format. This value is set at the factory. The year 2000 will be represented by 00." ::= { rPDUIdent 4 } rPDUIdentModelNumber OBJECT-TYPE SYNTAX DisplayString ACCESS read-only STATUS mandatory DESCRIPTION "A 10-character string identifying the model number of the Rack PDU. This value is set at the factory." ::= { rPDUIdent 5 } rPDUIdentSerialNumber OBJECT-TYPE SYNTAX DisplayString ACCESS read-only STATUS mandatory DESCRIPTION "A 12-character string identifying the serial number of the Rack PDU. This value is set at the factory." ::= { rPDUIdent 6 } rPDUIdentDeviceRating OBJECT-TYPE SYNTAX INTEGER ACCESS read-only STATUS mandatory DESCRIPTION "Getting this OID will return the electrical rating of the device." ::= { rPDUIdent 7 } rPDUIdentDeviceNumOutlets OBJECT-TYPE SYNTAX INTEGER ACCESS read-only STATUS mandatory DESCRIPTION "Getting this OID will return the number of outlets contained in the device." ::= { rPDUIdent 8 } rPDUIdentDeviceNumPhases OBJECT-TYPE SYNTAX INTEGER ACCESS read-only STATUS mandatory DESCRIPTION "Getting this OID will return the number of phases supported by the device." ::= { rPDUIdent 9 } rPDUIdentDeviceNumBreakers OBJECT-TYPE SYNTAX INTEGER ACCESS read-only STATUS mandatory DESCRIPTION "Getting this OID will return the number of circuit breakers supported by the device. This is the same as the number of banks of outlets." ::= { rPDUIdent 10 } rPDUIdentDeviceBreakerRating OBJECT-TYPE SYNTAX INTEGER ACCESS read-only STATUS mandatory DESCRIPTION "Getting this OID will return rating of the circuit breakers on the device if it has any." ::= { rPDUIdent 11 } rPDUIdentDeviceOrientation OBJECT-TYPE SYNTAX INTEGER { orientHorizontal (1), orientVertical (2) } ACCESS read-only STATUS mandatory DESCRIPTION "Getting this OID will return the intended physical orientation of the device. OrientHorizonatal(1) indicates Horizontal. OrientVertical(2) indicates Vertical." ::= { rPDUIdent 12 } rPDUIdentDeviceOutletLayout OBJECT-TYPE SYNTAX INTEGER { seqPhaseToNeutral (1), seqPhaseToPhase (2), seqPhToNeu21PhToPh (3), seqPhToPhGrouped (4) } ACCESS read-only STATUS mandatory DESCRIPTION "Getting this OID will return outlet layout for the device. SeqPhaseToNeutral(1) indicates outlet layout as follows: 1:1-N,2:2-N,3:3-N,4:1-N,5:2-N,... SeqPhaseToPhase(2) indicates outlet layout as follows: 1:1-2,2:2-3,3:3-1,4:1-2,5:2-3,... SeqPhToNeu21PhToPh(3) indicates outlet layout as follows: 1:1-N,2:2-N...21:3-N,22:1-2,23:2-3,24:3-1,... SeqPhToPhGrouped(4) indicates outlet layout as follows: Otlts1-8::(3-1),Otlts9-16::(2-3),Otlts17-24::(1-2)." ::= { rPDUIdent 13 } -- the rPDULoadDevice group rPDULoadDevMaxPhaseLoad OBJECT-TYPE SYNTAX INTEGER ACCESS read-only STATUS mandatory DESCRIPTION "Getting this OID will return the maximum rated power that each phase of the Rack PDU can provide. It is represented in Amps." ::= { rPDULoadDevice 1 } rPDULoadDevNumPhases OBJECT-TYPE SYNTAX INTEGER ACCESS read-only STATUS mandatory DESCRIPTION "The number of phases available with this Rack PDU." ::= { rPDULoadDevice 2 } rPDULoadDevMaxBankLoad OBJECT-TYPE SYNTAX INTEGER ACCESS read-only STATUS mandatory DESCRIPTION "Getting this OID will return the maximum rated power that each bank of the Rack PDU can provide. It is represented in Amps. 0 will be returned if the device does not have any banks." ::= { rPDULoadDevice 3 } rPDULoadDevNumBanks OBJECT-TYPE SYNTAX INTEGER ACCESS read-only STATUS mandatory DESCRIPTION "The number of banks of outlets available with this Rack PDU. A bank of outlets has a unique circuit breaker for a subset of the total number of outlets on the rPDU." ::= { rPDULoadDevice 4 } -- the rPDULoadPhaseConfig group rPDULoadPhaseConfigTable OBJECT-TYPE SYNTAX SEQUENCE OF LoadPhaseConfigEntry ACCESS not-accessible STATUS mandatory DESCRIPTION "Allows for configuration of each Rack PDU phase. The number of entries is contained in the rPDULoadDevNumPhases OID." ::= { rPDULoadPhaseConfig 1 } rPDULoadPhaseConfigEntry OBJECT-TYPE SYNTAX LoadPhaseConfigEntry ACCESS not-accessible STATUS mandatory DESCRIPTION "The Rack PDU phase to configure." INDEX { rPDULoadPhaseConfigIndex} ::= { rPDULoadPhaseConfigTable 1 } LoadPhaseConfigEntry ::= SEQUENCE { rPDULoadPhaseConfigIndex INTEGER, rPDULoadPhaseConfigLowLoadThreshold INTEGER, rPDULoadPhaseConfigNearOverloadThreshold INTEGER, rPDULoadPhaseConfigOverloadThreshold INTEGER } rPDULoadPhaseConfigIndex OBJECT-TYPE SYNTAX INTEGER { phase1 (1), phase2 (2), phase3 (3) } ACCESS read-only STATUS mandatory DESCRIPTION "The index to the Rack PDU phase entry." ::= { rPDULoadPhaseConfigEntry 1 } rPDULoadPhaseConfigLowLoadThreshold OBJECT-TYPE SYNTAX INTEGER ACCESS read-write STATUS mandatory DESCRIPTION "A threshold that indicates the power consumption of the load is nearing a low consumption condition. It is represented in amps. A warning will be issued when the load is less than the threshold value. A threshold value of 0 amps effectively disables this warning. Maximum value must be less than the value returned by the rPDULoadPhaseConfigNearOverloadThreshold OID." ::= { rPDULoadPhaseConfigEntry 2 } rPDULoadPhaseConfigNearOverloadThreshold OBJECT-TYPE SYNTAX INTEGER ACCESS read-write STATUS mandatory DESCRIPTION "A threshold that indicates the power consumption of the load is nearing an overload condition. It is represented in amps. A warning will be issued when the load is greater than or equal to the threshold value. Minimum value must be greater than the value returned by the rPDULoadPhaseConfigLowLoadThreshold OID. Maximum value must be less than or equal to the value returned by the rPDULoadPhaseConfigOverloadThreshold OID." ::= { rPDULoadPhaseConfigEntry 3 } rPDULoadPhaseConfigOverloadThreshold OBJECT-TYPE SYNTAX INTEGER ACCESS read-write STATUS mandatory DESCRIPTION "A threshold that indicates the power consumption of the load has entered an overload condition. It is represented in amps. A warning will be issued when the load is greater than or equal to the threshold value. Minimum value must be greater than or equal to the value returned by the rPDULoadPhaseConfigNearOverloadThreshold OID. Maximum value must be less than or equal to the value returned by the rPDULoadDevMaxPhaseLoad OID." ::= { rPDULoadPhaseConfigEntry 4 } -- the rPDULoadStatus group rPDULoadStatusTable OBJECT-TYPE SYNTAX SEQUENCE OF LoadStatusEntry ACCESS not-accessible STATUS mandatory DESCRIPTION "Allows for getting of status of each Rack PDU phase/bank. The number of entries is calculated by adding the number of phases (rPDULoadDevNumPhases OID) and the number of banks of outlets (rPDULoadDevNumBanks) Number of entries = #phases + #banks. NOTE: If a device has phase and bank information, all phase information shall preceed the bank information." ::= { rPDULoadStatus 1 } rPDULoadStatusEntry OBJECT-TYPE SYNTAX LoadStatusEntry ACCESS not-accessible STATUS mandatory DESCRIPTION "The Rack PDU phase/bank to gather status from." INDEX { rPDULoadStatusIndex} ::= { rPDULoadStatusTable 1 } LoadStatusEntry ::= SEQUENCE { rPDULoadStatusIndex INTEGER, rPDULoadStatusLoad Gauge, rPDULoadStatusLoadState INTEGER, rPDULoadStatusPhaseNumber INTEGER, rPDULoadStatusBankNumber INTEGER } rPDULoadStatusIndex OBJECT-TYPE SYNTAX INTEGER ACCESS read-only STATUS mandatory DESCRIPTION "The index to the Rack PDU phase/bank entry. All phase information will preceed any bank information" ::= { rPDULoadStatusEntry 1 } rPDULoadStatusLoad OBJECT-TYPE SYNTAX Gauge ACCESS read-only STATUS mandatory DESCRIPTION "Getting this OID will return the phase/bank load measured in tenths of amps." ::= { rPDULoadStatusEntry 2 } rPDULoadStatusLoadState OBJECT-TYPE SYNTAX INTEGER { phaseLoadNormal (1), phaseLoadLow (2), phaseLoadNearOverload (3), phaseLoadOverload (4) } ACCESS read-only STATUS mandatory DESCRIPTION "Getting this OID will return the phase/bank load state. phaseLoadNormal(1) indicates that the phase/bank is operating properly within the rPDULoadConfigLowLoadThreshold and rPDULoadConfigNearOverloadThreshold OID values. phaseLoadLow(2) indicates that the phase/bank load has dropped below the rPDULoadConfigLowLoadThreshold OID value. An SNMP trap will occur when this state is entered or cleared. phaseLoadNearOverload(3) indicates that the phase/bank load is greater than or equal to the rPDULoadConfigNearOverloadThreshold OID value. An SNMP trap will occur when this state is entered or cleared. phaseLoadOverload(4) indicates that the phase/bank load is greater than or equal to the rPDULoadConfigOverloadThreshold OID value. An SNMP trap will occur when this state is entered or cleared." ::= { rPDULoadStatusEntry 3 } rPDULoadStatusPhaseNumber OBJECT-TYPE SYNTAX INTEGER ACCESS read-only STATUS mandatory DESCRIPTION "The phase number to which this record refers. A value of 0 will be returned if this is bank related information." ::= { rPDULoadStatusEntry 4 } rPDULoadStatusBankNumber OBJECT-TYPE SYNTAX INTEGER ACCESS read-only STATUS mandatory DESCRIPTION "The bank number to which this record refers. A value of 0 will be returned if this is phase related information." ::= { rPDULoadStatusEntry 5 } -- the rPDULoadBankConfig group rPDULoadBankConfigTable OBJECT-TYPE SYNTAX SEQUENCE OF LoadBankConfigEntry ACCESS not-accessible STATUS mandatory DESCRIPTION "Allows for configuration of each Rack PDU bank. The number of entries is contained in the rPDULoadDevNumBanks OID." ::= { rPDULoadBankConfig 1 } rPDULoadBankConfigEntry OBJECT-TYPE SYNTAX LoadBankConfigEntry ACCESS not-accessible STATUS mandatory DESCRIPTION "The Rack PDU bank to configure." INDEX { rPDULoadBankConfigIndex} ::= { rPDULoadBankConfigTable 1 } LoadBankConfigEntry ::= SEQUENCE { rPDULoadBankConfigIndex INTEGER, rPDULoadBankConfigLowLoadThreshold INTEGER, rPDULoadBankConfigNearOverloadThreshold INTEGER, rPDULoadBankConfigOverloadThreshold INTEGER } rPDULoadBankConfigIndex OBJECT-TYPE SYNTAX INTEGER ACCESS read-only STATUS mandatory DESCRIPTION "The index to the Rack PDU bank entry." ::= { rPDULoadBankConfigEntry 1 } rPDULoadBankConfigLowLoadThreshold OBJECT-TYPE SYNTAX INTEGER ACCESS read-write STATUS mandatory DESCRIPTION "A threshold that indicates the power consumption of the load is nearing a low consumption condition. It is represented in amps. A warning will be issued when the load is less than the threshold value. A threshold value of 0 amps effectively disables this warning. Maximum value must be less than the value returned by the rPDULoadBankConfigNearOverloadThreshold OID. -1 will be returned if the device has no banks." ::= { rPDULoadBankConfigEntry 2 } rPDULoadBankConfigNearOverloadThreshold OBJECT-TYPE SYNTAX INTEGER ACCESS read-write STATUS mandatory DESCRIPTION "A threshold that indicates the power consumption of the load is nearing an overload condition. It is represented in amps. A warning will be issued when the load is greater than or equal to the threshold value. Minimum value must be greater than the value returned by the rPDULoadBankConfigLowLoadThreshold OID. Maximum value must be less than or equal to the value returned by the rPDULoadBankConfigOverloadThreshold OID. -1 will be returned if the device has no banks." ::= { rPDULoadBankConfigEntry 3 } rPDULoadBankConfigOverloadThreshold OBJECT-TYPE SYNTAX INTEGER ACCESS read-write STATUS mandatory DESCRIPTION "A threshold that indicates the power consumption of the load has entered an overload condition. It is represented in amps. A warning will be issued when the load is greater than or equal to the threshold value. Minimum value must be greater than or equal to the value returned by the rPDULoadBankConfigNearOverloadThreshold OID. Maximum value must be less than or equal to the value returned by the rPDULoadDevMaxBankLoad OID. -1 will be returned if the device has no banks." ::= { rPDULoadBankConfigEntry 4 } -- the rPDUOutletDevice group rPDUOutletDevCommand OBJECT-TYPE SYNTAX INTEGER { noCommandAll (1), immediateAllOn (2), immediateAllOff (3), immediateAllReboot (4), delayedAllOn (5), delayedAllOff (6), delayedAllReboot (7), cancelAllPendingCommands (8) } ACCESS read-write STATUS mandatory DESCRIPTION "Setting this OID to immediateAllOn (2) will turn all outlets on immediately. Setting this OID to immediateAllOff (3) will turn all outlets off immediately. Setting this OID to immediateAllReboot (4) will reboot all outlets immediately. Setting this OID to delayedAllOn (5) will turn all outlets on as defined by each outlet's rPDUOutletConfigPowerOnTime OID value. Setting this OID to delayedAllOff (6) will turn all outlets off as defined by each outlet's rPDUOutletConfigPowerOffTime OID value. Setting this OID to delayedAllReboot (7) will cause a delayedAllOff command to be performed. Once all outlets are off, the Switched Rack PDU will then delay the largest rPDUOutletConfigRebootDuration OID time, and then perform a delayedAllOn command. Setting this OID to cancelAllPendingCommands (8) will cause all pending commands on the Switched Rack PDU to be canceled. Getting this OID will return the noCommandAll (1) value." ::= { rPDUOutletDevice 1 } rPDUOutletDevColdstartDelay OBJECT-TYPE SYNTAX INTEGER ACCESS read-write STATUS mandatory DESCRIPTION "The amount of delay, in seconds, between when power is provided to the Switched Rack PDU and when the Switched Rack PDU provides basic master power to the outlets. Allowed values are: -1 - never apply power automatically. 0 - apply power immediately. 1 to 300 - delay up to 300 seconds (5 minutes)." ::= { rPDUOutletDevice 2 } rPDUOutletDevNumCntrlOutlets OBJECT-TYPE SYNTAX INTEGER ACCESS read-only STATUS mandatory DESCRIPTION "The number of controlled outlets on this Switched Rack PDU." ::= { rPDUOutletDevice 3 } rPDUOutletDevNumTotalOutlets OBJECT-TYPE SYNTAX INTEGER ACCESS read-only STATUS mandatory DESCRIPTION "The total number of outlets on this Rack PDU." ::= { rPDUOutletDevice 4 } -- the rPDUOutletPhase group rPDUOutletPhaseTable OBJECT-TYPE SYNTAX SEQUENCE OF OutletPhaseEntry ACCESS not-accessible STATUS mandatory DESCRIPTION "Allows for management of outlets on a per phase basis." ::= { rPDUOutletPhase 1 } rPDUOutletPhaseEntry OBJECT-TYPE SYNTAX OutletPhaseEntry ACCESS not-accessible STATUS mandatory DESCRIPTION "The phase to manage." INDEX { rPDUOutletPhaseIndex} ::= { rPDUOutletPhaseTable 1 } OutletPhaseEntry ::= SEQUENCE { rPDUOutletPhaseIndex INTEGER, rPDUOutletPhaseOverloadRestriction INTEGER } rPDUOutletPhaseIndex OBJECT-TYPE SYNTAX INTEGER { phase1 (1), phase2 (2), phase3 (3) } ACCESS read-only STATUS mandatory DESCRIPTION "The index to the Switched Rack PDU phase entry." ::= { rPDUOutletPhaseEntry 1 } rPDUOutletPhaseOverloadRestriction OBJECT-TYPE SYNTAX INTEGER { alwaysAllowTurnON (1), restrictOnNearOverload (2), restrictOnOverload (3) } ACCESS read-write STATUS mandatory DESCRIPTION "This OID controls the behavior of a Switched Rack PDU phase when an overload condition is possible and additional outlets are requested to be turned on. Setting this OID to alwaysAllowTurnON (1) will always allow the outlets on the corresponding phase to turn on. Setting this OID to restrictOnNearOverload (2) will not allow outlets on the corresponding phase to turn on if the rPDULoadConfigNearOverloadThreshold OID is exceeded. Setting this OID to restrictOnOverload (3) will not allow outlets on the corresponding phase to turn on if the rPDULoadConfigOverloadThreshold OID is exceeded." ::= { rPDUOutletPhaseEntry 2 } -- the rPDUOutletControl group rPDUOutletControlTable OBJECT-TYPE SYNTAX SEQUENCE OF RPDUOutletControlEntry ACCESS not-accessible STATUS mandatory DESCRIPTION "Allows for control of the individual outlets. The number of entries is contained in the rPDUOutletDevNumCntrlOutlets OID." ::= { rPDUOutletControl 1 } rPDUOutletControlEntry OBJECT-TYPE SYNTAX RPDUOutletControlEntry ACCESS not-accessible STATUS mandatory DESCRIPTION "The outlet to control." INDEX { rPDUOutletControlIndex} ::= { rPDUOutletControlTable 1 } RPDUOutletControlEntry ::= SEQUENCE { rPDUOutletControlIndex INTEGER, rPDUOutletControlOutletName DisplayString, rPDUOutletControlOutletPhase INTEGER, rPDUOutletControlOutletCommand INTEGER, rPDUOutletControlOutletBank INTEGER } rPDUOutletControlIndex OBJECT-TYPE SYNTAX INTEGER ACCESS read-only STATUS mandatory DESCRIPTION "The index to the outlet entry." ::= { rPDUOutletControlEntry 1 } rPDUOutletControlOutletName OBJECT-TYPE SYNTAX DisplayString ACCESS read-only STATUS mandatory DESCRIPTION "The name of the outlet. Maximum size is dependent on device. An error will be returned if the set request exceeds the max size. This OID is provided for informational purposes only." ::= { rPDUOutletControlEntry 2 } rPDUOutletControlOutletPhase OBJECT-TYPE SYNTAX INTEGER { phase1 (1), phase2 (2), phase3 (3), phase1-2 (4), phase2-3 (5), phase3-1 (6) } ACCESS read-only STATUS mandatory DESCRIPTION "The phase/s associated with this outlet. For single phase devices, this object will always return phase1(1). For 3-phase devices, this object will return phase1 (1), phase2 (2), or phase3 (3) for outlets tied to a single phase. For outlets tied to two phases, this object will return phase1-2 (4) for phases 1 and 2, phase2-3 (5) for phases 2 and 3, and phase3-1 (6) for phases 3 and 1." ::= { rPDUOutletControlEntry 3 } rPDUOutletControlOutletCommand OBJECT-TYPE SYNTAX INTEGER { immediateOn (1), immediateOff (2), immediateReboot (3), delayedOn (4), delayedOff (5), delayedReboot (6), cancelPendingCommand (7) } ACCESS read-write STATUS mandatory DESCRIPTION "Getting this variable will return the outlet state. If the outlet is on, the immediateOn (1) value will be returned. If the outlet is off, the immediateOff (2) value will be returned. Setting this variable to immediateOn (1) will immediately turn the outlet on. Setting this variable to immediateOff (2) will immediately turn the outlet off. Setting this variable to immediateReboot (3) will immediately reboot the outlet. Setting this variable to delayedOn (4) will turn the outlet on after the rPDUOutletConfigPowerOnTime OID time has elapsed. Setting this variable to delayedOff (5) will turn the outlet off after the rPDUOutletConfigPowerOffTime OID time has elapsed. Setting this variable to delayedReboot (6) will cause the Switched Rack PDU to perform a delayedOff command, wait the rPDUOutletConfigRebootDuration OID time, and then perform a delayedOn command. Setting this variable to cancelPendingCommand (7) will cause any pending command to this outlet to be canceled." ::= { rPDUOutletControlEntry 4 } rPDUOutletControlOutletBank OBJECT-TYPE SYNTAX INTEGER ACCESS read-only STATUS mandatory DESCRIPTION "The bank associated with this outlet." ::= { rPDUOutletControlEntry 5 } -- the rPDUOutletConfig group rPDUOutletConfigTable OBJECT-TYPE SYNTAX SEQUENCE OF RPDUOutletConfigEntry ACCESS not-accessible STATUS mandatory DESCRIPTION "Allows for configuration of individual outlets. The number of entries is contained in the rPDUOutletDevNumCntrlOutlets OID." ::= { rPDUOutletConfig 1 } rPDUOutletConfigEntry OBJECT-TYPE SYNTAX RPDUOutletConfigEntry ACCESS not-accessible STATUS mandatory DESCRIPTION "The outlet to configure." INDEX { rPDUOutletConfigIndex} ::= { rPDUOutletConfigTable 1 } RPDUOutletConfigEntry ::= SEQUENCE { rPDUOutletConfigIndex INTEGER, rPDUOutletConfigOutletName DisplayString, rPDUOutletConfigOutletPhase INTEGER, rPDUOutletConfigPowerOnTime INTEGER, rPDUOutletConfigPowerOffTime INTEGER, rPDUOutletConfigRebootDuration INTEGER, rPDUOutletConfigOutletBank INTEGER } rPDUOutletConfigIndex OBJECT-TYPE SYNTAX INTEGER ACCESS read-only STATUS mandatory DESCRIPTION "The index to the outlet entry." ::= { rPDUOutletConfigEntry 1 } rPDUOutletConfigOutletName OBJECT-TYPE SYNTAX DisplayString ACCESS read-write STATUS mandatory DESCRIPTION "The name of the outlet. Maximum size is dependent on device. An error will be returned if the set request exceeds the max size." ::= { rPDUOutletConfigEntry 2 } rPDUOutletConfigOutletPhase OBJECT-TYPE SYNTAX INTEGER { phase1 (1), phase2 (2), phase3 (3), phase1-2 (4), phase2-3 (5), phase3-1 (6) } ACCESS read-only STATUS mandatory DESCRIPTION "The phase/s associated with this outlet. For single phase devices, this object will always return phase1(1). For 3-phase devices, this object will return phase1 (1), phase2 (2), or phase3 (3) for outlets tied to a single phase. For outlets tied to two phases, this object will return phase1-2 (4) for phases 1 and 2, phase2-3 (5) for phases 2 and 3, and phase3-1 (6) for phases 3 and 1." ::= { rPDUOutletConfigEntry 3 } rPDUOutletConfigPowerOnTime OBJECT-TYPE SYNTAX INTEGER ACCESS read-write STATUS mandatory DESCRIPTION "The amount of time (in seconds) the outlet will delay powering on at coldstart or when a command that requires a turn-on delay is issued. Allowed values are: -1 - never power on. 0 - power on immediately. 1 to 300 - power on up to 300 seconds (5 minutes) after being commanded." ::= { rPDUOutletConfigEntry 4 } rPDUOutletConfigPowerOffTime OBJECT-TYPE SYNTAX INTEGER ACCESS read-write STATUS mandatory DESCRIPTION "The amount of time (in seconds) the outlet will delay powering off when a command that requires a turn-off delay is issued. Allowed values are: -1 - never power off. 0 - power off immediately. 1 to 300 - power off up to 300 seconds (5 minutes) after being commanded." ::= { rPDUOutletConfigEntry 5 } rPDUOutletConfigRebootDuration OBJECT-TYPE SYNTAX INTEGER ACCESS read-write STATUS mandatory DESCRIPTION "During a reboot sequence, power is turned off and then back on. This OID defines the amount of time to wait, in seconds, after turning the power off, at the start of the sequence, before turning power back on, at the end of the reboot sequence. Allowed range is any value between 5 and 60 seconds (1 minute)." ::= { rPDUOutletConfigEntry 6 } rPDUOutletConfigOutletBank OBJECT-TYPE SYNTAX INTEGER ACCESS read-only STATUS mandatory DESCRIPTION "The bank associated with this outlet." ::= { rPDUOutletConfigEntry 7 } -- the rPDUOutletStatus group rPDUOutletStatusTable OBJECT-TYPE SYNTAX SEQUENCE OF RPDUOutletStatusEntry ACCESS not-accessible STATUS mandatory DESCRIPTION "Allows for getting of status of individual outlets. The number of entries is contained in the rPDUOutletDevNumCntrlOutlets OID." ::= { rPDUOutletStatus 1 } rPDUOutletStatusEntry OBJECT-TYPE SYNTAX RPDUOutletStatusEntry ACCESS not-accessible STATUS mandatory DESCRIPTION "The outlet to gather status from." INDEX { rPDUOutletStatusIndex} ::= { rPDUOutletStatusTable 1 } RPDUOutletStatusEntry ::= SEQUENCE { rPDUOutletStatusIndex INTEGER, rPDUOutletStatusOutletName DisplayString, rPDUOutletStatusOutletPhase INTEGER, rPDUOutletStatusOutletState INTEGER, rPDUOutletStatusCommandPending INTEGER, rPDUOutletStatusOutletBank INTEGER } rPDUOutletStatusIndex OBJECT-TYPE SYNTAX INTEGER ACCESS read-only STATUS mandatory DESCRIPTION "The index to the outlet entry." ::= { rPDUOutletStatusEntry 1 } rPDUOutletStatusOutletName OBJECT-TYPE SYNTAX DisplayString ACCESS read-only STATUS mandatory DESCRIPTION "The name of the outlet. Maximum size is dependent on device. An error will be returned if the set request exceeds the max size. This OID is provided for informational purposes only." ::= { rPDUOutletStatusEntry 2 } rPDUOutletStatusOutletPhase OBJECT-TYPE SYNTAX INTEGER { phase1 (1), phase2 (2), phase3 (3), phase1-2 (4), phase2-3 (5), phase3-1 (6) } ACCESS read-only STATUS mandatory DESCRIPTION "The phase/s associated with this outlet. For single phase devices, this object will always return phase1(1). For 3-phase devices, this object will return phase1 (1), phase2 (2), or phase3 (3) for outlets tied to a single phase. For outlets tied to two phases, this object will return phase1-2 (4) for phases 1 and 2, phase2-3 (5) for phases 2 and 3, and phase3-1 (6) for phases 3 and 1." ::= { rPDUOutletStatusEntry 3 } rPDUOutletStatusOutletState OBJECT-TYPE SYNTAX INTEGER { outletStatusOn (1), outletStatusOff (2) } ACCESS read-only STATUS mandatory DESCRIPTION "Getting this variable will return the outlet state. If the outlet is on, the outletStatusOn (1) value will be returned. If the outlet is off, the outletStatusOff (2) value will be returned. " ::= { rPDUOutletStatusEntry 4 } rPDUOutletStatusCommandPending OBJECT-TYPE SYNTAX INTEGER { outletStatusCommandPending (1), outletStatusNoCommandPending (2) } ACCESS read-only STATUS mandatory DESCRIPTION "Getting this variable will return the command pending state of the outlet. If a command is pending on the outlet, the outletStatusCommandPending (1) value will be returned. If there is not a command pending on the outlet, the outletStatusNoCommandPending (2) will be returned." ::= { rPDUOutletStatusEntry 5 } rPDUOutletStatusOutletBank OBJECT-TYPE SYNTAX INTEGER ACCESS read-only STATUS mandatory DESCRIPTION "The bank associated with this outlet." ::= { rPDUOutletStatusEntry 6 } -- the rPDUOutletBank group rPDUOutletBankTable OBJECT-TYPE SYNTAX SEQUENCE OF OutletBankEntry ACCESS not-accessible STATUS mandatory DESCRIPTION "Allows for management of outlets on a per bank basis." ::= { rPDUOutletBank 1 } rPDUOutletBankEntry OBJECT-TYPE SYNTAX OutletBankEntry ACCESS not-accessible STATUS mandatory DESCRIPTION "The bank to manage." INDEX { rPDUOutletBankIndex} ::= { rPDUOutletBankTable 1 } OutletBankEntry ::= SEQUENCE { rPDUOutletBankIndex INTEGER, rPDUOutletBankOverloadRestriction INTEGER } rPDUOutletBankIndex OBJECT-TYPE SYNTAX INTEGER ACCESS read-only STATUS mandatory DESCRIPTION "The index to the Switched Rack PDU bank entry." ::= { rPDUOutletBankEntry 1 } rPDUOutletBankOverloadRestriction OBJECT-TYPE SYNTAX INTEGER { alwaysAllowTurnON (1), restrictOnNearOverload (2), restrictOnOverload (3) } ACCESS read-write STATUS mandatory DESCRIPTION "This OID controls the behavior of a Switched Rack PDU bank when an overload condition is possible and additional outlets are requested to be turned on. Setting this OID to alwaysAllowTurnON (1) will always allow the outlets on the corresponding bank to turn on. Setting this OID to restrictOnNearOverload (2) will not allow outlets on the corresponding bank to turn on if the rPDULoadConfigNearOverloadThreshold OID is exceeded. Setting this OID to restrictOnOverload (3) will not allow outlets on the corresponding bank to turn on if the rPDULoadConfigOverloadThreshold OID is exceeded." ::= { rPDUOutletBankEntry 2 } -- the rPDUPowerSupplyDevice group rPDUPowerSupply1Status OBJECT-TYPE SYNTAX INTEGER { powerSupply1Ok (1), powerSupply1Failed (2) } ACCESS read-only STATUS mandatory DESCRIPTION "Getting this OID will return powerSupply1Ok(1) if power supply 1 is functioning normally. If not functioning normally, this OID will return powerSupply1Failed(2)." ::= { rPDUPowerSupplyDevice 1 } rPDUPowerSupply2Status OBJECT-TYPE SYNTAX INTEGER { powerSupply2Ok (1), powerSupply2Failed (2) } ACCESS read-only STATUS mandatory DESCRIPTION "Getting this OID will return powerSupply2Ok(1) if power supply 2 is functioning normally. If not functioning normally, this OID will return powerSupply2Failed(2)." ::= { rPDUPowerSupplyDevice 2 } -- the dm3IdentSystem group dm3IdentSysDescriptionTableSize OBJECT-TYPE SYNTAX INTEGER ACCESS read-only STATUS mandatory DESCRIPTION "The number of DC description records." ::= { dm3IdentSystem 1 } dm3IdentSysDescriptionTable OBJECT-TYPE SYNTAX SEQUENCE OF IdentSysDescriptionEntry ACCESS not-accessible STATUS mandatory DESCRIPTION "Allows for accessing description records of the powerplant. The number of entries is contained in the dm3IdentSysDescriptionTableSize OID." ::= { dm3IdentSystem 2 } dm3IdentSysDescriptionEntry OBJECT-TYPE SYNTAX IdentSysDescriptionEntry ACCESS not-accessible STATUS mandatory DESCRIPTION "The powerplant description record to reference." INDEX { dm3IdentSysDescriptionIndex } ::= { dm3IdentSysDescriptionTable 1 } IdentSysDescriptionEntry ::= SEQUENCE { dm3IdentSysDescriptionIndex INTEGER, dm3IdentSysDescriptionText DisplayString } dm3IdentSysDescriptionIndex OBJECT-TYPE SYNTAX INTEGER ACCESS read-only STATUS mandatory DESCRIPTION "The index to the DC powerplant description record." ::= { dm3IdentSysDescriptionEntry 1 } dm3IdentSysDescriptionText OBJECT-TYPE SYNTAX DisplayString ACCESS read-only STATUS mandatory DESCRIPTION "A 16 character text field describing the DC power plant device. This field can be configured from the dm3ConfigSysDescriptionText OID." ::= { dm3IdentSysDescriptionEntry 2 } dm3IdentSysModel OBJECT-TYPE SYNTAX INTEGER ACCESS read-only STATUS mandatory DESCRIPTION "Model type of the DC power plant." ::= { dm3IdentSystem 3 } dm3IdentSysCntrlRev OBJECT-TYPE SYNTAX INTEGER ACCESS read-only STATUS mandatory DESCRIPTION "Integer representation of the hardware revision of the Master Controller board." ::= { dm3IdentSystem 4 } dm3IdentSysFWVersion OBJECT-TYPE SYNTAX INTEGER ACCESS read-only STATUS mandatory DESCRIPTION "Integer representation of the power plant Master Controller firmware revision." ::= { dm3IdentSystem 5 } -- the dm3ConfigSystem group dm3ConfigSysDescriptionTableSize OBJECT-TYPE SYNTAX INTEGER ACCESS read-only STATUS mandatory DESCRIPTION "The number of DC description records." ::= { dm3ConfigSystem 1 } dm3ConfigSysDescriptionTable OBJECT-TYPE SYNTAX SEQUENCE OF ConfigSysDescriptionEntry ACCESS not-accessible STATUS mandatory DESCRIPTION "Allows for accessing description records of the powerplant. The number of entries is contained in the dm3ConfigSysDescriptionTableSize OID." ::= { dm3ConfigSystem 2 } dm3ConfigSysDescriptionEntry OBJECT-TYPE SYNTAX ConfigSysDescriptionEntry ACCESS not-accessible STATUS mandatory DESCRIPTION "The powerplant description record to reference." INDEX { dm3ConfigSysDescriptionIndex } ::= { dm3ConfigSysDescriptionTable 1 } ConfigSysDescriptionEntry ::= SEQUENCE { dm3ConfigSysDescriptionIndex INTEGER, dm3ConfigSysDescriptionText DisplayString } dm3ConfigSysDescriptionIndex OBJECT-TYPE SYNTAX INTEGER ACCESS read-only STATUS mandatory DESCRIPTION "The index to the DC powerplant description record." ::= { dm3ConfigSysDescriptionEntry 1 } dm3ConfigSysDescriptionText OBJECT-TYPE SYNTAX DisplayString ACCESS read-write STATUS mandatory DESCRIPTION "16 character text field describing the DC power plant device." ::= { dm3ConfigSysDescriptionEntry 2 } dm3ConfigSysHighTempThresh OBJECT-TYPE SYNTAX INTEGER ACCESS read-write STATUS mandatory DESCRIPTION "Ambient high temperature threshold. Temperature sensor located on Master Controller board. Values are represented in thousandths of a degree. Units are displayed in the scale shown in the 'dm3StatusSysTempUnits' OID (Celsius or Fahrenheit). Attempts to set the value above or below the acceptable range of the powerplant will cause the value to be set at the high or low point of the range respectively." ::= { dm3ConfigSystem 3 } dm3ConfigSysHighTempAlarm OBJECT-TYPE SYNTAX INTEGER { alarmIgnore (1), alarmRelay1 (2), alarmRelay2 (3), alarmRelay3 (4), alarmRelay4 (5), alarmRelay5 (6), alarmRelay6 (7), alarmMinor (8), alarmMajor (9) } ACCESS read-write STATUS mandatory DESCRIPTION "For the System High Temperature Alarm; Setting this OID to alarmIgnore (1) results in the alarm condition being ignored. Setting this OID to alarmRelay1 (2) causes relay 1 to be activated for an alarm condition. Setting this OID to alarmRelay2 (3) causes relay 2 to be activated for an alarm condition. Setting this OID to alarmRelay3 (4) causes relay 3 to be activated for an alarm condition. Setting this OID to alarmRelay4 (5) causes relay 4 to be activated for an alarm condition. Setting this OID to alarmRelay5 (6) causes relay 5 to be activated for an alarm condition. Setting this OID to alarmRelay6 (7) causes relay 6 to be activated for an alarm condition. Setting this OID to alarmMinor (8) causes the Minor relay to be activated for an alarm condition. Setting this OID to alarmMajor (9) causes the Major relay to be activated for an alarm condition." ::= { dm3ConfigSystem 4 } dm3ConfigSysLowTempThresh OBJECT-TYPE SYNTAX INTEGER ACCESS read-write STATUS mandatory DESCRIPTION "Ambient low temperature threshold. Temperature sensor located on Master Controller board. Values are represented in thousandths of a degree. Units are displayed in the scale shown in the 'dm3StatusSysTempUnits' OID (Celsius or Fahrenheit). Attempts to set the value above or below the acceptable range of the powerplant will cause the value to be set at the high or low point of the range respectively." ::= { dm3ConfigSystem 5 } dm3ConfigSysLowTempAlarm OBJECT-TYPE SYNTAX INTEGER { alarmIgnore (1), alarmRelay1 (2), alarmRelay2 (3), alarmRelay3 (4), alarmRelay4 (5), alarmRelay5 (6), alarmRelay6 (7), alarmMinor (8), alarmMajor (9) } ACCESS read-write STATUS mandatory DESCRIPTION "For the System Low Temperature Alarm; Setting this OID to alarmIgnore (1) results in the alarm condition being ignored. Setting this OID to alarmRelay1 (2) causes relay 1 to be activated for an alarm condition. Setting this OID to alarmRelay2 (3) causes relay 2 to be activated for an alarm condition. Setting this OID to alarmRelay3 (4) causes relay 3 to be activated for an alarm condition. Setting this OID to alarmRelay4 (5) causes relay 4 to be activated for an alarm condition. Setting this OID to alarmRelay5 (6) causes relay 5 to be activated for an alarm condition. Setting this OID to alarmRelay6 (7) causes relay 6 to be activated for an alarm condition. Setting this OID to alarmMinor (8) causes the Minor relay to be activated for an alarm condition. Setting this OID to alarmMajor (9) causes the Major relay to be activated for an alarm condition." ::= { dm3ConfigSystem 6 } dm3ConfigSysHardwareTempAlarm OBJECT-TYPE SYNTAX INTEGER { alarmIgnore (1), alarmRelay1 (2), alarmRelay2 (3), alarmRelay3 (4), alarmRelay4 (5), alarmRelay5 (6), alarmRelay6 (7), alarmMinor (8), alarmMajor (9) } ACCESS read-write STATUS mandatory DESCRIPTION "For the System Hardware Temperature Alarm; Setting this OID to alarmIgnore (1) results in the alarm condition being ignored. Setting this OID to alarmRelay1 (2) causes relay 1 to be activated for an alarm condition. Setting this OID to alarmRelay2 (3) causes relay 2 to be activated for an alarm condition. Setting this OID to alarmRelay3 (4) causes relay 3 to be activated for an alarm condition. Setting this OID to alarmRelay4 (5) causes relay 4 to be activated for an alarm condition. Setting this OID to alarmRelay5 (6) causes relay 5 to be activated for an alarm condition. Setting this OID to alarmRelay6 (7) causes relay 6 to be activated for an alarm condition. Setting this OID to alarmMinor (8) causes the Minor relay to be activated for an alarm condition. Setting this OID to alarmMajor (9) causes the Major relay to be activated for an alarm condition." ::= { dm3ConfigSystem 7 } dm3ConfigSysRemoteAccess OBJECT-TYPE SYNTAX INTEGER { accessEnabled (1), accessDisabled (2) } ACCESS read-write STATUS mandatory DESCRIPTION " This OID is used to disable remote write access to the power plant. Setting this OID to accessEnabled (1) will have no affect. Setting this OID to accessDisabled (2) will disable the ability to remotely configure the DC powerplant. Once remote access is disabled, it can only be restored from the front panel of the DC power plant." ::= { dm3ConfigSystem 8 } -- the dm3ConfigLVD group dm3ConfigLVDTableSize OBJECT-TYPE SYNTAX INTEGER ACCESS read-only STATUS mandatory DESCRIPTION "The number of DC powerplant LVDs controllable by this IP address." ::= { dm3ConfigLVD 1 } dm3ConfigLVDTable OBJECT-TYPE SYNTAX SEQUENCE OF ConfigLVDEntry ACCESS not-accessible STATUS mandatory DESCRIPTION "Allows for accessing settings of the LVDs. The number of entries is contained in the dm3ConfigLVDTableSize OID." ::= { dm3ConfigLVD 2 } dm3ConfigLVDEntry OBJECT-TYPE SYNTAX ConfigLVDEntry ACCESS not-accessible STATUS mandatory DESCRIPTION "The LVD to configure." INDEX { dm3ConfigLVDIndex } ::= { dm3ConfigLVDTable 1 } ConfigLVDEntry ::= SEQUENCE { dm3ConfigLVDIndex INTEGER, dm3ConfigLVDName DisplayString, dm3ConfigLVDEnable INTEGER, dm3ConfigLVDTripThresh INTEGER, dm3ConfigLVDResetThresh INTEGER, dm3ConfigLVDOpenAlarm INTEGER, dm3ConfigLVDHWAlarm INTEGER } dm3ConfigLVDIndex OBJECT-TYPE SYNTAX INTEGER ACCESS read-only STATUS mandatory DESCRIPTION "The index to the DC powerplant LVD." ::= { dm3ConfigLVDEntry 1 } dm3ConfigLVDName OBJECT-TYPE SYNTAX DisplayString ACCESS read-write STATUS mandatory DESCRIPTION "The name of the LVD. The maximum value is 16 characters." ::= { dm3ConfigLVDEntry 2 } dm3ConfigLVDEnable OBJECT-TYPE SYNTAX INTEGER { enabledYes (1), enabledNo (2) } ACCESS read-write STATUS mandatory DESCRIPTION "This OID is used to control and indicate if the LVD is on or off. Setting this OID to enabledYes (1) will enable (turn on) the LVD. Setting this OID to enabledNo (2) will disable (turn off) the LVD." ::= { dm3ConfigLVDEntry 3 } dm3ConfigLVDTripThresh OBJECT-TYPE SYNTAX INTEGER ACCESS read-write STATUS mandatory DESCRIPTION "LVD Trip threshold. If voltage exceeds threshold, the LVD will trip. Values are represented in thousandths of Volts (mV). Attempts to set the value above or below the acceptable range of the powerplant will cause the value to be set at the high or low point of the range respectively." ::= { dm3ConfigLVDEntry 4 } dm3ConfigLVDResetThresh OBJECT-TYPE SYNTAX INTEGER ACCESS read-write STATUS mandatory DESCRIPTION "LVD Reset threshold. If voltage exceeds threshold, the LVD will reset. Values are represented in thousandths of Volts (mV). Attempts to set the value above or below the acceptable range of the powerplant will cause the value to be set at the high or low point of the range respectively." ::= { dm3ConfigLVDEntry 5 } dm3ConfigLVDOpenAlarm OBJECT-TYPE SYNTAX INTEGER { alarmIgnore (1), alarmRelay1 (2), alarmRelay2 (3), alarmRelay3 (4), alarmRelay4 (5), alarmRelay5 (6), alarmRelay6 (7), alarmMinor (8), alarmMajor (9) } ACCESS read-write STATUS mandatory DESCRIPTION "For the LVD Open Alarm; Setting this OID to alarmIgnore (1) results in the alarm condition being ignored. Setting this OID to alarmRelay1 (2) causes relay 1 to be activated for an alarm condition. Setting this OID to alarmRelay2 (3) causes relay 2 to be activated for an alarm condition. Setting this OID to alarmRelay3 (4) causes relay 3 to be activated for an alarm condition. Setting this OID to alarmRelay4 (5) causes relay 4 to be activated for an alarm condition. Setting this OID to alarmRelay5 (6) causes relay 5 to be activated for an alarm condition. Setting this OID to alarmRelay6 (7) causes relay 6 to be activated for an alarm condition. Setting this OID to alarmMinor (8) causes the Minor relay to be activated for an alarm condition. Setting this OID to alarmMajor (9) causes the Major relay to be activated for an alarm condition." ::= { dm3ConfigLVDEntry 6 } dm3ConfigLVDHWAlarm OBJECT-TYPE SYNTAX INTEGER { alarmIgnore (1), alarmRelay1 (2), alarmRelay2 (3), alarmRelay3 (4), alarmRelay4 (5), alarmRelay5 (6), alarmRelay6 (7), alarmMinor (8), alarmMajor (9) } ACCESS read-write STATUS mandatory DESCRIPTION "For the LVD Hardware Alarm; Setting this OID to alarmIgnore (1) results in the alarm condition being ignored. Setting this OID to alarmRelay1 (2) causes relay 1 to be activated for an alarm condition. Setting this OID to alarmRelay2 (3) causes relay 2 to be activated for an alarm condition. Setting this OID to alarmRelay3 (4) causes relay 3 to be activated for an alarm condition. Setting this OID to alarmRelay4 (5) causes relay 4 to be activated for an alarm condition. Setting this OID to alarmRelay5 (6) causes relay 5 to be activated for an alarm condition. Setting this OID to alarmRelay6 (7) causes relay 6 to be activated for an alarm condition. Setting this OID to alarmMinor (8) causes the Minor relay to be activated for an alarm condition. Setting this OID to alarmMajor (9) causes the Major relay to be activated for an alarm condition." ::= { dm3ConfigLVDEntry 7 } -- the dm3ConfigBattery group dm3ConfigBattFloatVolt OBJECT-TYPE SYNTAX INTEGER ACCESS read-write STATUS mandatory DESCRIPTION "Battery Float Voltage. This setting controls the power plant voltage. Values are represented in thousandths of Volts (mV). Attempts to set the value above or below the acceptable range of the powerplant will cause the value to be set at the high or low point of the range respectively." ::= { dm3ConfigBattery 1 } dm3ConfigBattMaxRecharge OBJECT-TYPE SYNTAX INTEGER ACCESS read-write STATUS mandatory DESCRIPTION "Battery Maximum Recharge Rate. This setting controls the battery max recharge rate. The value is based on C/20 for 240 AHr battery string. Values are represented in thousandths of Amps (mA). Attempts to set the value above or below the acceptable range of the powerplant will cause the value to be set at the high or low point of the range respectively." ::= { dm3ConfigBattery 2 } dm3ConfigBattDischargeThresh OBJECT-TYPE SYNTAX INTEGER ACCESS read-write STATUS mandatory DESCRIPTION "Battery discharge threshold. If battery output current exceeds threshold a battery discharge alarm will occur. Values are represented in thousandths of Amps (mA). Attempts to set the value above or below the acceptable range of the powerplant will cause the value to be set at the high or low point of the range respectively." ::= { dm3ConfigBattery 3 } dm3ConfigBattDischargeAlarm OBJECT-TYPE SYNTAX INTEGER { alarmIgnore (1), alarmRelay1 (2), alarmRelay2 (3), alarmRelay3 (4), alarmRelay4 (5), alarmRelay5 (6), alarmRelay6 (7), alarmMinor (8), alarmMajor (9) } ACCESS read-write STATUS mandatory DESCRIPTION "For the Battery Discharge Alarm; Setting this OID to alarmIgnore (1) results in the alarm condition being ignored. Setting this OID to alarmRelay1 (2) causes relay 1 to be activated for an alarm condition. Setting this OID to alarmRelay2 (3) causes relay 2 to be activated for an alarm condition. Setting this OID to alarmRelay3 (4) causes relay 3 to be activated for an alarm condition. Setting this OID to alarmRelay4 (5) causes relay 4 to be activated for an alarm condition. Setting this OID to alarmRelay5 (6) causes relay 5 to be activated for an alarm condition. Setting this OID to alarmRelay6 (7) causes relay 6 to be activated for an alarm condition. Setting this OID to alarmMinor (8) causes the Minor relay to be activated for an alarm condition. Setting this OID to alarmMajor (9) causes the Major relay to be activated for an alarm condition." ::= { dm3ConfigBattery 4 } dm3ConfigBattHighVoltThresh OBJECT-TYPE SYNTAX INTEGER ACCESS read-write STATUS mandatory DESCRIPTION "Battery high voltage threshold. If system battery voltage exceeds threshold a battery high voltage alarm will occur. Values are represented in thousandths of Volts (mV). Attempts to set the value above or below the acceptable range of the powerplant will cause the value to be set at the high or low point of the range respectively." ::= { dm3ConfigBattery 5 } dm3ConfigBattHighVoltAlarm OBJECT-TYPE SYNTAX INTEGER { alarmIgnore (1), alarmRelay1 (2), alarmRelay2 (3), alarmRelay3 (4), alarmRelay4 (5), alarmRelay5 (6), alarmRelay6 (7), alarmMinor (8), alarmMajor (9) } ACCESS read-write STATUS mandatory DESCRIPTION "For the Battery High Voltage Alarm; Setting this OID to alarmIgnore (1) results in the alarm condition being ignored. Setting this OID to alarmRelay1 (2) causes relay 1 to be activated for an alarm condition. Setting this OID to alarmRelay2 (3) causes relay 2 to be activated for an alarm condition. Setting this OID to alarmRelay3 (4) causes relay 3 to be activated for an alarm condition. Setting this OID to alarmRelay4 (5) causes relay 4 to be activated for an alarm condition. Setting this OID to alarmRelay5 (6) causes relay 5 to be activated for an alarm condition. Setting this OID to alarmRelay6 (7) causes relay 6 to be activated for an alarm condition. Setting this OID to alarmMinor (8) causes the Minor relay to be activated for an alarm condition. Setting this OID to alarmMajor (9) causes the Major relay to be activated for an alarm condition." ::= { dm3ConfigBattery 6 } dm3ConfigBattLowVoltThresh OBJECT-TYPE SYNTAX INTEGER ACCESS read-write STATUS mandatory DESCRIPTION "Battery low voltage threshold. If system battery voltage is under threshold a battery low voltage alarm will occur. Values are represented in thousandths of Volts (mV). Attempts to set the value above or below the acceptable range of the powerplant will cause the value to be set at the high or low point of the range respectively." ::= { dm3ConfigBattery 7 } dm3ConfigBattLowVoltAlarm OBJECT-TYPE SYNTAX INTEGER { alarmIgnore (1), alarmRelay1 (2), alarmRelay2 (3), alarmRelay3 (4), alarmRelay4 (5), alarmRelay5 (6), alarmRelay6 (7), alarmMinor (8), alarmMajor (9) } ACCESS read-write STATUS mandatory DESCRIPTION "For the Battery Low Voltage Alarm; Setting this OID to alarmIgnore (1) results in the alarm condition being ignored. Setting this OID to alarmRelay1 (2) causes relay 1 to be activated for an alarm condition. Setting this OID to alarmRelay2 (3) causes relay 2 to be activated for an alarm condition. Setting this OID to alarmRelay3 (4) causes relay 3 to be activated for an alarm condition. Setting this OID to alarmRelay4 (5) causes relay 4 to be activated for an alarm condition. Setting this OID to alarmRelay5 (6) causes relay 5 to be activated for an alarm condition. Setting this OID to alarmRelay6 (7) causes relay 6 to be activated for an alarm condition. Setting this OID to alarmMinor (8) causes the Minor relay to be activated for an alarm condition. Setting this OID to alarmMajor (9) causes the Major relay to be activated for an alarm condition." ::= { dm3ConfigBattery 8 } dm3ConfigBattHighTempThresh OBJECT-TYPE SYNTAX INTEGER ACCESS read-write STATUS mandatory DESCRIPTION "Battery high temperature threshold. If system battery temperature exceeds threshold a battery high temperature alarm will occur. Values are represented in thousandths of a degree. Units are displayed in the scale shown in the 'dm3StatusSysTempUnits' OID (Celsius or Fahrenheit). Attempts to set the value above or below the acceptable range of the powerplant will cause the value to be set at the high or low point of the range respectively." ::= { dm3ConfigBattery 9 } dm3ConfigBattHighTempAlarm OBJECT-TYPE SYNTAX INTEGER { alarmIgnore (1), alarmRelay1 (2), alarmRelay2 (3), alarmRelay3 (4), alarmRelay4 (5), alarmRelay5 (6), alarmRelay6 (7), alarmMinor (8), alarmMajor (9) } ACCESS read-write STATUS mandatory DESCRIPTION "For the Battery High Temperature Alarm; Setting this OID to alarmIgnore (1) results in the alarm condition being ignored. Setting this OID to alarmRelay1 (2) causes relay 1 to be activated for an alarm condition. Setting this OID to alarmRelay2 (3) causes relay 2 to be activated for an alarm condition. Setting this OID to alarmRelay3 (4) causes relay 3 to be activated for an alarm condition. Setting this OID to alarmRelay4 (5) causes relay 4 to be activated for an alarm condition. Setting this OID to alarmRelay5 (6) causes relay 5 to be activated for an alarm condition. Setting this OID to alarmRelay6 (7) causes relay 6 to be activated for an alarm condition. Setting this OID to alarmMinor (8) causes the Minor relay to be activated for an alarm condition. Setting this OID to alarmMajor (9) causes the Major relay to be activated for an alarm condition." ::= { dm3ConfigBattery 10 } dm3ConfigBattLowTempThresh OBJECT-TYPE SYNTAX INTEGER ACCESS read-write STATUS mandatory DESCRIPTION "Battery low temperature threshold. If system battery temperature is under threshold a battery low temperature alarm will occur. Values are represented in thousandths of a degree. Units are displayed in the scale shown in the 'dm3StatusSysTempUnits' OID (Celsius or Fahrenheit). Attempts to set the value above or below the acceptable range of the powerplant will cause the value to be set at the high or low point of the range respectively." ::= { dm3ConfigBattery 11 } dm3ConfigBattLowTempAlarm OBJECT-TYPE SYNTAX INTEGER { alarmIgnore (1), alarmRelay1 (2), alarmRelay2 (3), alarmRelay3 (4), alarmRelay4 (5), alarmRelay5 (6), alarmRelay6 (7), alarmMinor (8), alarmMajor (9) } ACCESS read-write STATUS mandatory DESCRIPTION "For the Battery Low Temperature Alarm; Setting this OID to alarmIgnore (1) results in the alarm condition being ignored. Setting this OID to alarmRelay1 (2) causes relay 1 to be activated for an alarm condition. Setting this OID to alarmRelay2 (3) causes relay 2 to be activated for an alarm condition. Setting this OID to alarmRelay3 (4) causes relay 3 to be activated for an alarm condition. Setting this OID to alarmRelay4 (5) causes relay 4 to be activated for an alarm condition. Setting this OID to alarmRelay5 (6) causes relay 5 to be activated for an alarm condition. Setting this OID to alarmRelay6 (7) causes relay 6 to be activated for an alarm condition. Setting this OID to alarmMinor (8) causes the Minor relay to be activated for an alarm condition. Setting this OID to alarmMajor (9) causes the Major relay to be activated for an alarm condition." ::= { dm3ConfigBattery 12 } dm3ConfigBattAmpHour OBJECT-TYPE SYNTAX INTEGER ACCESS read-write STATUS mandatory DESCRIPTION "Battery Amp-Hour Size. Units are thousandths of Amp hours (mAHr). Attempts to set the value above or below the acceptable range of the powerplant will cause the value to be set at the high or low point of the range respectively." ::= { dm3ConfigBattery 13 } dm3ConfigCompMethod OBJECT-TYPE SYNTAX INTEGER { tempcompOn (1), tempcompOff (2) } ACCESS read-write STATUS mandatory DESCRIPTION "This OID is used to configure and get the state of the battery temperature compensation. Setting this OID to tempcompOn (1) will enable/turn on the battery temperature compensation. Setting this OID to tempcompOff (2) will disable/turn off the battery temperature compensation." ::= { dm3ConfigBattery 14 } dm3ConfigCompTempCoeff OBJECT-TYPE SYNTAX INTEGER ACCESS read-write STATUS mandatory DESCRIPTION "Compensation Temperature Coefficient. (uV/degC/cell). Units are presented in microvolts. Attempts to set the value above or below the acceptable range of the powerplant will cause the value to be set at the high or low point of the range respectively." ::= { dm3ConfigBattery 15 } dm3ConfigHighKneeTemp OBJECT-TYPE SYNTAX INTEGER ACCESS read-write STATUS mandatory DESCRIPTION "High Knee for temperature compensation: Compensation temperature coefficient becomes 0mV/degC/cell. Values are represented in thousandths of degrees Celcius. Attempts to set the value above or below the acceptable range of the powerplant will cause the value to be set at the high or low point of the range respectively." ::= { dm3ConfigBattery 16 } dm3ConfigLowKneeTemp OBJECT-TYPE SYNTAX INTEGER ACCESS read-write STATUS mandatory DESCRIPTION "Low Knee for temperature compensation: Compensation temperature coefficient becomes 0mV/degC/cell. Values are represented in thousandths of degrees Celcius. Attempts to set the value above or below the acceptable range of the powerplant will cause the value to be set at the high or low point of the range respectively." ::= { dm3ConfigBattery 17 } dm3ConfigBattHwCurrentAlarm OBJECT-TYPE SYNTAX INTEGER { alarmIgnore (1), alarmRelay1 (2), alarmRelay2 (3), alarmRelay3 (4), alarmRelay4 (5), alarmRelay5 (6), alarmRelay6 (7), alarmMinor (8), alarmMajor (9) } ACCESS read-write STATUS mandatory DESCRIPTION "For the Battery Current Hardware Alarm (indicating current is outside realistic limits, or a possible measurement fault; Setting this OID to alarmIgnore (1) results in the alarm condition being ignored. Setting this OID to alarmRelay1 (2) causes relay 1 to be activated for an alarm condition. Setting this OID to alarmRelay2 (3) causes relay 2 to be activated for an alarm condition. Setting this OID to alarmRelay3 (4) causes relay 3 to be activated for an alarm condition. Setting this OID to alarmRelay4 (5) causes relay 4 to be activated for an alarm condition. Setting this OID to alarmRelay5 (6) causes relay 5 to be activated for an alarm condition. Setting this OID to alarmRelay6 (7) causes relay 6 to be activated for an alarm condition. Setting this OID to alarmMinor (8) causes the Minor relay to be activated for an alarm condition. Setting this OID to alarmMajor (9) causes the Major relay to be activated for an alarm condition." ::= { dm3ConfigBattery 18 } dm3ConfigBattHwTempAlarm OBJECT-TYPE SYNTAX INTEGER { alarmIgnore (1), alarmRelay1 (2), alarmRelay2 (3), alarmRelay3 (4), alarmRelay4 (5), alarmRelay5 (6), alarmRelay6 (7), alarmMinor (8), alarmMajor (9) } ACCESS read-write STATUS mandatory DESCRIPTION "For the Battery Temperature Hardware Alarm (indicating temperature is outside realistic limits, or a possible measurement fault; Setting this OID to alarmIgnore (1) results in the alarm condition being ignored. Setting this OID to alarmRelay1 (2) causes relay 1 to be activated for an alarm condition. Setting this OID to alarmRelay2 (3) causes relay 2 to be activated for an alarm condition. Setting this OID to alarmRelay3 (4) causes relay 3 to be activated for an alarm condition. Setting this OID to alarmRelay4 (5) causes relay 4 to be activated for an alarm condition. Setting this OID to alarmRelay5 (6) causes relay 5 to be activated for an alarm condition. Setting this OID to alarmRelay6 (7) causes relay 6 to be activated for an alarm condition. Setting this OID to alarmMinor (8) causes the Minor relay to be activated for an alarm condition. Setting this OID to alarmMajor (9) causes the Major relay to be activated for an alarm condition." ::= { dm3ConfigBattery 19 } -- the dm3ConfigRectThresh group dm3ConfigRectHighVoltThresh OBJECT-TYPE SYNTAX INTEGER ACCESS read-write STATUS mandatory DESCRIPTION "Rectifier high voltage threshold. If rectifier voltage exceeds threshold a rectifier high voltage alarm will occur. Values are represented in thousandths of Volts (mV). Attempts to set the value above or below the acceptable range of the powerplant will cause the value to be set at the high or low point of the range respectively." ::= { dm3ConfigRectThresh 1 } dm3ConfigRectLowVoltThresh OBJECT-TYPE SYNTAX INTEGER ACCESS read-write STATUS mandatory DESCRIPTION "Rectifier low voltage threshold. If rectifier voltage is under threshold a rectifier low voltage alarm will occur. Values are represented in thousandths of Volts (mV). Attempts to set the value above or below the acceptable range of the powerplant will cause the value to be set at the high or low point of the range respectively." ::= { dm3ConfigRectThresh 2 } dm3ConfigRectFailSafe OBJECT-TYPE SYNTAX INTEGER ACCESS read-write STATUS mandatory DESCRIPTION "Rectifier Fail Safe point. This OID represents the value sent to rectifier controllers to use in the event of communications loss with the Master Controller or Master Controller board failure. Values are represented in thousandths of Volts (mV). Attempts to set the value above or below the acceptable range of the powerplant will cause the value to be set at the high or low point of the range respectively." ::= { dm3ConfigRectThresh 3 } dm3ConfigRectFailComm OBJECT-TYPE SYNTAX INTEGER ACCESS read-write STATUS mandatory DESCRIPTION "Rectifier Communication Fail timeout. This OID represents the time interval in which there is no communication between the rectifier and the master controller at which the rectifier will reset all its values to default. Values are represented in hundredths of Seconds. Attempts to set the value above or below the acceptable range of the powerplant will cause the value to be set at the high or low point of the range respectively." ::= { dm3ConfigRectThresh 4 } -- the dm3ConfigRectAlarms group dm3ConfigRectHighVoltAlarm OBJECT-TYPE SYNTAX INTEGER { alarmIgnore (1), alarmRelay1 (2), alarmRelay2 (3), alarmRelay3 (4), alarmRelay4 (5), alarmRelay5 (6), alarmRelay6 (7), alarmMinor (8), alarmMajor (9) } ACCESS read-write STATUS mandatory DESCRIPTION "For the Rectifier High Voltage Alarm; Setting this OID to alarmIgnore (1) results in the alarm condition being ignored. Setting this OID to alarmRelay1 (2) causes relay 1 to be activated for an alarm condition. Setting this OID to alarmRelay2 (3) causes relay 2 to be activated for an alarm condition. Setting this OID to alarmRelay3 (4) causes relay 3 to be activated for an alarm condition. Setting this OID to alarmRelay4 (5) causes relay 4 to be activated for an alarm condition. Setting this OID to alarmRelay5 (6) causes relay 5 to be activated for an alarm condition. Setting this OID to alarmRelay6 (7) causes relay 6 to be activated for an alarm condition. Setting this OID to alarmMinor (8) causes the Minor relay to be activated for an alarm condition. Setting this OID to alarmMajor (9) causes the Major relay to be activated for an alarm condition." ::= { dm3ConfigRectAlarms 1 } dm3ConfigRectLowVoltAlarm OBJECT-TYPE SYNTAX INTEGER { alarmIgnore (1), alarmRelay1 (2), alarmRelay2 (3), alarmRelay3 (4), alarmRelay4 (5), alarmRelay5 (6), alarmRelay6 (7), alarmMinor (8), alarmMajor (9) } ACCESS read-write STATUS mandatory DESCRIPTION "For the Rectifier Low Voltage Alarm; Setting this OID to alarmIgnore (1) results in the alarm condition being ignored. Setting this OID to alarmRelay1 (2) causes relay 1 to be activated for an alarm condition. Setting this OID to alarmRelay2 (3) causes relay 2 to be activated for an alarm condition. Setting this OID to alarmRelay3 (4) causes relay 3 to be activated for an alarm condition. Setting this OID to alarmRelay4 (5) causes relay 4 to be activated for an alarm condition. Setting this OID to alarmRelay5 (6) causes relay 5 to be activated for an alarm condition. Setting this OID to alarmRelay6 (7) causes relay 6 to be activated for an alarm condition. Setting this OID to alarmMinor (8) causes the Minor relay to be activated for an alarm condition. Setting this OID to alarmMajor (9) causes the Major relay to be activated for an alarm condition." ::= { dm3ConfigRectAlarms 2 } dm3ConfigRectConfigAlarm OBJECT-TYPE SYNTAX INTEGER { alarmIgnore (1), alarmRelay1 (2), alarmRelay2 (3), alarmRelay3 (4), alarmRelay4 (5), alarmRelay5 (6), alarmRelay6 (7), alarmMinor (8), alarmMajor (9) } ACCESS read-write STATUS mandatory DESCRIPTION "This alarm is activated when a new rectifier is detected; Setting this OID to alarmIgnore (1) results in the alarm condition being ignored. Setting this OID to alarmRelay1 (2) causes relay 1 to be activated for an alarm condition. Setting this OID to alarmRelay2 (3) causes relay 2 to be activated for an alarm condition. Setting this OID to alarmRelay3 (4) causes relay 3 to be activated for an alarm condition. Setting this OID to alarmRelay4 (5) causes relay 4 to be activated for an alarm condition. Setting this OID to alarmRelay5 (6) causes relay 5 to be activated for an alarm condition. Setting this OID to alarmRelay6 (7) causes relay 6 to be activated for an alarm condition. Setting this OID to alarmMinor (8) causes the Minor relay to be activated for an alarm condition. Setting this OID to alarmMajor (9) causes the Major relay to be activated for an alarm condition." ::= { dm3ConfigRectAlarms 3 } dm3ConfigRect1ofNAlarm OBJECT-TYPE SYNTAX INTEGER { alarmIgnore (1), alarmRelay1 (2), alarmRelay2 (3), alarmRelay3 (4), alarmRelay4 (5), alarmRelay5 (6), alarmRelay6 (7), alarmMinor (8), alarmMajor (9) } ACCESS read-write STATUS mandatory DESCRIPTION "This setting indicates the action if ONE rectifier of a N+1 system has failed; Setting this OID to alarmIgnore (1) results in the alarm condition being ignored. Setting this OID to alarmRelay1 (2) causes relay 1 to be activated for an alarm condition. Setting this OID to alarmRelay2 (3) causes relay 2 to be activated for an alarm condition. Setting this OID to alarmRelay3 (4) causes relay 3 to be activated for an alarm condition. Setting this OID to alarmRelay4 (5) causes relay 4 to be activated for an alarm condition. Setting this OID to alarmRelay5 (6) causes relay 5 to be activated for an alarm condition. Setting this OID to alarmRelay6 (7) causes relay 6 to be activated for an alarm condition. Setting this OID to alarmMinor (8) causes the Minor relay to be activated for an alarm condition. Setting this OID to alarmMajor (9) causes the Major relay to be activated for an alarm condition." ::= { dm3ConfigRectAlarms 4 } dm3ConfigRect2ofNAlarm OBJECT-TYPE SYNTAX INTEGER { alarmIgnore (1), alarmRelay1 (2), alarmRelay2 (3), alarmRelay3 (4), alarmRelay4 (5), alarmRelay5 (6), alarmRelay6 (7), alarmMinor (8), alarmMajor (9) } ACCESS read-write STATUS mandatory DESCRIPTION "This setting indicates the action if TWO OR MORE rectifiers of a N+1 system have failed; Setting this OID to alarmIgnore (1) results in the alarm condition being ignored. Setting this OID to alarmRelay1 (2) causes relay 1 to be activated for an alarm condition. Setting this OID to alarmRelay2 (3) causes relay 2 to be activated for an alarm condition. Setting this OID to alarmRelay3 (4) causes relay 3 to be activated for an alarm condition. Setting this OID to alarmRelay4 (5) causes relay 4 to be activated for an alarm condition. Setting this OID to alarmRelay5 (6) causes relay 5 to be activated for an alarm condition. Setting this OID to alarmRelay6 (7) causes relay 6 to be activated for an alarm condition. Setting this OID to alarmMinor (8) causes the Minor relay to be activated for an alarm condition. Setting this OID to alarmMajor (9) causes the Major relay to be activated for an alarm condition." ::= { dm3ConfigRectAlarms 5 } dm3ConfigRectDiagAlarm OBJECT-TYPE SYNTAX INTEGER { alarmIgnore (1), alarmRelay1 (2), alarmRelay2 (3), alarmRelay3 (4), alarmRelay4 (5), alarmRelay5 (6), alarmRelay6 (7), alarmMinor (8), alarmMajor (9), alarmNofN (10) } ACCESS read-write STATUS mandatory DESCRIPTION "For the Rectifier Controller Diagnostics Alarm; Setting this OID to alarmIgnore (1) results in the alarm condition being ignored. Setting this OID to alarmRelay1 (2) causes relay 1 to be activated for an alarm condition. Setting this OID to alarmRelay2 (3) causes relay 2 to be activated for an alarm condition. Setting this OID to alarmRelay3 (4) causes relay 3 to be activated for an alarm condition. Setting this OID to alarmRelay4 (5) causes relay 4 to be activated for an alarm condition. Setting this OID to alarmRelay5 (6) causes relay 5 to be activated for an alarm condition. Setting this OID to alarmRelay6 (7) causes relay 6 to be activated for an alarm condition. Setting this OID to alarmMinor (8) causes the Minor relay to be activated for an alarm condition. Setting this OID to alarmMajor (9) causes the Major relay to be activated for an alarm condition. Setting this OID to alarmNofN (10) causes the alarm specified in the dm3ConfigRect1ofNAlarm OID to be activated if ONE rectifier fails in an N+1 system. It causes the alarm specified in the dm3ConfigRect2ofNAlarm OID to be activated if TWO OR MORE rectifiers fail in an N+1 system." ::= { dm3ConfigRectAlarms 6 } dm3ConfigRectImbalanceAlarm OBJECT-TYPE SYNTAX INTEGER { alarmIgnore (1), alarmRelay1 (2), alarmRelay2 (3), alarmRelay3 (4), alarmRelay4 (5), alarmRelay5 (6), alarmRelay6 (7), alarmMinor (8), alarmMajor (9) } ACCESS read-write STATUS mandatory DESCRIPTION "For the Rectifier Imbalance Alarm; Setting this OID to alarmIgnore (1) results in the alarm condition being ignored. Setting this OID to alarmRelay1 (2) causes relay 1 to be activated for an alarm condition. Setting this OID to alarmRelay2 (3) causes relay 2 to be activated for an alarm condition. Setting this OID to alarmRelay3 (4) causes relay 3 to be activated for an alarm condition. Setting this OID to alarmRelay4 (5) causes relay 4 to be activated for an alarm condition. Setting this OID to alarmRelay5 (6) causes relay 5 to be activated for an alarm condition. Setting this OID to alarmRelay6 (7) causes relay 6 to be activated for an alarm condition. Setting this OID to alarmMinor (8) causes the Minor relay to be activated for an alarm condition. Setting this OID to alarmMajor (9) causes the Major relay to be activated for an alarm condition." ::= { dm3ConfigRectAlarms 7 } dm3ConfigRectCurrLimitAlarm OBJECT-TYPE SYNTAX INTEGER { alarmIgnore (1), alarmRelay1 (2), alarmRelay2 (3), alarmRelay3 (4), alarmRelay4 (5), alarmRelay5 (6), alarmRelay6 (7), alarmMinor (8), alarmMajor (9), alarmNofN (10) } ACCESS read-write STATUS mandatory DESCRIPTION "For the Rectifier Current Limit Alarm (indicating rectifier in the Current Limit state); Setting this OID to alarmIgnore (1) results in the alarm condition being ignored. Setting this OID to alarmRelay1 (2) causes relay 1 to be activated for an alarm condition. Setting this OID to alarmRelay2 (3) causes relay 2 to be activated for an alarm condition. Setting this OID to alarmRelay3 (4) causes relay 3 to be activated for an alarm condition. Setting this OID to alarmRelay4 (5) causes relay 4 to be activated for an alarm condition. Setting this OID to alarmRelay5 (6) causes relay 5 to be activated for an alarm condition. Setting this OID to alarmRelay6 (7) causes relay 6 to be activated for an alarm condition. Setting this OID to alarmMinor (8) causes the Minor relay to be activated for an alarm condition. Setting this OID to alarmMajor (9) causes the Major relay to be activated for an alarm condition. Setting this OID to alarmNofN (10) causes the alarm specified in the dm3ConfigRect1ofNAlarm OID to be activated if ONE rectifier fails in an N+1 system. It causes the alarm specified in the dm3ConfigRect2ofNAlarm OID to be activated if TWO OR MORE rectifiers fail in an N+1 system." ::= { dm3ConfigRectAlarms 8 } dm3ConfigRectStandbyAlarm OBJECT-TYPE SYNTAX INTEGER { alarmIgnore (1), alarmRelay1 (2), alarmRelay2 (3), alarmRelay3 (4), alarmRelay4 (5), alarmRelay5 (6), alarmRelay6 (7), alarmMinor (8), alarmMajor (9), alarmNofN (10) } ACCESS read-write STATUS mandatory DESCRIPTION "For the Rectifier Standby Alarm (indicating output DC has been turned off); Setting this OID to alarmIgnore (1) results in the alarm condition being ignored. Setting this OID to alarmRelay1 (2) causes relay 1 to be activated for an alarm condition. Setting this OID to alarmRelay2 (3) causes relay 2 to be activated for an alarm condition. Setting this OID to alarmRelay3 (4) causes relay 3 to be activated for an alarm condition. Setting this OID to alarmRelay4 (5) causes relay 4 to be activated for an alarm condition. Setting this OID to alarmRelay5 (6) causes relay 5 to be activated for an alarm condition. Setting this OID to alarmRelay6 (7) causes relay 6 to be activated for an alarm condition. Setting this OID to alarmMinor (8) causes the Minor relay to be activated for an alarm condition. Setting this OID to alarmMajor (9) causes the Major relay to be activated for an alarm condition. Setting this OID to alarmNofN (10) causes the alarm specified in the dm3ConfigRect1ofNAlarm OID to be activated if ONE rectifier fails in an N+1 system. It causes the alarm specified in the dm3ConfigRect2ofNAlarm OID to be activated if TWO OR MORE rectifiers fail in an N+1 system." ::= { dm3ConfigRectAlarms 9 } dm3ConfigRectFanFailAlarm OBJECT-TYPE SYNTAX INTEGER { alarmIgnore (1), alarmRelay1 (2), alarmRelay2 (3), alarmRelay3 (4), alarmRelay4 (5), alarmRelay5 (6), alarmRelay6 (7), alarmMinor (8), alarmMajor (9), alarmNofN (10) } ACCESS read-write STATUS mandatory DESCRIPTION "For the Rectifier Fan Fail Alarm; Setting this OID to alarmIgnore (1) results in the alarm condition being ignored. Setting this OID to alarmRelay1 (2) causes relay 1 to be activated for an alarm condition. Setting this OID to alarmRelay2 (3) causes relay 2 to be activated for an alarm condition. Setting this OID to alarmRelay3 (4) causes relay 3 to be activated for an alarm condition. Setting this OID to alarmRelay4 (5) causes relay 4 to be activated for an alarm condition. Setting this OID to alarmRelay5 (6) causes relay 5 to be activated for an alarm condition. Setting this OID to alarmRelay6 (7) causes relay 6 to be activated for an alarm condition. Setting this OID to alarmMinor (8) causes the Minor relay to be activated for an alarm condition. Setting this OID to alarmMajor (9) causes the Major relay to be activated for an alarm condition. Setting this OID to alarmNofN (10) causes the alarm specified in the dm3ConfigRect1ofNAlarm OID to be activated if ONE rectifier fails in an N+1 system. It causes the alarm specified in the dm3ConfigRect2ofNAlarm OID to be activated if TWO OR MORE rectifiers fail in an N+1 system." ::= { dm3ConfigRectAlarms 10 } dm3ConfigRectFailAlarm OBJECT-TYPE SYNTAX INTEGER { alarmIgnore (1), alarmRelay1 (2), alarmRelay2 (3), alarmRelay3 (4), alarmRelay4 (5), alarmRelay5 (6), alarmRelay6 (7), alarmMinor (8), alarmMajor (9), alarmNofN (10) } ACCESS read-write STATUS mandatory DESCRIPTION "For the Rectifier Fail Alarm; Setting this OID to alarmIgnore (1) results in the alarm condition being ignored. Setting this OID to alarmRelay1 (2) causes relay 1 to be activated for an alarm condition. Setting this OID to alarmRelay2 (3) causes relay 2 to be activated for an alarm condition. Setting this OID to alarmRelay3 (4) causes relay 3 to be activated for an alarm condition. Setting this OID to alarmRelay4 (5) causes relay 4 to be activated for an alarm condition. Setting this OID to alarmRelay5 (6) causes relay 5 to be activated for an alarm condition. Setting this OID to alarmRelay6 (7) causes relay 6 to be activated for an alarm condition. Setting this OID to alarmMinor (8) causes the Minor relay to be activated for an alarm condition. Setting this OID to alarmMajor (9) causes the Major relay to be activated for an alarm condition. Setting this OID to alarmNofN (10) causes the alarm specified in the dm3ConfigRect1ofNAlarm OID to be activated if ONE rectifier fails in an N+1 system. It causes the alarm specified in the dm3ConfigRect2ofNAlarm OID to be activated if TWO OR MORE rectifiers fail in an N+1 system." ::= { dm3ConfigRectAlarms 11 } dm3ConfigRectHwVoltAlarm OBJECT-TYPE SYNTAX INTEGER { alarmIgnore (1), alarmRelay1 (2), alarmRelay2 (3), alarmRelay3 (4), alarmRelay4 (5), alarmRelay5 (6), alarmRelay6 (7), alarmMinor (8), alarmMajor (9) } ACCESS read-write STATUS mandatory DESCRIPTION "For the Rectifier Hardware Voltage Alarm (indicating voltage outside realistic limits, or a possible measurement fault); Setting this OID to alarmIgnore (1) results in the alarm condition being ignored. Setting this OID to alarmRelay1 (2) causes relay 1 to be activated for an alarm condition. Setting this OID to alarmRelay2 (3) causes relay 2 to be activated for an alarm condition. Setting this OID to alarmRelay3 (4) causes relay 3 to be activated for an alarm condition. Setting this OID to alarmRelay4 (5) causes relay 4 to be activated for an alarm condition. Setting this OID to alarmRelay5 (6) causes relay 5 to be activated for an alarm condition. Setting this OID to alarmRelay6 (7) causes relay 6 to be activated for an alarm condition. Setting this OID to alarmMinor (8) causes the Minor relay to be activated for an alarm condition. Setting this OID to alarmMajor (9) causes the Major relay to be activated for an alarm condition." ::= { dm3ConfigRectAlarms 12 } -- the dm3ConfigConvThresh group dm3ConfigConvHighVoltThresh OBJECT-TYPE SYNTAX INTEGER ACCESS read-write STATUS mandatory DESCRIPTION "Converter high voltage threshold. If converter voltage exceeds threshold a converter high voltage alarm will occur. Values are represented in thousandths of Volts (mV). Attempts to set the value above or below the acceptable range of the powerplant will cause the value to be set at the high or low point of the range respectively." ::= { dm3ConfigConvThresh 1 } dm3ConfigConvLowVoltThresh OBJECT-TYPE SYNTAX INTEGER ACCESS read-write STATUS mandatory DESCRIPTION "Converter low voltage threshold. If converter voltage exceeds threshold a converter low voltage alarm will occur. Values are represented in thousandths of Volts (mV). Attempts to set the value above or below the acceptable range of the powerplant will cause the value to be set at the high or low point of the range respectively." ::= { dm3ConfigConvThresh 2 } dm3ConfigConvFailSafe OBJECT-TYPE SYNTAX INTEGER ACCESS read-write STATUS mandatory DESCRIPTION "Converter Fail Safe point. This OID represents the value sent to converter controllers to use in the event of communications loss with the Master Controller or Master Controller board failure. Values are represented in thousandths of Volts (mV). Attempts to set the value above or below the acceptable range of the powerplant will cause the value to be set at the high or low point of the range respectively." ::= { dm3ConfigConvThresh 3 } dm3ConfigConvSetPoint OBJECT-TYPE SYNTAX INTEGER ACCESS read-write STATUS mandatory DESCRIPTION "Converter Set point. This OID represents the initial set point used in the voltage control loop. Units are thousandths of Volts (mV). Attempts to set the value above or below the acceptable range of the powerplant will cause the value to be set at the high or low point of the range respectively." ::= { dm3ConfigConvThresh 4 } dm3ConfigConvFailMax OBJECT-TYPE SYNTAX INTEGER ACCESS read-write STATUS mandatory DESCRIPTION "Converter Fail Maximum limit. This OID represents the value sent to the converter controllers to define the maximum set point allowed. Units are thousandths of Volts (mV). Attempts to set the value above or below the acceptable range of the powerplant will cause the value to be set at the high or low point of the range respectively." ::= { dm3ConfigConvThresh 5 } dm3ConfigConvFailMin OBJECT-TYPE SYNTAX INTEGER ACCESS read-write STATUS mandatory DESCRIPTION "Converter Fail Minimum limit. This OID represents the value sent to the converter controllers to define the minimum set point allowed. Units are thousandths of Volts (mV). Attempts to set the value above or below the acceptable range of the powerplant will cause the value to be set at the high or low point of the range respectively." ::= { dm3ConfigConvThresh 6 } dm3ConfigConvFailComm OBJECT-TYPE SYNTAX INTEGER ACCESS read-write STATUS mandatory DESCRIPTION "Converter Communication Fail timeout. This OID represents the time interval in which there is no communication between the converter and the master controller at which the converter will reset all its values to default. Values are represented in hundredths of Seconds. Attempts to set the value above or below the acceptable range of the powerplant will cause the value to be set at the high or low point of the range respectively." ::= { dm3ConfigConvThresh 7 } -- the dm3ConfigConvAlarms group dm3ConfigConvHighVoltAlarm OBJECT-TYPE SYNTAX INTEGER { alarmIgnore (1), alarmRelay1 (2), alarmRelay2 (3), alarmRelay3 (4), alarmRelay4 (5), alarmRelay5 (6), alarmRelay6 (7), alarmMinor (8), alarmMajor (9) } ACCESS read-write STATUS mandatory DESCRIPTION "For the Converter High Voltage Alarm; Setting this OID to alarmIgnore (1) results in the alarm condition being ignored. Setting this OID to alarmRelay1 (2) causes relay 1 to be activated for an alarm condition. Setting this OID to alarmRelay2 (3) causes relay 2 to be activated for an alarm condition. Setting this OID to alarmRelay3 (4) causes relay 3 to be activated for an alarm condition. Setting this OID to alarmRelay4 (5) causes relay 4 to be activated for an alarm condition. Setting this OID to alarmRelay5 (6) causes relay 5 to be activated for an alarm condition. Setting this OID to alarmRelay6 (7) causes relay 6 to be activated for an alarm condition. Setting this OID to alarmMinor (8) causes the Minor relay to be activated for an alarm condition. Setting this OID to alarmMajor (9) causes the Major relay to be activated for an alarm condition." ::= { dm3ConfigConvAlarms 1 } dm3ConfigConvLowVoltAlarm OBJECT-TYPE SYNTAX INTEGER { alarmIgnore (1), alarmRelay1 (2), alarmRelay2 (3), alarmRelay3 (4), alarmRelay4 (5), alarmRelay5 (6), alarmRelay6 (7), alarmMinor (8), alarmMajor (9) } ACCESS read-write STATUS mandatory DESCRIPTION "For the Converter Low Voltage Alarm; Setting this OID to alarmIgnore (1) results in the alarm condition being ignored. Setting this OID to alarmRelay1 (2) causes relay 1 to be activated for an alarm condition. Setting this OID to alarmRelay2 (3) causes relay 2 to be activated for an alarm condition. Setting this OID to alarmRelay3 (4) causes relay 3 to be activated for an alarm condition. Setting this OID to alarmRelay4 (5) causes relay 4 to be activated for an alarm condition. Setting this OID to alarmRelay5 (6) causes relay 5 to be activated for an alarm condition. Setting this OID to alarmRelay6 (7) causes relay 6 to be activated for an alarm condition. Setting this OID to alarmMinor (8) causes the Minor relay to be activated for an alarm condition. Setting this OID to alarmMajor (9) causes the Major relay to be activated for an alarm condition." ::= { dm3ConfigConvAlarms 2 } dm3ConfigConvConfigAlarm OBJECT-TYPE SYNTAX INTEGER { alarmIgnore (1), alarmRelay1 (2), alarmRelay2 (3), alarmRelay3 (4), alarmRelay4 (5), alarmRelay5 (6), alarmRelay6 (7), alarmMinor (8), alarmMajor (9) } ACCESS read-write STATUS mandatory DESCRIPTION "For the Converter Configuration Alarm (indicating a new converter has been detected); Setting this OID to alarmIgnore (1) results in the alarm condition being ignored. Setting this OID to alarmRelay1 (2) causes relay 1 to be activated for an alarm condition. Setting this OID to alarmRelay2 (3) causes relay 2 to be activated for an alarm condition. Setting this OID to alarmRelay3 (4) causes relay 3 to be activated for an alarm condition. Setting this OID to alarmRelay4 (5) causes relay 4 to be activated for an alarm condition. Setting this OID to alarmRelay5 (6) causes relay 5 to be activated for an alarm condition. Setting this OID to alarmRelay6 (7) causes relay 6 to be activated for an alarm condition. Setting this OID to alarmMinor (8) causes the Minor relay to be activated for an alarm condition. Setting this OID to alarmMajor (9) causes the Major relay to be activated for an alarm condition." ::= { dm3ConfigConvAlarms 3 } dm3ConfigConv1ofNAlarm OBJECT-TYPE SYNTAX INTEGER { alarmIgnore (1), alarmRelay1 (2), alarmRelay2 (3), alarmRelay3 (4), alarmRelay4 (5), alarmRelay5 (6), alarmRelay6 (7), alarmMinor (8), alarmMajor (9) } ACCESS read-write STATUS mandatory DESCRIPTION "For the Converter 1ofN Alarm (indicating action if ONE converter of a N+1 system has failed); Setting this OID to alarmIgnore (1) results in the alarm condition being ignored. Setting this OID to alarmRelay1 (2) causes relay 1 to be activated for an alarm condition. Setting this OID to alarmRelay2 (3) causes relay 2 to be activated for an alarm condition. Setting this OID to alarmRelay3 (4) causes relay 3 to be activated for an alarm condition. Setting this OID to alarmRelay4 (5) causes relay 4 to be activated for an alarm condition. Setting this OID to alarmRelay5 (6) causes relay 5 to be activated for an alarm condition. Setting this OID to alarmRelay6 (7) causes relay 6 to be activated for an alarm condition. Setting this OID to alarmMinor (8) causes the Minor relay to be activated for an alarm condition. Setting this OID to alarmMajor (9) causes the Major relay to be activated for an alarm condition." ::= { dm3ConfigConvAlarms 4 } dm3ConfigConv2ofNAlarm OBJECT-TYPE SYNTAX INTEGER { alarmIgnore (1), alarmRelay1 (2), alarmRelay2 (3), alarmRelay3 (4), alarmRelay4 (5), alarmRelay5 (6), alarmRelay6 (7), alarmMinor (8), alarmMajor (9) } ACCESS read-write STATUS mandatory DESCRIPTION "For the Converter 2ofN Alarm (indicating action if TWO OR MORE converters of a N+1 system has failed); Setting this OID to alarmIgnore (1) results in the alarm condition being ignored. Setting this OID to alarmRelay1 (2) causes relay 1 to be activated for an alarm condition. Setting this OID to alarmRelay2 (3) causes relay 2 to be activated for an alarm condition. Setting this OID to alarmRelay3 (4) causes relay 3 to be activated for an alarm condition. Setting this OID to alarmRelay4 (5) causes relay 4 to be activated for an alarm condition. Setting this OID to alarmRelay5 (6) causes relay 5 to be activated for an alarm condition. Setting this OID to alarmRelay6 (7) causes relay 6 to be activated for an alarm condition. Setting this OID to alarmMinor (8) causes the Minor relay to be activated for an alarm condition. Setting this OID to alarmMajor (9) causes the Major relay to be activated for an alarm condition." ::= { dm3ConfigConvAlarms 5 } dm3ConfigConvDiagAlarm OBJECT-TYPE SYNTAX INTEGER { alarmIgnore (1), alarmRelay1 (2), alarmRelay2 (3), alarmRelay3 (4), alarmRelay4 (5), alarmRelay5 (6), alarmRelay6 (7), alarmMinor (8), alarmMajor (9), alarmNofN (10) } ACCESS read-write STATUS mandatory DESCRIPTION "For the Converter Diagnostics Alarm; Setting this OID to alarmIgnore (1) results in the alarm condition being ignored. Setting this OID to alarmRelay1 (2) causes relay 1 to be activated for an alarm condition. Setting this OID to alarmRelay2 (3) causes relay 2 to be activated for an alarm condition. Setting this OID to alarmRelay3 (4) causes relay 3 to be activated for an alarm condition. Setting this OID to alarmRelay4 (5) causes relay 4 to be activated for an alarm condition. Setting this OID to alarmRelay5 (6) causes relay 5 to be activated for an alarm condition. Setting this OID to alarmRelay6 (7) causes relay 6 to be activated for an alarm condition. Setting this OID to alarmMinor (8) causes the Minor relay to be activated for an alarm condition. Setting this OID to alarmMajor (9) causes the Major relay to be activated for an alarm condition. Setting this OID to alarmNofN (10) causes the alarm specified in the dm3ConfigConv1ofNAlarm OID to be activated if ONE converter fails in an N+1 system. It causes the alarm specified in the dm3ConfigConv2ofNAlarm OID to be activated if TWO OR MORE converters fail in an N+1 system." ::= { dm3ConfigConvAlarms 6 } dm3ConfigConvImbalanceAlarm OBJECT-TYPE SYNTAX INTEGER { alarmIgnore (1), alarmRelay1 (2), alarmRelay2 (3), alarmRelay3 (4), alarmRelay4 (5), alarmRelay5 (6), alarmRelay6 (7), alarmMinor (8), alarmMajor (9), alarmNofN (10) } ACCESS read-write STATUS mandatory DESCRIPTION "For the Converter Imbalance Alarm; Setting this OID to alarmIgnore (1) results in the alarm condition being ignored. Setting this OID to alarmRelay1 (2) causes relay 1 to be activated for an alarm condition. Setting this OID to alarmRelay2 (3) causes relay 2 to be activated for an alarm condition. Setting this OID to alarmRelay3 (4) causes relay 3 to be activated for an alarm condition. Setting this OID to alarmRelay4 (5) causes relay 4 to be activated for an alarm condition. Setting this OID to alarmRelay5 (6) causes relay 5 to be activated for an alarm condition. Setting this OID to alarmRelay6 (7) causes relay 6 to be activated for an alarm condition. Setting this OID to alarmMinor (8) causes the Minor relay to be activated for an alarm condition. Setting this OID to alarmMajor (9) causes the Major relay to be activated for an alarm condition. Setting this OID to alarmNofN (10) causes the alarm specified in the dm3ConfigConv1ofNAlarm OID to be activated if ONE converter fails in an N+1 system. It causes the alarm specified in the dm3ConfigConv2ofNAlarm OID to be activated if TWO OR MORE converters fail in an N+1 system." ::= { dm3ConfigConvAlarms 7 } dm3ConfigConvCurrLimitAlarm OBJECT-TYPE SYNTAX INTEGER { alarmIgnore (1), alarmRelay1 (2), alarmRelay2 (3), alarmRelay3 (4), alarmRelay4 (5), alarmRelay5 (6), alarmRelay6 (7), alarmMinor (8), alarmMajor (9), alarmNofN (10) } ACCESS read-write STATUS mandatory DESCRIPTION "For the Converter Current Limit Alarm (indicating the converter is in the Current Limit state); Setting this OID to alarmIgnore (1) results in the alarm condition being ignored. Setting this OID to alarmRelay1 (2) causes relay 1 to be activated for an alarm condition. Setting this OID to alarmRelay2 (3) causes relay 2 to be activated for an alarm condition. Setting this OID to alarmRelay3 (4) causes relay 3 to be activated for an alarm condition. Setting this OID to alarmRelay4 (5) causes relay 4 to be activated for an alarm condition. Setting this OID to alarmRelay5 (6) causes relay 5 to be activated for an alarm condition. Setting this OID to alarmRelay6 (7) causes relay 6 to be activated for an alarm condition. Setting this OID to alarmMinor (8) causes the Minor relay to be activated for an alarm condition. Setting this OID to alarmMajor (9) causes the Major relay to be activated for an alarm condition. Setting this OID to alarmNofN (10) causes the alarm specified in the dm3ConfigConv1ofNAlarm OID to be activated if ONE converter fails in an N+1 system. It causes the alarm specified in the dm3ConfigConv2ofNAlarm OID to be activated if TWO OR MORE converters fail in an N+1 system." ::= { dm3ConfigConvAlarms 8 } dm3ConfigConvStandbyAlarm OBJECT-TYPE SYNTAX INTEGER { alarmIgnore (1), alarmRelay1 (2), alarmRelay2 (3), alarmRelay3 (4), alarmRelay4 (5), alarmRelay5 (6), alarmRelay6 (7), alarmMinor (8), alarmMajor (9), alarmNofN (10) } ACCESS read-write STATUS mandatory DESCRIPTION "For the Converter Standby Alarm (indicating the converter is in the Standby state); Setting this OID to alarmIgnore (1) results in the alarm condition being ignored. Setting this OID to alarmRelay1 (2) causes relay 1 to be activated for an alarm condition. Setting this OID to alarmRelay2 (3) causes relay 2 to be activated for an alarm condition. Setting this OID to alarmRelay3 (4) causes relay 3 to be activated for an alarm condition. Setting this OID to alarmRelay4 (5) causes relay 4 to be activated for an alarm condition. Setting this OID to alarmRelay5 (6) causes relay 5 to be activated for an alarm condition. Setting this OID to alarmRelay6 (7) causes relay 6 to be activated for an alarm condition. Setting this OID to alarmMinor (8) causes the Minor relay to be activated for an alarm condition. Setting this OID to alarmMajor (9) causes the Major relay to be activated for an alarm condition. Setting this OID to alarmNofN (10) causes the alarm specified in the dm3ConfigConv1ofNAlarm OID to be activated if ONE converter fails in an N+1 system. It causes the alarm specified in the dm3ConfigConv2ofNAlarm OID to be activated if TWO OR MORE converters fail in an N+1 system." ::= { dm3ConfigConvAlarms 9 } dm3ConfigConvFanFailAlarm OBJECT-TYPE SYNTAX INTEGER { alarmIgnore (1), alarmRelay1 (2), alarmRelay2 (3), alarmRelay3 (4), alarmRelay4 (5), alarmRelay5 (6), alarmRelay6 (7), alarmMinor (8), alarmMajor (9), alarmNofN (10) } ACCESS read-write STATUS mandatory DESCRIPTION "For the Converter Fan Fail Alarm; Setting this OID to alarmIgnore (1) results in the alarm condition being ignored. Setting this OID to alarmRelay1 (2) causes relay 1 to be activated for an alarm condition. Setting this OID to alarmRelay2 (3) causes relay 2 to be activated for an alarm condition. Setting this OID to alarmRelay3 (4) causes relay 3 to be activated for an alarm condition. Setting this OID to alarmRelay4 (5) causes relay 4 to be activated for an alarm condition. Setting this OID to alarmRelay5 (6) causes relay 5 to be activated for an alarm condition. Setting this OID to alarmRelay6 (7) causes relay 6 to be activated for an alarm condition. Setting this OID to alarmMinor (8) causes the Minor relay to be activated for an alarm condition. Setting this OID to alarmMajor (9) causes the Major relay to be activated for an alarm condition. Setting this OID to alarmNofN (10) causes the alarm specified in the dm3ConfigConv1ofNAlarm OID to be activated if ONE converter fails in an N+1 system. It causes the alarm specified in the dm3ConfigConv2ofNAlarm OID to be activated if TWO OR MORE converters fail in an N+1 system." ::= { dm3ConfigConvAlarms 10 } dm3ConfigConvFailAlarm OBJECT-TYPE SYNTAX INTEGER { alarmIgnore (1), alarmRelay1 (2), alarmRelay2 (3), alarmRelay3 (4), alarmRelay4 (5), alarmRelay5 (6), alarmRelay6 (7), alarmMinor (8), alarmMajor (9), alarmNofN (10) } ACCESS read-write STATUS mandatory DESCRIPTION "For the Converter Fail Alarm; Setting this OID to alarmIgnore (1) results in the alarm condition being ignored. Setting this OID to alarmRelay1 (2) causes relay 1 to be activated for an alarm condition. Setting this OID to alarmRelay2 (3) causes relay 2 to be activated for an alarm condition. Setting this OID to alarmRelay3 (4) causes relay 3 to be activated for an alarm condition. Setting this OID to alarmRelay4 (5) causes relay 4 to be activated for an alarm condition. Setting this OID to alarmRelay5 (6) causes relay 5 to be activated for an alarm condition. Setting this OID to alarmRelay6 (7) causes relay 6 to be activated for an alarm condition. Setting this OID to alarmMinor (8) causes the Minor relay to be activated for an alarm condition. Setting this OID to alarmMajor (9) causes the Major relay to be activated for an alarm condition. Setting this OID to alarmNofN (10) causes the alarm specified in the dm3ConfigConv1ofNAlarm OID to be activated if ONE converter fails in an N+1 system. It causes the alarm specified in the dm3ConfigConv2ofNAlarm OID to be activated if TWO OR MORE converters fail in an N+1 system." ::= { dm3ConfigConvAlarms 11 } dm3ConfigConvHwVoltAlarm OBJECT-TYPE SYNTAX INTEGER { alarmIgnore (1), alarmRelay1 (2), alarmRelay2 (3), alarmRelay3 (4), alarmRelay4 (5), alarmRelay5 (6), alarmRelay6 (7), alarmMinor (8), alarmMajor (9), alarmNofN (10) } ACCESS read-write STATUS mandatory DESCRIPTION "For the Converter Voltage Alarm (indicating voltage outside realistic limits, or a possible measurement fault); Setting this OID to alarmIgnore (1) results in the alarm condition being ignored. Setting this OID to alarmRelay1 (2) causes relay 1 to be activated for an alarm condition. Setting this OID to alarmRelay2 (3) causes relay 2 to be activated for an alarm condition. Setting this OID to alarmRelay3 (4) causes relay 3 to be activated for an alarm condition. Setting this OID to alarmRelay4 (5) causes relay 4 to be activated for an alarm condition. Setting this OID to alarmRelay5 (6) causes relay 5 to be activated for an alarm condition. Setting this OID to alarmRelay6 (7) causes relay 6 to be activated for an alarm condition. Setting this OID to alarmMinor (8) causes the Minor relay to be activated for an alarm condition. Setting this OID to alarmMajor (9) causes the Major relay to be activated for an alarm condition. Setting this OID to alarmNofN (10) causes the alarm specified in the dm3ConfigConv1ofNAlarm OID to be activated if ONE converter fails in an N+1 system. It causes the alarm specified in the dm3ConfigConv2ofNAlarm OID to be activated if TWO OR MORE converters fail in an N+1 system." ::= { dm3ConfigConvAlarms 12 } -- the dm3ConfigOutputRelays group dm3ConfigOutRlyTableSize OBJECT-TYPE SYNTAX INTEGER ACCESS read-only STATUS mandatory DESCRIPTION "The number of DC powerplant Output Relays controllable by this IP address." ::= { dm3ConfigOutputRelays 1 } dm3ConfigOutRlyTable OBJECT-TYPE SYNTAX SEQUENCE OF ConfigOutRlyEntry ACCESS not-accessible STATUS mandatory DESCRIPTION "Allows for accessing settings of the Output Relays. The number of entries is contained in the dm3ConfigOutRlyTableSize OID." ::= { dm3ConfigOutputRelays 2 } dm3ConfigOutRlyEntry OBJECT-TYPE SYNTAX ConfigOutRlyEntry ACCESS not-accessible STATUS mandatory DESCRIPTION "The output relay to configure." INDEX { dm3ConfigOutRlyIndex } ::= { dm3ConfigOutRlyTable 1 } ConfigOutRlyEntry ::= SEQUENCE { dm3ConfigOutRlyIndex INTEGER, dm3ConfigOutRlyName DisplayString, dm3ConfigOutRlyDelay INTEGER, dm3ConfigOutRlyAlarm INTEGER } dm3ConfigOutRlyIndex OBJECT-TYPE SYNTAX INTEGER ACCESS read-only STATUS mandatory DESCRIPTION "The index to the DC powerplant output relay." ::= { dm3ConfigOutRlyEntry 1 } dm3ConfigOutRlyName OBJECT-TYPE SYNTAX DisplayString ACCESS read-write STATUS mandatory DESCRIPTION "The name of the output relay. The maximum value is 16 characters." ::= { dm3ConfigOutRlyEntry 2 } dm3ConfigOutRlyDelay OBJECT-TYPE SYNTAX INTEGER ACCESS read-write STATUS mandatory DESCRIPTION "Output Relay Delay. This OID represents the time delay from the initiation of an output relay action to when the output relay action does occur. If the alarm condition disappears before the end of the delay, no action will occur. Delay for Major and Minor alarms is not configurable and is always set to 0. Values are represented in hundredths of seconds. Attempts to set the value above or below the acceptable range of the powerplant will cause the value to be set at the high or low point of the range respectively." ::= { dm3ConfigOutRlyEntry 3 } dm3ConfigOutRlyAlarm OBJECT-TYPE SYNTAX INTEGER { alarmIgnore (1), alarmRelay1 (2), alarmRelay2 (3), alarmRelay3 (4), alarmRelay4 (5), alarmRelay5 (6), alarmRelay6 (7), alarmMinor (8), alarmMajor (9) } ACCESS read-write STATUS mandatory DESCRIPTION "Output Relay Alarm. This setting indicates what action to perform in the event of an output relay alarm condition; Setting this OID to alarmIgnore (1) results in the alarm condition being ignored. Setting this OID to alarmRelay1 (2) causes relay 1 to be activated for an alarm condition. Setting this OID to alarmRelay2 (3) causes relay 2 to be activated for an alarm condition. Setting this OID to alarmRelay3 (4) causes relay 3 to be activated for an alarm condition. Setting this OID to alarmRelay4 (5) causes relay 4 to be activated for an alarm condition. Setting this OID to alarmRelay5 (6) causes relay 5 to be activated for an alarm condition. Setting this OID to alarmRelay6 (7) causes relay 6 to be activated for an alarm condition. Setting this OID to alarmMinor (8) causes the Minor relay to be activated for an alarm condition. Setting this OID to alarmMajor (9) causes the Major relay to be activated for an alarm condition. Relay Alarm for Major and Minor alarms is not configurable and is always set to alarmMajor and alarmMinor respectively." ::= { dm3ConfigOutRlyEntry 4 } -- the dm3ConfigInputRelays group dm3ConfigInRlyTableSize OBJECT-TYPE SYNTAX INTEGER ACCESS read-only STATUS mandatory DESCRIPTION "The number of DC powerplant Input Relays controllable by this IP address." ::= { dm3ConfigInputRelays 1 } dm3ConfigInRlyTable OBJECT-TYPE SYNTAX SEQUENCE OF ConfigInRlyEntry ACCESS not-accessible STATUS mandatory DESCRIPTION "Allows for accessing settings of the Input Relays. The number of entries is contained in the dm3ConfigInRlyTableSize OID." ::= { dm3ConfigInputRelays 2 } dm3ConfigInRlyEntry OBJECT-TYPE SYNTAX ConfigInRlyEntry ACCESS not-accessible STATUS mandatory DESCRIPTION "The input relay to configure." INDEX { dm3ConfigInRlyIndex } ::= { dm3ConfigInRlyTable 1 } ConfigInRlyEntry ::= SEQUENCE { dm3ConfigInRlyIndex INTEGER, dm3ConfigInRlyName DisplayString, dm3ConfigInRlyDelay INTEGER, dm3ConfigInRlyAlarm INTEGER } dm3ConfigInRlyIndex OBJECT-TYPE SYNTAX INTEGER ACCESS read-only STATUS mandatory DESCRIPTION "The index to the DC powerplant input relay." ::= { dm3ConfigInRlyEntry 1 } dm3ConfigInRlyName OBJECT-TYPE SYNTAX DisplayString ACCESS read-write STATUS mandatory DESCRIPTION "The name of the input relay. The maximum value is 16 characters." ::= { dm3ConfigInRlyEntry 2 } dm3ConfigInRlyDelay OBJECT-TYPE SYNTAX INTEGER ACCESS read-write STATUS mandatory DESCRIPTION "Input Relay Delay. This OID represents the time delay from the initiation of an input relay action to when the input relay action does occur. If the alarm condition disappears before the end of the delay, no action will occur. Values are represented in hundredths of seconds. Attempts to set the value above or below the acceptable range of the powerplant will cause the value to be set at the high or low point of the range respectively." ::= { dm3ConfigInRlyEntry 3 } dm3ConfigInRlyAlarm OBJECT-TYPE SYNTAX INTEGER { alarmIgnore (1), alarmRelay1 (2), alarmRelay2 (3), alarmRelay3 (4), alarmRelay4 (5), alarmRelay5 (6), alarmRelay6 (7), alarmMinor (8), alarmMajor (9) } ACCESS read-write STATUS mandatory DESCRIPTION "Input Relay Alarm. This setting indicates what action to perform in the event of an input relay alarm condition; Setting this OID to alarmIgnore (1) results in the alarm condition being ignored. Setting this OID to alarmRelay1 (2) causes relay 1 to be activated for an alarm condition. Setting this OID to alarmRelay2 (3) causes relay 2 to be activated for an alarm condition. Setting this OID to alarmRelay3 (4) causes relay 3 to be activated for an alarm condition. Setting this OID to alarmRelay4 (5) causes relay 4 to be activated for an alarm condition. Setting this OID to alarmRelay5 (6) causes relay 5 to be activated for an alarm condition. Setting this OID to alarmRelay6 (7) causes relay 6 to be activated for an alarm condition. Setting this OID to alarmMinor (8) causes the Minor relay to be activated for an alarm condition. Setting this OID to alarmMajor (9) causes the Major relay to be activated for an alarm condition." ::= { dm3ConfigInRlyEntry 4 } -- the dm3ConfigBreakers group dm3ConfigBreakersTableSize OBJECT-TYPE SYNTAX INTEGER ACCESS read-only STATUS mandatory DESCRIPTION "The number of DC powerplant circuit breakers controllable by this IP address." ::= { dm3ConfigBreakers 1 } dm3ConfigBreakersTable OBJECT-TYPE SYNTAX SEQUENCE OF ConfigBreakersEntry ACCESS not-accessible STATUS mandatory DESCRIPTION "Allows for accessing settings of the circuit breakers. The number of entries is contained in the dm3ConfigBreakersTableSize OID." ::= { dm3ConfigBreakers 2 } dm3ConfigBreakersEntry OBJECT-TYPE SYNTAX ConfigBreakersEntry ACCESS not-accessible STATUS mandatory DESCRIPTION "The circuit breaker to configure." INDEX { dm3ConfigBreakersIndex } ::= { dm3ConfigBreakersTable 1 } ConfigBreakersEntry ::= SEQUENCE { dm3ConfigBreakersIndex INTEGER, dm3ConfigBreakersName DisplayString, dm3ConfigBreakersAlarm INTEGER } dm3ConfigBreakersIndex OBJECT-TYPE SYNTAX INTEGER ACCESS read-only STATUS mandatory DESCRIPTION "The index to the DC powerplant circuit breaker." ::= { dm3ConfigBreakersEntry 1 } dm3ConfigBreakersName OBJECT-TYPE SYNTAX DisplayString ACCESS read-write STATUS mandatory DESCRIPTION "The name of the circuit breaker. The maximum value is 16 characters." ::= { dm3ConfigBreakersEntry 2 } dm3ConfigBreakersAlarm OBJECT-TYPE SYNTAX INTEGER { alarmIgnore (1), alarmRelay1 (2), alarmRelay2 (3), alarmRelay3 (4), alarmRelay4 (5), alarmRelay5 (6), alarmRelay6 (7), alarmMinor (8), alarmMajor (9) } ACCESS read-write STATUS mandatory DESCRIPTION "Circuit Breaker Alarm. This setting indicates what action to perform in the event of a circuit breaker alarm condition; Setting this OID to alarmIgnore (1) results in the alarm condition being ignored. Setting this OID to alarmRelay1 (2) causes relay 1 to be activated for an alarm condition. Setting this OID to alarmRelay2 (3) causes relay 2 to be activated for an alarm condition. Setting this OID to alarmRelay3 (4) causes relay 3 to be activated for an alarm condition. Setting this OID to alarmRelay4 (5) causes relay 4 to be activated for an alarm condition. Setting this OID to alarmRelay5 (6) causes relay 5 to be activated for an alarm condition. Setting this OID to alarmRelay6 (7) causes relay 6 to be activated for an alarm condition. Setting this OID to alarmMinor (8) causes the Minor relay to be activated for an alarm condition. Setting this OID to alarmMajor (9) causes the Major relay to be activated for an alarm condition." ::= { dm3ConfigBreakersEntry 3 } -- the dm3ConfigFuses group dm3ConfigFusesTableSize OBJECT-TYPE SYNTAX INTEGER ACCESS read-only STATUS mandatory DESCRIPTION "The number of DC powerplant Fuses controllable by this IP address." ::= { dm3ConfigFuses 1 } dm3ConfigFusesTable OBJECT-TYPE SYNTAX SEQUENCE OF ConfigFusesEntry ACCESS not-accessible STATUS mandatory DESCRIPTION "Allows for accessing settings of the Fuses. The number of entries is contained in the dm3ConfigFusesTableSize OID." ::= { dm3ConfigFuses 2 } dm3ConfigFusesEntry OBJECT-TYPE SYNTAX ConfigFusesEntry ACCESS not-accessible STATUS mandatory DESCRIPTION "The fuse to configure." INDEX { dm3ConfigFusesIndex } ::= { dm3ConfigFusesTable 1 } ConfigFusesEntry ::= SEQUENCE { dm3ConfigFusesIndex INTEGER, dm3ConfigFusesName DisplayString, dm3ConfigFusesAlarm INTEGER } dm3ConfigFusesIndex OBJECT-TYPE SYNTAX INTEGER ACCESS read-only STATUS mandatory DESCRIPTION "The index to the DC powerplant fuse." ::= { dm3ConfigFusesEntry 1 } dm3ConfigFusesName OBJECT-TYPE SYNTAX DisplayString ACCESS read-write STATUS mandatory DESCRIPTION "The name of the fuse. The maximum value is 16 characters." ::= { dm3ConfigFusesEntry 2 } dm3ConfigFusesAlarm OBJECT-TYPE SYNTAX INTEGER { alarmIgnore (1), alarmRelay1 (2), alarmRelay2 (3), alarmRelay3 (4), alarmRelay4 (5), alarmRelay5 (6), alarmRelay6 (7), alarmMinor (8), alarmMajor (9) } ACCESS read-write STATUS mandatory DESCRIPTION "Fuses Alarm. This setting indicates what action to perform in the event of a Fuse alarm condition; Setting this OID to alarmIgnore (1) results in the alarm condition being ignored. Setting this OID to alarmRelay1 (2) causes relay 1 to be activated for an alarm condition. Setting this OID to alarmRelay2 (3) causes relay 2 to be activated for an alarm condition. Setting this OID to alarmRelay3 (4) causes relay 3 to be activated for an alarm condition. Setting this OID to alarmRelay4 (5) causes relay 4 to be activated for an alarm condition. Setting this OID to alarmRelay5 (6) causes relay 5 to be activated for an alarm condition. Setting this OID to alarmRelay6 (7) causes relay 6 to be activated for an alarm condition. Setting this OID to alarmMinor (8) causes the Minor relay to be activated for an alarm condition. Setting this OID to alarmMajor (9) causes the Major relay to be activated for an alarm condition." ::= { dm3ConfigFusesEntry 3 } -- the dm3StatusSystem group dm3StatusSystemTemp OBJECT-TYPE SYNTAX INTEGER ACCESS read-only STATUS mandatory DESCRIPTION "System temperature based on sensor on Master Controller PCB. Values are represented in thousandths of a degree. Units are displayed in the scale shown in the 'dm3StatusSysTempUnits' OID (Celsius or Fahrenheit)." ::= { dm3StatusSystem 1 } dm3StatusSystemStart OBJECT-TYPE SYNTAX DisplayString ACCESS read-only STATUS mandatory DESCRIPTION "Time stamp at DC powerplant initialization. The time is represented as MMM,DD,YYYY,HH:MM:SS." ::= { dm3StatusSystem 2 } dm3StatusSysRemoteAccess OBJECT-TYPE SYNTAX INTEGER { accessEnabled (1), accessDisabled (2) } ACCESS read-only STATUS mandatory DESCRIPTION "Remote Access indicator This setting indicates if configuration (write) access to the powerplant is enabled or disabled at the powerplant level. This value will be accessEnabled (1) if remote configuration is enabled, and accessDisabled (2) if remote configuration is disabled." ::= { dm3StatusSystem 3 } dm3StatusSysSecurityLevel OBJECT-TYPE SYNTAX INTEGER ACCESS read-only STATUS mandatory DESCRIPTION "This variable shows the current active security access level of controller. This can only be changed directly from the front panel." ::= { dm3StatusSystem 4 } dm3StatusSysTempSanity OBJECT-TYPE SYNTAX INTEGER{ saneYES (1), saneNO (2) } ACCESS read-only STATUS mandatory DESCRIPTION "System temperature sanity indicator. Indicates if the system temperature is reasonable. Reasonable is defined based on powerplant type. A value of saneYes (1) indicates temperature is reasonable, a value of saneNo (2) indicates it is not." ::= { dm3StatusSystem 5 } dm3StatusSysAlarmState OBJECT-TYPE SYNTAX INTEGER{ alarmMinor (1), alarmMajor (2), alarmBoth (3), alarmNone (4) } ACCESS read-only STATUS mandatory DESCRIPTION "System Alarm State. Reflects the alarm status of the overall DC system. If a minor alarm is present, the value will be alarmMinor(1). If a major alarm is present, the value will be alarmMajor(2). If both minor and a major alarm is present, the value will be alarmBoth(3). If no alarm is present, the value will be alarmNone(4)." ::= { dm3StatusSystem 6 } dm3StatusSysTempUnits OBJECT-TYPE SYNTAX INTEGER { celsius(1), fahrenheit(2) } ACCESS read-only STATUS mandatory DESCRIPTION "The temperature scale used to display the temperature in the DC system, Celsius(1) or Fahrenheit(2). This setting is based on the system preferences configuration in the agent." ::= { dm3StatusSystem 7 } -- the dm3StatusAlarms group dm3StatusAlarmsTableSize OBJECT-TYPE SYNTAX INTEGER ACCESS read-only STATUS mandatory DESCRIPTION "The number of DC powerplant alarms viewable by this IP address." ::= { dm3StatusAlarms 1 } dm3StatusAlarmsTable OBJECT-TYPE SYNTAX SEQUENCE OF StatusAlarmsEntry ACCESS not-accessible STATUS mandatory DESCRIPTION "Allows for accessing system alarms. The number of entries is contained in the dm3StatusAlarmsTableSize OID." ::= { dm3StatusAlarms 2 } dm3StatusAlarmsEntry OBJECT-TYPE SYNTAX StatusAlarmsEntry ACCESS not-accessible STATUS mandatory DESCRIPTION "The alarm to display." INDEX { dm3StatusAlarmsIndex } ::= { dm3StatusAlarmsTable 1 } StatusAlarmsEntry ::= SEQUENCE { dm3StatusAlarmsIndex INTEGER, dm3StatusAlarmsText DisplayString } dm3StatusAlarmsIndex OBJECT-TYPE SYNTAX INTEGER ACCESS read-only STATUS mandatory DESCRIPTION "The index of the system alarm." ::= { dm3StatusAlarmsEntry 1 } dm3StatusAlarmsText OBJECT-TYPE SYNTAX DisplayString ACCESS read-only STATUS mandatory DESCRIPTION "The 16 character text describing the active alarm condition." ::= { dm3StatusAlarmsEntry 2 } -- the dm3StatusBattery group dm3StatusBattCurrent OBJECT-TYPE SYNTAX INTEGER ACCESS read-only STATUS mandatory DESCRIPTION "Battery Current: This OID shows the battery current in thousandths of Amps (mA)." ::= { dm3StatusBattery 1 } dm3StatusBattTemp OBJECT-TYPE SYNTAX INTEGER ACCESS read-only STATUS mandatory DESCRIPTION "Battery Temperature: Values are represented in thousandths of a degree. Units are displayed in the scale shown in the 'dm3StatusSysTempUnits' OID (Celsius or Fahrenheit)." ::= { dm3StatusBattery 2 } dm3StatusBattCurrentSanity OBJECT-TYPE SYNTAX INTEGER{ saneYES (1), saneNO (2) } ACCESS read-only STATUS mandatory DESCRIPTION "Battery current sanity indicator. Indicates if the battery current is reasonable. Reasonable is defined based on powerplant type. A value of saneYes (1) indicates current is reasonable, a value of saneNo (2) indicates it is not." ::= { dm3StatusBattery 3 } dm3StatusBattTempSanity OBJECT-TYPE SYNTAX INTEGER{ saneYES (1), saneNO (2) } ACCESS read-only STATUS mandatory DESCRIPTION "Battery temperature sanity indicator. Indicates if the battery temperature is reasonable. Reasonable is defined based on powerplant type. A value of saneYes (1) indicates temperature is reasonable, a value of saneNo (2) indicates it is not." ::= { dm3StatusBattery 4 } -- the dm3StatusOEM group dm3StatusOEMrectOffset OBJECT-TYPE SYNTAX INTEGER ACCESS read-only STATUS mandatory DESCRIPTION "This OID shows the rectifier offset value in thousandths of Volts (mV)." ::= { dm3StatusOEM 1 } dm3StatusOEMrectGain OBJECT-TYPE SYNTAX INTEGER ACCESS read-only STATUS mandatory DESCRIPTION "This OID shows the rectifier gain value in thousandths of Volts (mV/V)." ::= { dm3StatusOEM 2 } dm3StatusOEMconvOffset OBJECT-TYPE SYNTAX INTEGER ACCESS read-only STATUS mandatory DESCRIPTION "This OID shows the converter offset value in thousandths of Volts (mV)." ::= { dm3StatusOEM 3 } dm3StatusOEMconvGain OBJECT-TYPE SYNTAX INTEGER ACCESS read-only STATUS mandatory DESCRIPTION "This OID shows the converter gain value in thousandths of Volts (mV/V)." ::= { dm3StatusOEM 4 } dm3StatusOEMshuntOffset OBJECT-TYPE SYNTAX INTEGER ACCESS read-only STATUS mandatory DESCRIPTION "This OID shows the shunt offset value in thousandths of Amps (mA)." ::= { dm3StatusOEM 5 } dm3StatusOEMshuntGain OBJECT-TYPE SYNTAX INTEGER ACCESS read-only STATUS mandatory DESCRIPTION "This OID shows the shunt gain value in thousandths of Amps (mA/A)." ::= { dm3StatusOEM 6 } -- the dm3StatusLVD group dm3StatusLVDTableSize OBJECT-TYPE SYNTAX INTEGER ACCESS read-only STATUS mandatory DESCRIPTION "The number of DC powerplant LVDs viewable by this IP address." ::= { dm3StatusLVD 1 } dm3StatusLVDTable OBJECT-TYPE SYNTAX SEQUENCE OF StatusLVDEntry ACCESS not-accessible STATUS mandatory DESCRIPTION "Allows for accessing settings of the LVDs. The number of entries is contained in the dm3StatusLVDTableSize OID." ::= { dm3StatusLVD 2 } dm3StatusLVDEntry OBJECT-TYPE SYNTAX StatusLVDEntry ACCESS not-accessible STATUS mandatory DESCRIPTION "The LVD to gather status from." INDEX { dm3StatusLVDIndex } ::= { dm3StatusLVDTable 1 } StatusLVDEntry ::= SEQUENCE { dm3StatusLVDIndex INTEGER, dm3StatusLVDName DisplayString, dm3StatusLVDState INTEGER, dm3StatusLVDHwFault INTEGER } dm3StatusLVDIndex OBJECT-TYPE SYNTAX INTEGER ACCESS read-only STATUS mandatory DESCRIPTION "The index to the DC powerplant LVD." ::= { dm3StatusLVDEntry 1 } dm3StatusLVDName OBJECT-TYPE SYNTAX DisplayString ACCESS read-only STATUS mandatory DESCRIPTION "The name of the LVD. The maximum size is 16 characters. The name is set by using the dm3ConfigLVDName OID. This OID is provided for informational purposes only." ::= { dm3StatusLVDEntry 2 } dm3StatusLVDState OBJECT-TYPE SYNTAX INTEGER { statusClosed (1), statusOpened (2) } ACCESS read-only STATUS mandatory DESCRIPTION "Getting this OID will return statusClosed (1) if the LVD is closed. statusOpened (2) will be returned if the LVD is opened." ::= { dm3StatusLVDEntry 3 } dm3StatusLVDHwFault OBJECT-TYPE SYNTAX INTEGER { statusFault (1), statusNofault (2) } ACCESS read-only STATUS mandatory DESCRIPTION "Getting this OID will return statusFault (1) if the LVD is faulted. statusNofault (2) will be returned if the LVD is not faulted." ::= { dm3StatusLVDEntry 4 } -- the dm3StatusRectifier group dm3StatusRectTableSize OBJECT-TYPE SYNTAX INTEGER ACCESS read-only STATUS mandatory DESCRIPTION "The number of DC powerplant rectifiers viewable by this IP address." ::= { dm3StatusRectifier 1 } dm3StatusRectTable OBJECT-TYPE SYNTAX SEQUENCE OF StatusRectEntry ACCESS not-accessible STATUS mandatory DESCRIPTION "Allows for accessing settings of the rectifiers. The number of entries is contained in the dm3StatusRectTableSize OID." ::= { dm3StatusRectifier 2 } dm3StatusRectEntry OBJECT-TYPE SYNTAX StatusRectEntry ACCESS not-accessible STATUS mandatory DESCRIPTION "The rectifier to gather status from." INDEX { dm3StatusRectIndex } ::= { dm3StatusRectTable 1 } StatusRectEntry ::= SEQUENCE { dm3StatusRectIndex INTEGER, dm3StatusRectID INTEGER, dm3StatusRectDesc DisplayString, dm3StatusRectCurrent INTEGER, dm3StatusRectCurrentLimit INTEGER, dm3StatusRectStandby INTEGER, dm3StatusRectFanFail INTEGER, dm3StatusRectFail INTEGER, dm3StatusRectDevType INTEGER, dm3StatusRectPhyAddr INTEGER, dm3StatusRectCfg INTEGER, dm3StatusRectPcbRev INTEGER, dm3StatusRectFwVer INTEGER, dm3StatusRectPresent INTEGER, dm3StatusRectDiagPass INTEGER, dm3StatusRectState INTEGER } dm3StatusRectIndex OBJECT-TYPE SYNTAX INTEGER ACCESS read-only STATUS mandatory DESCRIPTION "The index to the DC powerplant rectifier." ::= { dm3StatusRectEntry 1 } dm3StatusRectID OBJECT-TYPE SYNTAX INTEGER ACCESS read-only STATUS mandatory DESCRIPTION "This OID shows the rectifier ID. This enumerates the number of the rectifier within a group of rectifiers." ::= { dm3StatusRectEntry 2 } dm3StatusRectDesc OBJECT-TYPE SYNTAX DisplayString ACCESS read-only STATUS mandatory DESCRIPTION "This OID shows the 16-character rectifier description." ::= { dm3StatusRectEntry 3 } dm3StatusRectCurrent OBJECT-TYPE SYNTAX INTEGER ACCESS read-only STATUS mandatory DESCRIPTION "This OID shows the rectifier current in thousandths of Amps (mA)." ::= { dm3StatusRectEntry 4 } dm3StatusRectCurrentLimit OBJECT-TYPE SYNTAX INTEGER { statusTrue (1), statusFalse (2) } ACCESS read-only STATUS mandatory DESCRIPTION "Getting this OID will return statusTrue (1) if the rectifier is in the Current Limit state. statusFalse (2) will be returned if the rectifier is not in the Current Limit state." ::= { dm3StatusRectEntry 5 } dm3StatusRectStandby OBJECT-TYPE SYNTAX INTEGER { statusTrue (1), statusFalse (2) } ACCESS read-only STATUS mandatory DESCRIPTION "Getting this OID will return statusTrue (1) if the rectifier is in the Standby state. statusFalse (2) will be returned if the rectifier is not in the Standby state." ::= { dm3StatusRectEntry 6 } dm3StatusRectFanFail OBJECT-TYPE SYNTAX INTEGER { statusTrue (1), statusFalse (2) } ACCESS read-only STATUS mandatory DESCRIPTION "Getting this OID will return statusTrue (1) if the rectifier Fan has failed. statusFalse (2) will be returned if the rectifier Fan has not failed." ::= { dm3StatusRectEntry 7 } dm3StatusRectFail OBJECT-TYPE SYNTAX INTEGER { statusTrue (1), statusFalse (2) } ACCESS read-only STATUS mandatory DESCRIPTION "Getting this OID will return statusTrue (1) if the rectifier has failed. statusFalse (2) will be returned if the rectifier has not failed." ::= { dm3StatusRectEntry 8 } dm3StatusRectDevType OBJECT-TYPE SYNTAX INTEGER ACCESS read-only STATUS mandatory DESCRIPTION "This OID shows the rectifier device type." ::= { dm3StatusRectEntry 9 } dm3StatusRectPhyAddr OBJECT-TYPE SYNTAX INTEGER ACCESS read-only STATUS mandatory DESCRIPTION "This OID shows the rectifier physical address (the address on the bus)." ::= { dm3StatusRectEntry 10 } dm3StatusRectCfg OBJECT-TYPE SYNTAX INTEGER { statusTrue (1), statusFalse (2) } ACCESS read-only STATUS mandatory DESCRIPTION "Getting this OID will return statusTrue (1) if the rectifier is present after power-up or set-configuration. statusFalse (2) will be returned if the rectifier is not configured." ::= { dm3StatusRectEntry 11 } dm3StatusRectPcbRev OBJECT-TYPE SYNTAX INTEGER ACCESS read-only STATUS mandatory DESCRIPTION "This OID shows the rectifier device PCB serial number." ::= { dm3StatusRectEntry 12 } dm3StatusRectFwVer OBJECT-TYPE SYNTAX INTEGER ACCESS read-only STATUS mandatory DESCRIPTION "This OID shows the rectifier device firmware revision." ::= { dm3StatusRectEntry 13 } dm3StatusRectPresent OBJECT-TYPE SYNTAX INTEGER { statusTrue (1), statusFalse (2) } ACCESS read-only STATUS mandatory DESCRIPTION "Getting this OID will return statusTrue (1) if the rectifier is present. statusFalse (2) will be returned if the rectifier is not present." ::= { dm3StatusRectEntry 14 } dm3StatusRectDiagPass OBJECT-TYPE SYNTAX INTEGER { statusTrue (1), statusFalse (2) } ACCESS read-only STATUS mandatory DESCRIPTION "Getting this OID will return statusTrue (1) if the rectifier diagnostics have passed. statusFalse (2) will be returned if the rectifier diagnostics have not passed." ::= { dm3StatusRectEntry 15 } dm3StatusRectState OBJECT-TYPE SYNTAX INTEGER ACCESS read-only STATUS mandatory DESCRIPTION "This OID shows the rectifier device state as defined by the device status register." ::= { dm3StatusRectEntry 16 } dm3StatusSysRectVoltSanity OBJECT-TYPE SYNTAX INTEGER { saneYES (1), saneNO (2) } ACCESS read-only STATUS mandatory DESCRIPTION "Rectifier voltage sanity indicator. Indicates if the rectifier voltage is reasonable. Reasonable is defined based on powerplant type. A value of saneYes (1) indicates voltage is reasonable, a value of saneNo (2) indicates it is not." ::= { dm3StatusRectifier 3 } dm3StatusSysRectAvailable OBJECT-TYPE SYNTAX INTEGER { statusTrue (1), statusFalse (2) } ACCESS read-only STATUS mandatory DESCRIPTION "Getting this OID will return statusTrue (1) if the rectifier is available. statusFalse (2) will be returned if the rectifier is not available." ::= { dm3StatusRectifier 4 } dm3StatusSysRectType OBJECT-TYPE SYNTAX INTEGER ACCESS read-only STATUS mandatory DESCRIPTION "This OID shows the type of rectifier the system has. There can only be a single type of rectifier in the power plant" ::= { dm3StatusRectifier 5 } dm3StatusSysRectVoltage OBJECT-TYPE SYNTAX INTEGER ACCESS read-only STATUS mandatory DESCRIPTION "This OID shows the system level rectifier voltage in thousandths of Volts (mV)." ::= { dm3StatusRectifier 6 } dm3StatusSysRectCurrent OBJECT-TYPE SYNTAX INTEGER ACCESS read-only STATUS mandatory DESCRIPTION "This OID shows the system level rectifier current in thousandths of Amps (mA)." ::= { dm3StatusRectifier 7 } -- the dm3StatusConverter group dm3StatusConvTableSize OBJECT-TYPE SYNTAX INTEGER ACCESS read-only STATUS mandatory DESCRIPTION "The number of DC powerplant converters viewable by this IP address." ::= { dm3StatusConverter 1 } dm3StatusConvTable OBJECT-TYPE SYNTAX SEQUENCE OF StatusConvEntry ACCESS not-accessible STATUS mandatory DESCRIPTION "Allows for viewing status of the converters. The number of entries is contained in the dm3StatusConvTableSize OID." ::= { dm3StatusConverter 2 } dm3StatusConvEntry OBJECT-TYPE SYNTAX StatusConvEntry ACCESS not-accessible STATUS mandatory DESCRIPTION "The converter to gather status from." INDEX { dm3StatusConvIndex } ::= { dm3StatusConvTable 1 } StatusConvEntry ::= SEQUENCE { dm3StatusConvIndex INTEGER, dm3StatusConvID INTEGER, dm3StatusConvDesc DisplayString, dm3StatusConvCurrent INTEGER, dm3StatusConvCurrentLimit INTEGER, dm3StatusConvStandby INTEGER, dm3StatusConvFanFail INTEGER, dm3StatusConvFail INTEGER, dm3StatusConvDevType INTEGER, dm3StatusConvPhyAddr INTEGER, dm3StatusConvCfg INTEGER, dm3StatusConvPcbRev INTEGER, dm3StatusConvFwVer INTEGER, dm3StatusConvPresent INTEGER, dm3StatusConvDiagPass INTEGER, dm3StatusConvState INTEGER } dm3StatusConvIndex OBJECT-TYPE SYNTAX INTEGER ACCESS read-only STATUS mandatory DESCRIPTION "The index to the DC powerplant converter." ::= { dm3StatusConvEntry 1 } dm3StatusConvID OBJECT-TYPE SYNTAX INTEGER ACCESS read-only STATUS mandatory DESCRIPTION "This OID shows the converter ID. This enumerates the number of the converter within a group of converters." ::= { dm3StatusConvEntry 2 } dm3StatusConvDesc OBJECT-TYPE SYNTAX DisplayString ACCESS read-only STATUS mandatory DESCRIPTION "This OID shows the 16 character converter description." ::= { dm3StatusConvEntry 3 } dm3StatusConvCurrent OBJECT-TYPE SYNTAX INTEGER ACCESS read-only STATUS mandatory DESCRIPTION "This OID shows the converter current in thousandths of Amps (mA)." ::= { dm3StatusConvEntry 4 } dm3StatusConvCurrentLimit OBJECT-TYPE SYNTAX INTEGER { statusTrue (1), statusFalse (2) } ACCESS read-only STATUS mandatory DESCRIPTION "Getting this OID will return statusTrue (1) if the converter is in the Current Limit state. statusFalse (2) will be returned if the converter is not in the Current Limit state." ::= { dm3StatusConvEntry 5 } dm3StatusConvStandby OBJECT-TYPE SYNTAX INTEGER { statusTrue (1), statusFalse (2) } ACCESS read-only STATUS mandatory DESCRIPTION "Getting this OID will return statusTrue (1) if the converter is in the Standby state. statusFalse (2) will be returned if the converter is not in the Standby state." ::= { dm3StatusConvEntry 6 } dm3StatusConvFanFail OBJECT-TYPE SYNTAX INTEGER { statusTrue (1), statusFalse (2) } ACCESS read-only STATUS mandatory DESCRIPTION "Getting this OID will return statusTrue (1) if the converter Fan has failed. statusFalse (2) will be returned if the converter Fan has not failed." ::= { dm3StatusConvEntry 7 } dm3StatusConvFail OBJECT-TYPE SYNTAX INTEGER { statusTrue (1), statusFalse (2) } ACCESS read-only STATUS mandatory DESCRIPTION "Getting this OID will return statusTrue (1) if the converter has failed. statusFalse (2) will be returned if the converter has not failed." ::= { dm3StatusConvEntry 8 } dm3StatusConvDevType OBJECT-TYPE SYNTAX INTEGER ACCESS read-only STATUS mandatory DESCRIPTION "This OID shows the converter device type." ::= { dm3StatusConvEntry 9 } dm3StatusConvPhyAddr OBJECT-TYPE SYNTAX INTEGER ACCESS read-only STATUS mandatory DESCRIPTION "This OID shows the converter physical address (the address on the bus)." ::= { dm3StatusConvEntry 10 } dm3StatusConvCfg OBJECT-TYPE SYNTAX INTEGER { statusTrue (1), statusFalse (2) } ACCESS read-only STATUS mandatory DESCRIPTION "Getting this OID will return statusTrue (1) if the converter is present after power-up or set-configuration. statusFalse (2) will be returned if the converter is not configured." ::= { dm3StatusConvEntry 11 } dm3StatusConvPcbRev OBJECT-TYPE SYNTAX INTEGER ACCESS read-only STATUS mandatory DESCRIPTION "This OID shows the converter device PCB serial number." ::= { dm3StatusConvEntry 12 } dm3StatusConvFwVer OBJECT-TYPE SYNTAX INTEGER ACCESS read-only STATUS mandatory DESCRIPTION "This OID shows the converter device firmware version." ::= { dm3StatusConvEntry 13 } dm3StatusConvPresent OBJECT-TYPE SYNTAX INTEGER { statusTrue (1), statusFalse (2) } ACCESS read-only STATUS mandatory DESCRIPTION "Getting this OID will return statusTrue (1) if the converter is present. statusFalse (2) will be returned if the converter is not present." ::= { dm3StatusConvEntry 14 } dm3StatusConvDiagPass OBJECT-TYPE SYNTAX INTEGER { statusTrue (1), statusFalse (2) } ACCESS read-only STATUS mandatory DESCRIPTION "Getting this OID will return statusTrue (1) if the converter diagnostics have passed. statusFalse (2) will be returned if the converter diagnostics have not passed." ::= { dm3StatusConvEntry 15 } dm3StatusConvState OBJECT-TYPE SYNTAX INTEGER ACCESS read-only STATUS mandatory DESCRIPTION "This OID shows the converter state as defined by the device status register." ::= { dm3StatusConvEntry 16 } dm3StatusSysConvVoltSanity OBJECT-TYPE SYNTAX INTEGER{ saneYES (1), saneNO (2) } ACCESS read-only STATUS mandatory DESCRIPTION "Converter voltage sanity indicator. Indicates if the converter voltage is reasonable. Reasonable is defined based on powerplant type. A value of saneYes (1) indicates voltage is reasonable, a value of saneNo (2) indicates it is not." ::= { dm3StatusConverter 3 } dm3StatusSysConvAvailable OBJECT-TYPE SYNTAX INTEGER { statusTrue (1), statusFalse (2) } ACCESS read-only STATUS mandatory DESCRIPTION "Getting this OID will return statusTrue (1) if the converter is available. statusFalse (2) will be returned if the converter is not available." ::= { dm3StatusConverter 4 } dm3StatusSysConvType OBJECT-TYPE SYNTAX INTEGER ACCESS read-only STATUS mandatory DESCRIPTION "This OID shows the converter type." ::= { dm3StatusConverter 5 } dm3StatusSysConvVoltage OBJECT-TYPE SYNTAX INTEGER ACCESS read-only STATUS mandatory DESCRIPTION "This OID shows the system level converter voltage in thousandths of volts (mV)." ::= { dm3StatusConverter 6 } dm3StatusSysConvCurrent OBJECT-TYPE SYNTAX INTEGER ACCESS read-only STATUS mandatory DESCRIPTION "This OID shows the system level converter current in thousandths of Amps (mA)." ::= { dm3StatusConverter 7 } -- the dm3StatusOutputRelays group dm3StatusOutRlyTableSize OBJECT-TYPE SYNTAX INTEGER ACCESS read-only STATUS mandatory DESCRIPTION "The number of DC powerplant output relays viewable by this IP address." ::= { dm3StatusOutputRelays 1 } dm3StatusOutRlyTable OBJECT-TYPE SYNTAX SEQUENCE OF StatusOutRlyEntry ACCESS not-accessible STATUS mandatory DESCRIPTION "Allows for viewing status of the output relays. The number of entries is contained in the dm3StatusOutRlyTableSize OID." ::= { dm3StatusOutputRelays 2 } dm3StatusOutRlyEntry OBJECT-TYPE SYNTAX StatusOutRlyEntry ACCESS not-accessible STATUS mandatory DESCRIPTION "The output relay to gather status from." INDEX { dm3StatusOutRlyIndex } ::= { dm3StatusOutRlyTable 1 } StatusOutRlyEntry ::= SEQUENCE { dm3StatusOutRlyIndex INTEGER, dm3StatusOutRlyName DisplayString, dm3StatusOutRlyStatus INTEGER } dm3StatusOutRlyIndex OBJECT-TYPE SYNTAX INTEGER ACCESS read-only STATUS mandatory DESCRIPTION "The index to the DC powerplant output relay." ::= { dm3StatusOutRlyEntry 1 } dm3StatusOutRlyName OBJECT-TYPE SYNTAX DisplayString ACCESS read-only STATUS mandatory DESCRIPTION "The name of the output relay. The maximum size is 16 characters. The name is set by using the dm3ConfigOutRlyName OID. This OID is provided for informational purposes only." ::= { dm3StatusOutRlyEntry 2 } dm3StatusOutRlyStatus OBJECT-TYPE SYNTAX INTEGER { statusOn (1), statusOff (2) } ACCESS read-only STATUS mandatory DESCRIPTION "Getting this OID will return statusOn (1) if the output relay is enabled/on. statusOff (2) will be returned if the output relay is disabled/off." ::= { dm3StatusOutRlyEntry 3 } -- the dm3StatusInputRelays group dm3StatusInRlyTableSize OBJECT-TYPE SYNTAX INTEGER ACCESS read-only STATUS mandatory DESCRIPTION "The number of DC powerplant input relays viewable by this IP address." ::= { dm3StatusInputRelays 1 } dm3StatusInRlyTable OBJECT-TYPE SYNTAX SEQUENCE OF StatusInRlyEntry ACCESS not-accessible STATUS mandatory DESCRIPTION "Allows for viewing status of the input relays. The number of entries is contained in the dm3StatusInRlyTableSize OID." ::= { dm3StatusInputRelays 2 } dm3StatusInRlyEntry OBJECT-TYPE SYNTAX StatusInRlyEntry ACCESS not-accessible STATUS mandatory DESCRIPTION "The input relays to gather status from." INDEX { dm3StatusInRlyIndex } ::= { dm3StatusInRlyTable 1 } StatusInRlyEntry ::= SEQUENCE { dm3StatusInRlyIndex INTEGER, dm3StatusInRlyName DisplayString, dm3StatusInRlyStatus INTEGER } dm3StatusInRlyIndex OBJECT-TYPE SYNTAX INTEGER ACCESS read-only STATUS mandatory DESCRIPTION "The index to the DC powerplant input relay." ::= { dm3StatusInRlyEntry 1 } dm3StatusInRlyName OBJECT-TYPE SYNTAX DisplayString ACCESS read-only STATUS mandatory DESCRIPTION "The name of the input relay. The maximum size is 16 characters. The name is set by using the dm3ConfigInRlyName OID. This OID is provided for informational purposes only." ::= { dm3StatusInRlyEntry 2 } dm3StatusInRlyStatus OBJECT-TYPE SYNTAX INTEGER { statusOn (1), statusOff (2) } ACCESS read-only STATUS mandatory DESCRIPTION "Getting this OID will return statusOn (1) if the input relay is enabled/on. statusOff (2) will be returned if the input relay is disabled/off." ::= { dm3StatusInRlyEntry 3 } -- the dm3StatusBreakers group dm3StatusBreakersTableSize OBJECT-TYPE SYNTAX INTEGER ACCESS read-only STATUS mandatory DESCRIPTION "The number of DC powerplant circuit breakers viewable by this IP address." ::= { dm3StatusBreakers 1 } dm3StatusBreakersTable OBJECT-TYPE SYNTAX SEQUENCE OF StatusBreakersEntry ACCESS not-accessible STATUS mandatory DESCRIPTION "Allows for viewing status of the circuit breakers. The number of entries is contained in the dm3StatusBreakersTableSize OID." ::= { dm3StatusBreakers 2 } dm3StatusBreakersEntry OBJECT-TYPE SYNTAX StatusBreakersEntry ACCESS not-accessible STATUS mandatory DESCRIPTION "The circuit breaker to gather status from." INDEX { dm3StatusBreakersIndex } ::= { dm3StatusBreakersTable 1 } StatusBreakersEntry ::= SEQUENCE { dm3StatusBreakersIndex INTEGER, dm3StatusBreakersName DisplayString, dm3StatusBreakersStatus INTEGER } dm3StatusBreakersIndex OBJECT-TYPE SYNTAX INTEGER ACCESS read-only STATUS mandatory DESCRIPTION "The index to the DC powerplant circuit breaker." ::= { dm3StatusBreakersEntry 1 } dm3StatusBreakersName OBJECT-TYPE SYNTAX DisplayString ACCESS read-only STATUS mandatory DESCRIPTION "The name of the circuit breaker. The maximum size is 16 characters. The name is set by using the dm3ConfigBreakersName OID. This OID is provided for informational purposes only." ::= { dm3StatusBreakersEntry 2 } dm3StatusBreakersStatus OBJECT-TYPE SYNTAX INTEGER { statusClosed (1), statusOpen (2) } ACCESS read-only STATUS mandatory DESCRIPTION "Getting this OID will return statusClosed (1) if the circuit breaker is closed. statusOpen (2) will be returned if the circuit breaker is open." ::= { dm3StatusBreakersEntry 3 } -- the dm3StatusFuses group dm3StatusFusesTableSize OBJECT-TYPE SYNTAX INTEGER ACCESS read-only STATUS mandatory DESCRIPTION "The number of DC powerplant fuses controllable by this IP address." ::= { dm3StatusFuses 1 } dm3StatusFusesTable OBJECT-TYPE SYNTAX SEQUENCE OF StatusFusesEntry ACCESS not-accessible STATUS mandatory DESCRIPTION "Allows for viewing status of the fuses. The number of entries is contained in the dm3StatusFusesTableSize OID." ::= { dm3StatusFuses 2 } dm3StatusFusesEntry OBJECT-TYPE SYNTAX StatusFusesEntry ACCESS not-accessible STATUS mandatory DESCRIPTION "The fuse to gather status from." INDEX { dm3StatusFusesIndex } ::= { dm3StatusFusesTable 1 } StatusFusesEntry ::= SEQUENCE { dm3StatusFusesIndex INTEGER, dm3StatusFusesName DisplayString, dm3StatusFusesStatus INTEGER } dm3StatusFusesIndex OBJECT-TYPE SYNTAX INTEGER ACCESS read-only STATUS mandatory DESCRIPTION "The index to the DC powerplant fuse." ::= { dm3StatusFusesEntry 1 } dm3StatusFusesName OBJECT-TYPE SYNTAX DisplayString ACCESS read-only STATUS mandatory DESCRIPTION "The name of the fuse. The maximum size is 16 characters. The name is set by using the dm3ConfigFuseName OID. This OID is provided for informational purposes only." ::= { dm3StatusFusesEntry 2 } dm3StatusFusesStatus OBJECT-TYPE SYNTAX INTEGER { statusClosed (1), statusOpen (2) } ACCESS read-only STATUS mandatory DESCRIPTION "Getting this OID will return statusClosed (1) if the fuse is closed. statusOpen (2) will be returned if the fuse is open." ::= { dm3StatusFusesEntry 3 } -- the atsIdent group atsIdentHardwareRev OBJECT-TYPE SYNTAX DisplayString ACCESS read-only STATUS mandatory DESCRIPTION "The hardware version of the Automatic Transfer Switch. This value is set at the factory." ::= { atsIdent 1 } atsIdentFirmwareRev OBJECT-TYPE SYNTAX DisplayString ACCESS read-only STATUS mandatory DESCRIPTION "A string identifying the Automatic Transfer Switch firmware version." ::= { atsIdent 2 } atsIdentFirmwareDate OBJECT-TYPE SYNTAX DisplayString ACCESS read-only STATUS mandatory DESCRIPTION "The date of release for this Automatic Transfer Switch firmware version. " ::= { atsIdent 3 } atsIdentDateOfManufacture OBJECT-TYPE SYNTAX DisplayString ACCESS read-only STATUS mandatory DESCRIPTION "The date when the Automatic Transfer Switch was manufactured in mm/dd/yyyy format. This value is set at the factory. " ::= { atsIdent 4 } atsIdentModelNumber OBJECT-TYPE SYNTAX DisplayString ACCESS read-only STATUS mandatory DESCRIPTION "A string identifying the model number of the Automatic Transfer Switch. This value is set at the factory." ::= { atsIdent 5 } atsIdentSerialNumber OBJECT-TYPE SYNTAX DisplayString ACCESS read-only STATUS mandatory DESCRIPTION "A string identifying the serial number of the Automatic Transfer Switch. This value is set at the factory." ::= { atsIdent 6 } atsIdentNominalLineVoltage OBJECT-TYPE SYNTAX INTEGER ACCESS read-only STATUS mandatory DESCRIPTION "RMS Utility Voltage measured in V." ::= { atsIdent 7 } atsIdentNominalLineFrequency OBJECT-TYPE SYNTAX INTEGER ACCESS read-only STATUS mandatory DESCRIPTION "Utility Power Frequency measured in Hz." ::= { atsIdent 8 } -- the atsCalibration group -- Input Voltage Calibration Factor table atsCalibrationNumInputs OBJECT-TYPE SYNTAX INTEGER ACCESS read-only STATUS mandatory DESCRIPTION "The number of inputs to this device." ::= { atsCalibrationInput 1 } atsCalibrationNumInputPhases OBJECT-TYPE SYNTAX INTEGER ACCESS read-only STATUS mandatory DESCRIPTION "The number of phases per input for this device." ::= { atsCalibrationInput 2 } atsCalibrationInputTable OBJECT-TYPE SYNTAX SEQUENCE OF ATSCalibrationInputPhaseEntry ACCESS not-accessible STATUS mandatory DESCRIPTION "The number of phases per input line to this device." ::= { atsCalibrationInput 3 } atsCalibrationInputPhaseEntry OBJECT-TYPE SYNTAX ATSCalibrationInputPhaseEntry ACCESS not-accessible STATUS mandatory DESCRIPTION "An entry containing calibration information applicable to a particular input phase." INDEX { atsCalibrationInputTableIndex, atsCalibrationInputPhaseTableIndex } ::= { atsCalibrationInputTable 1 } ATSCalibrationInputPhaseEntry ::= SEQUENCE { atsCalibrationInputTableIndex INTEGER, atsCalibrationInputPhaseTableIndex INTEGER, atsLineVoltageCalibrationFactor INTEGER } atsCalibrationInputTableIndex OBJECT-TYPE SYNTAX INTEGER ACCESS read-only STATUS mandatory DESCRIPTION "The input identifier." ::= { atsCalibrationInputPhaseEntry 1 } atsCalibrationInputPhaseTableIndex OBJECT-TYPE SYNTAX INTEGER ACCESS read-only STATUS mandatory DESCRIPTION "The input phase identifier." ::= { atsCalibrationInputPhaseEntry 2 } atsLineVoltageCalibrationFactor OBJECT-TYPE SYNTAX INTEGER ACCESS read-only STATUS mandatory DESCRIPTION "The Line Voltage Calibration factor. This value is set at the factory." ::= { atsCalibrationInputPhaseEntry 3 } -- Power Supply Voltage Calibration table atsCalibrationPowerSupplyVoltages OBJECT-TYPE SYNTAX INTEGER ACCESS read-only STATUS mandatory DESCRIPTION "The number of power supply voltages supported by this device. This variable indicates the number of rows in the atsCalibrationPowerSupplyTable. There is one entry per supported voltage: 24V, 12V and 5V" ::= { atsCalibrationPowerSupply 1 } atsCalibrationPowerSupplyVoltageTable OBJECT-TYPE SYNTAX SEQUENCE OF ATSCalibrationPowerSupplyVoltageEntry ACCESS not-accessible STATUS mandatory DESCRIPTION "A list of Power Supply table entries." ::= { atsCalibrationPowerSupply 2 } atsCalibrationPowerSupplyVoltageEntry OBJECT-TYPE SYNTAX ATSCalibrationPowerSupplyVoltageEntry ACCESS not-accessible STATUS mandatory DESCRIPTION "An entry containing information applicable to a particular Power Supply Voltage." INDEX { atsCalibrationPowerSupplyVoltageTableIndex } ::= { atsCalibrationPowerSupplyVoltageTable 1 } ATSCalibrationPowerSupplyVoltageEntry ::= SEQUENCE { atsCalibrationPowerSupplyVoltageTableIndex INTEGER, atsCalibrationPowerSupplyVoltage INTEGER, atsPowerSupplyVoltageCalibrationFactor INTEGER } atsCalibrationPowerSupplyVoltageTableIndex OBJECT-TYPE SYNTAX INTEGER ACCESS read-only STATUS mandatory DESCRIPTION "The power supply voltage identifier. Three power supply voltages are supported by the ATS: 24V , 12V and 5V . The value of this index indicates the power supply voltage: 1 = 24V 2 = 12V 3 = 5V" ::= { atsCalibrationPowerSupplyVoltageEntry 1 } atsCalibrationPowerSupplyVoltage OBJECT-TYPE SYNTAX INTEGER { powerSupply24V(1), powerSupply12V(2), powerSupply(3) } ACCESS read-only STATUS mandatory DESCRIPTION "This value describes the power supply voltage." ::= { atsCalibrationPowerSupplyVoltageEntry 2 } atsPowerSupplyVoltageCalibrationFactor OBJECT-TYPE SYNTAX INTEGER ACCESS read-only STATUS mandatory DESCRIPTION "The Line Voltage Calibration factor. This value is set at the factory." ::= { atsCalibrationPowerSupplyVoltageEntry 3 } -- Output Current Calibration table atsCalibrationNumOutputs OBJECT-TYPE SYNTAX INTEGER ACCESS read-only STATUS mandatory DESCRIPTION "The number of output lines from this device. This variable indicates the number of rows in the atsCalibrationOutputTable." ::= { atsCalibrationOutput 1 } atsCalibrationNumOutputPhases OBJECT-TYPE SYNTAX INTEGER ACCESS read-only STATUS mandatory DESCRIPTION "The number of output phases utilized in this device." ::= { atsCalibrationOutput 2 } atsCalibrationOutputTable OBJECT-TYPE SYNTAX SEQUENCE OF ATSCalibrationOutputEntry ACCESS not-accessible STATUS mandatory DESCRIPTION "A list of output table entries." ::= { atsCalibrationOutput 3 } atsCalibrationOutputEntry OBJECT-TYPE SYNTAX ATSCalibrationOutputEntry ACCESS not-accessible STATUS mandatory DESCRIPTION "An entry containing information applicable to a particular output." INDEX { atsCalibrationOutputTableIndex, atsCalibrationOutputPhasesTableIndex } ::= { atsCalibrationOutputTable 1 } ATSCalibrationOutputEntry ::= SEQUENCE { atsCalibrationOutputTableIndex INTEGER, atsCalibrationOutputPhasesTableIndex INTEGER, atsOutputCurrentCalibrationFactor INTEGER } atsCalibrationOutputTableIndex OBJECT-TYPE SYNTAX INTEGER ACCESS read-only STATUS mandatory DESCRIPTION "The output identifier." ::= { atsCalibrationOutputEntry 1 } atsCalibrationOutputPhasesTableIndex OBJECT-TYPE SYNTAX INTEGER{ phase1(1), phase2(2), phase3(3), neutral(4) } ACCESS read-only STATUS mandatory DESCRIPTION "Description of each calibration factor for each output phase utilized in this device and one for neutral. " ::= { atsCalibrationOutputEntry 2 } atsOutputCurrentCalibrationFactor OBJECT-TYPE SYNTAX INTEGER ACCESS read-only STATUS mandatory DESCRIPTION "The output current calibration factor measured in Amps." ::= { atsCalibrationOutputEntry 3 } -- the atsControl group atsControlResetATS OBJECT-TYPE SYNTAX INTEGER { none(1), reset(2) } ACCESS read-write STATUS mandatory DESCRIPTION "Setting this variable will cause the Automatic Transfer Switch to perform a power-on reset." ::= { atsControl 1 } atsControlClearAllAlarms OBJECT-TYPE SYNTAX INTEGER { none(1), clear(2) } ACCESS read-write STATUS mandatory DESCRIPTION "Setting this variable will clear all alarms in the Automatic Transfer Switch." ::= { atsControl 2 } -- the atsConfig group atsConfigProductName OBJECT-TYPE SYNTAX DisplayString ACCESS read-write STATUS mandatory DESCRIPTION "A configurable character string." ::= { atsConfig 1 } atsConfigPreferredSource OBJECT-TYPE SYNTAX INTEGER { sourceA(1), sourceB(2), none(3) } ACCESS read-write STATUS mandatory DESCRIPTION "This variable returns the preferred source of power when both sources are OK." ::= { atsConfig 2 } atsConfigFrontPanelLockout OBJECT-TYPE SYNTAX INTEGER { disableFrontPanel(1), enableFrontPanel(2) } ACCESS read-write STATUS mandatory DESCRIPTION "Setting this variable to disableFrontPanel(1) will disallow source preference configuration of the Automatic Transfer Switch via the Front Panel. Once this value is set, it can only be re-enabled through the serial interface of the ATS. When this variable is set to enableFrontPanel(2), source preference configuration of the Automatic Transfer Switch via the Front Panel is allowed." ::= { atsConfig 3 } atsConfigVoltageSensitivity OBJECT-TYPE SYNTAX INTEGER { high(1), low(2) } ACCESS read-write STATUS mandatory DESCRIPTION "This variable defines the sensitivity to changes in voltage: high(1) for best protection, low(2) for frequent small line voltage changes." ::= { atsConfig 4 } atsConfigTransferVoltageRange OBJECT-TYPE SYNTAX INTEGER { wide(1), medium(2), narrow(3) } ACCESS read-write STATUS mandatory DESCRIPTION "This variable defines the range of acceptable voltage from a power source. If the voltage measured from the selected input source is not within this range, the Automatic Transfer Switch will switch over (transfer) to the alternate power source." ::= { atsConfig 5 } atsConfigCurrentLimit OBJECT-TYPE SYNTAX INTEGER (0..20) ACCESS read-write STATUS mandatory DESCRIPTION "The threshold (in Amps) at which an Over Current Alarm will be generated." ::= { atsConfig 6 } atsConfigResetValues OBJECT-TYPE SYNTAX INTEGER { none(1), reset(2) } ACCESS read-write STATUS mandatory DESCRIPTION "Resets the ATS configuration to its default values." ::= { atsConfig 7 } -- the atsStatus group atsStatusCommStatus OBJECT-TYPE SYNTAX INTEGER { atsNeverDiscovered(1), atsCommEstablished(2), atsCommLost(3) } ACCESS read-only STATUS mandatory DESCRIPTION "This variable returns the current communication status of the Automatic Transfer Switch. " ::= { atsStatusDeviceStatus 1 } atsStatusSelectedSource OBJECT-TYPE SYNTAX INTEGER { sourceA(1), sourceB(2) } ACCESS read-only STATUS mandatory DESCRIPTION "This variable returns the current source of power. " ::= { atsStatusDeviceStatus 2 } atsStatusRedundancyState OBJECT-TYPE SYNTAX INTEGER { atsRedundancyLost(1), atsFullyRedundant(2) } ACCESS read-only STATUS mandatory DESCRIPTION "This variable returns the current redundancy state of the ATS. atsRedundancyLost(1) indicates that the ATS is unable to switch over to the alternate power source if the current source fails. atsFullyRedundant(2) indicates that the ATS will switch over to the alternate power source if the current source fails." ::= { atsStatusDeviceStatus 3 } atsStatusOverCurrentState OBJECT-TYPE SYNTAX INTEGER { atsOverCurrent(1), atsCurrentOK(2) } ACCESS read-only STATUS mandatory DESCRIPTION "This variable returns the output current state of the ATS. atsOverCurrent(1) indicates that the ATS has exceeded the output current threshold and will not allow a switch over to the alternate power source if the current source fails. atsCurrentOK(2) indicates that the output current is below the output current threshold." ::= { atsStatusDeviceStatus 4 } atsStatus5VPowerSupply OBJECT-TYPE SYNTAX INTEGER { atsPowerSupplyFailure(1), atsPowerSupplyOK(2) } ACCESS read-only STATUS mandatory DESCRIPTION "This variable returns the current state of the ATS 5-volt power supply. atsPowerSupplyFailure(1) indicates the 5-volt power supply has failed and that the ATS serial port Configuration Menu is not accessible . atsPowerSupplyOK(2) indicates that the ATS 5-volt power supply is operating within tolerance." ::= { atsStatusDeviceStatus 5 } atsStatus24VPowerSupply OBJECT-TYPE SYNTAX INTEGER { atsPowerSupplyFailure(1), atsPowerSupplyOK(2) } ACCESS read-only STATUS mandatory DESCRIPTION "This variable returns the current state of the ATS 24-volt power supply. atsPowerSupplyFailure(1) indicates the 24-volt power supply has failed and the ATS is unable to switch over to the alternate power source if the current source fails. atsPowerSupplyOK(2) indicates that the ATS 24-volt power supply is operating within tolerance." ::= { atsStatusDeviceStatus 6 } atsStatusResetMaxMinValues OBJECT-TYPE SYNTAX INTEGER { none(1), reset(2) } ACCESS read-write STATUS mandatory DESCRIPTION "Resets the maximum and minimum ATS values: atsInputMaxVoltage, atsInputMinVoltage, atsInputMaxCurrent, atsInputMinCurrent, atsInputMaxPower, atsInputMinPower, atsOutputMaxCurrent, atsOutputMinCurrent, atsOutputMaxLoad, atsOutputMinLoad, atsOutputMaxPercentLoad, atsOutputMinPercentLoad, atsOutputMaxPower, atsOutputMinPower, atsOutputMaxPercentPower, atsOutputMinPercentPower. These variables represent the maximum and minimum ATS values since the last time they were read or reset by this OID. Values unsupported by this ATS will return (-1)." ::= { atsStatusResetValues 1 } -- -- Input Group -- -- Number of Inputs atsNumInputs OBJECT-TYPE SYNTAX INTEGER ACCESS read-only STATUS mandatory DESCRIPTION "The number of input feeds to this device. This variable indicates the number of rows in the input table." ::= { atsStatusInput 1 } -- Input Table atsInputTable OBJECT-TYPE SYNTAX SEQUENCE OF ATSPhaseInputEntry ACCESS not-accessible STATUS mandatory DESCRIPTION "A list of input table entries. The number of entries is given by the value of atsNumInputs." ::= { atsStatusInput 2 } atsInputEntry OBJECT-TYPE SYNTAX ATSPhaseInputEntry ACCESS not-accessible STATUS mandatory DESCRIPTION "An entry containing information applicable to a particular input." INDEX { atsInputTableIndex } ::= { atsInputTable 1 } ATSPhaseInputEntry ::= SEQUENCE { atsInputTableIndex INTEGER, atsNumInputPhases INTEGER, atsInputVoltageOrientation INTEGER, atsInputFrequency INTEGER, atsInputType INTEGER, atsInputName DisplayString } atsInputTableIndex OBJECT-TYPE SYNTAX INTEGER ACCESS read-only STATUS mandatory DESCRIPTION "The input identifier." ::= { atsInputEntry 1 } atsNumInputPhases OBJECT-TYPE SYNTAX INTEGER ACCESS read-only STATUS mandatory DESCRIPTION "The number of input phases utilized in this device. The sum of all the atsNumInputPhases variable indicates the number of rows in the input phase table." ::= { atsInputEntry 2 } atsInputVoltageOrientation OBJECT-TYPE SYNTAX INTEGER { unknown(1), singlePhase(2), splitPhase(3), threePhasePhaseToNeutral(4), threePhasePhaseToPhase(5) } ACCESS read-only STATUS mandatory DESCRIPTION "The input voltage orientation: 1: unknown for this Source 2: singlePhase - phase 1 voltage is between Phase 1 and Neutral. 3: splitPhase - phase 1 voltage is between Phase 1 and Neutral; phase 2 voltage is between Phase 2 and Neutral; phase 3 voltage is between Phase 1 and Phase2. 4: threePhasePhaseToNeutral - phase 1 voltage is between Phase 1 and Neutral; phase 2 voltage is between Phase 2 and Neutral; phase 3 voltage is between Phase3 and Neutral. 5: threePhasePhaseToPhase - phase 1 voltage is between Phase 1 and Phase 2; phase 2 voltage is between Phase 2 and Phase 3; phase 3 voltage is between Phase 3 and Phase 1." ::= { atsInputEntry 3 } atsInputFrequency OBJECT-TYPE SYNTAX INTEGER ACCESS read-only STATUS mandatory DESCRIPTION "The input frequency in Hertz, or -1 if it's unsupported by this Source." ::= { atsInputEntry 4 } atsInputType OBJECT-TYPE SYNTAX INTEGER { unknown(1), main(2), bypass(3) } ACCESS read-only STATUS mandatory DESCRIPTION "The input type." ::= { atsInputEntry 5 } atsInputName OBJECT-TYPE SYNTAX DisplayString ACCESS read-write STATUS mandatory DESCRIPTION "A name given to a particular input." ::= { atsInputEntry 6 } -- Input Phase Table atsInputPhaseTable OBJECT-TYPE SYNTAX SEQUENCE OF ATSPhaseInputPhaseEntry ACCESS not-accessible STATUS mandatory DESCRIPTION "A list of input table entries. The number of entries is given by the sum of the atsNumInputPhases." ::= { atsStatusInput 3 } atsInputPhaseEntry OBJECT-TYPE SYNTAX ATSPhaseInputPhaseEntry ACCESS not-accessible STATUS mandatory DESCRIPTION "An entry containing information applicable to a particular input phase." INDEX { atsInputPhaseTableIndex, atsInputPhaseIndex } ::= { atsInputPhaseTable 1 } ATSPhaseInputPhaseEntry ::= SEQUENCE { atsInputPhaseTableIndex INTEGER, atsInputPhaseIndex INTEGER, atsInputVoltage INTEGER, atsInputMaxVoltage INTEGER, atsInputMinVoltage INTEGER, atsInputCurrent INTEGER, atsInputMaxCurrent INTEGER, atsInputMinCurrent INTEGER, atsInputPower INTEGER, atsInputMaxPower INTEGER, atsInputMinPower INTEGER } atsInputPhaseTableIndex OBJECT-TYPE SYNTAX INTEGER ACCESS read-only STATUS mandatory DESCRIPTION "The input identifier." ::= { atsInputPhaseEntry 1 } atsInputPhaseIndex OBJECT-TYPE SYNTAX INTEGER ACCESS read-only STATUS mandatory DESCRIPTION "The input phase identifier." ::= { atsInputPhaseEntry 2 } atsInputVoltage OBJECT-TYPE SYNTAX INTEGER ACCESS read-only STATUS mandatory DESCRIPTION "The input voltage in VAC, or -1 if it's unsupported by this Source." ::= { atsInputPhaseEntry 3 } atsInputMaxVoltage OBJECT-TYPE SYNTAX INTEGER ACCESS read-only STATUS mandatory DESCRIPTION "The maximum input voltage in VAC measured since the last time this variable was read or reset (atsStatusResetMaxMinValues). Returns (-1) if unsupported." ::= { atsInputPhaseEntry 4 } atsInputMinVoltage OBJECT-TYPE SYNTAX INTEGER ACCESS read-only STATUS mandatory DESCRIPTION "The minimum input voltage in VAC measured since the last time this variable was read or reset (atsStatusResetMaxMinValues). Returns (-1) if unsupported." ::= { atsInputPhaseEntry 5 } atsInputCurrent OBJECT-TYPE SYNTAX INTEGER ACCESS read-only STATUS mandatory DESCRIPTION "The input current in amperes, or -1 if it's unsupported by this Source." ::= { atsInputPhaseEntry 6 } atsInputMaxCurrent OBJECT-TYPE SYNTAX INTEGER ACCESS read-only STATUS mandatory DESCRIPTION "The maximum input current in amperes measured since the last time this variable was read or reset (atsStatusResetMaxMinValues). Returns (-1) if unsupported." ::= { atsInputPhaseEntry 7 } atsInputMinCurrent OBJECT-TYPE SYNTAX INTEGER ACCESS read-only STATUS mandatory DESCRIPTION "The minimum input current in amperes measured since the last time this variable was read or reset (atsStatusResetMaxMinValues). Returns (-1) if unsupported." ::= { atsInputPhaseEntry 8 } atsInputPower OBJECT-TYPE SYNTAX INTEGER ACCESS read-only STATUS mandatory DESCRIPTION "The input power in Watts, or -1 if it's unsupported by this Source." ::= { atsInputPhaseEntry 9 } atsInputMaxPower OBJECT-TYPE SYNTAX INTEGER ACCESS read-only STATUS mandatory DESCRIPTION "The maximum input power in Watts measured since the last time this variable was read or reset (atsStatusResetMaxMinValues). Returns (-1) if unsupported." ::= { atsInputPhaseEntry 10 } atsInputMinPower OBJECT-TYPE SYNTAX INTEGER ACCESS read-only STATUS mandatory DESCRIPTION "The minimum input power in Watts measured since the last time this variable was read or reset (atsStatusResetMaxMinValues). Returns (-1) if unsupported." ::= { atsInputPhaseEntry 11 } -- -- The Output group. -- -- Number of Outputs atsNumOutputs OBJECT-TYPE SYNTAX INTEGER ACCESS read-only STATUS mandatory DESCRIPTION "The number of output feeds to this device. This variable indicates the number of rows in the output table." ::= { atsStatusOutput 1 } -- Output Table atsOutputTable OBJECT-TYPE SYNTAX SEQUENCE OF ATSPhaseOutputEntry ACCESS not-accessible STATUS mandatory DESCRIPTION "A list of output table entries. The number of entries is given by the value of atsOutputNumPhases." ::= { atsStatusOutput 2 } atsOutputEntry OBJECT-TYPE SYNTAX ATSPhaseOutputEntry ACCESS not-accessible STATUS mandatory DESCRIPTION "An entry containing information applicable to a particular output." INDEX { atsOutputTableIndex } ::= { atsOutputTable 1 } ATSPhaseOutputEntry ::= SEQUENCE { atsOutputTableIndex INTEGER, atsNumOutputPhases INTEGER, atsOutputVoltageOrientation INTEGER, atsOutputFrequency INTEGER } atsOutputTableIndex OBJECT-TYPE SYNTAX INTEGER ACCESS read-only STATUS mandatory DESCRIPTION "The output identifier." ::= { atsOutputEntry 1 } atsNumOutputPhases OBJECT-TYPE SYNTAX INTEGER ACCESS read-only STATUS mandatory DESCRIPTION "The number of output phases utilized in this device. The sum of all the atsNumOutputPhases variable indicates the number of rows in the output phase table." ::= { atsOutputEntry 2 } atsOutputVoltageOrientation OBJECT-TYPE SYNTAX INTEGER { unknown(1), singlePhase(2), splitPhase(3), threePhasePhaseToNeutral(4), threePhasePhaseToPhase(5) } ACCESS read-only STATUS mandatory DESCRIPTION "The output voltage orientation: 1: unknown for this ATS 2: singlePhase - phase 1 voltage is between Phase 1 and Neutral. 3: splitPhase - phase 1 voltage is between Phase 1 and Neutral; phase 2 voltage is between Phase 2 and Neutral; phase 3 voltage is between Phase 1 and Phase2. 4: threePhasePhaseToNeutral - phase 1 voltage is between Phase 1 and Neutral; phase 2 voltage is between Phase 2 and Neutral; phase 3 voltage is between Phase3 and Neutral. 5: threePhasePhaseToPhase - phase 1 voltage is between Phase 1 and Phase 2; phase 2 voltage is between Phase 2 and Phase 3; phase 3 voltage is between Phase 3 and Phase 1." ::= { atsOutputEntry 3 } atsOutputFrequency OBJECT-TYPE SYNTAX INTEGER ACCESS read-only STATUS mandatory DESCRIPTION "The output frequency in Hertz, or -1 if it's unsupported by this ATS." ::= { atsOutputEntry 4 } -- Output Phase Table atsOutputPhaseTable OBJECT-TYPE SYNTAX SEQUENCE OF ATSPhaseOutputPhaseEntry ACCESS not-accessible STATUS mandatory DESCRIPTION "A list of output table entries. The number of entries is given by the sum of the atsNumOutputPhases." ::= { atsStatusOutput 3 } atsOutputPhaseEntry OBJECT-TYPE SYNTAX ATSPhaseOutputPhaseEntry ACCESS not-accessible STATUS mandatory DESCRIPTION "An entry containing information applicable to a particular output phase." INDEX { atsOutputPhaseTableIndex, atsOutputPhaseIndex } ::= { atsOutputPhaseTable 1 } ATSPhaseOutputPhaseEntry ::= SEQUENCE { atsOutputPhaseTableIndex INTEGER, atsOutputPhaseIndex INTEGER, atsOutputVoltage INTEGER, atsOutputCurrent INTEGER, atsOutputMaxCurrent INTEGER, atsOutputMinCurrent INTEGER, atsOutputLoad INTEGER, atsOutputMaxLoad INTEGER, atsOutputMinLoad INTEGER, atsOutputPercentLoad INTEGER, atsOutputMaxPercentLoad INTEGER, atsOutputMinPercentLoad INTEGER, atsOutputPower INTEGER, atsOutputMaxPower INTEGER, atsOutputMinPower INTEGER, atsOutputPercentPower INTEGER, atsOutputMaxPercentPower INTEGER, atsOutputMinPercentPower INTEGER } atsOutputPhaseTableIndex OBJECT-TYPE SYNTAX INTEGER ACCESS read-only STATUS mandatory DESCRIPTION "The output identifier." ::= { atsOutputPhaseEntry 1 } atsOutputPhaseIndex OBJECT-TYPE SYNTAX INTEGER{ phase1(1), phase2(2), phase3(3), neutral(4) } ACCESS read-only STATUS mandatory DESCRIPTION "Description of each output phase utilized in this device and one for neutral. " ::= { atsOutputPhaseEntry 2 } atsOutputVoltage OBJECT-TYPE SYNTAX INTEGER ACCESS read-only STATUS mandatory DESCRIPTION "The output voltage in VAC, or -1 if it's unsupported by this ATS." ::= { atsOutputPhaseEntry 3 } atsOutputCurrent OBJECT-TYPE SYNTAX INTEGER ACCESS read-only STATUS mandatory DESCRIPTION "The output current in 0.1 amperes drawn by the load on the ATS, or -1 if it's unsupported by this ATS." ::= { atsOutputPhaseEntry 4 } atsOutputMaxCurrent OBJECT-TYPE SYNTAX INTEGER ACCESS read-only STATUS mandatory DESCRIPTION "The maximum output current in 0.1 amperes measured since the last time this variable was read or reset (atsStatusResetMaxMinValues). Returns (-1) if unsupported." ::= { atsOutputPhaseEntry 5 } atsOutputMinCurrent OBJECT-TYPE SYNTAX INTEGER ACCESS read-only STATUS mandatory DESCRIPTION "The minimum output current in 0.1 amperes measured since the last time this variable was read or reset (atsStatusResetMaxMinValues). Returns (-1) if unsupported." ::= { atsOutputPhaseEntry 6 } atsOutputLoad OBJECT-TYPE SYNTAX INTEGER ACCESS read-only STATUS mandatory DESCRIPTION "The output load in VA, or -1 if it's unsupported by this ATS." ::= { atsOutputPhaseEntry 7 } atsOutputMaxLoad OBJECT-TYPE SYNTAX INTEGER ACCESS read-only STATUS mandatory DESCRIPTION "The maximum output load in VA measured since the last time this variable was read or reset (atsStatusResetMaxMinValues). Returns (-1) if unsupported." ::= { atsOutputPhaseEntry 8 } atsOutputMinLoad OBJECT-TYPE SYNTAX INTEGER ACCESS read-only STATUS mandatory DESCRIPTION "The minimum output load in VA measured since the last time this variable was read or reset (atsStatusResetMaxMinValues). Returns (-1) if unsupported." ::= { atsOutputPhaseEntry 9 } atsOutputPercentLoad OBJECT-TYPE SYNTAX INTEGER ACCESS read-only STATUS mandatory DESCRIPTION "The percentage of the ATS load capacity in VA at redundancy @ (n + x) presently being used on this output phase, or -1 if it's unsupported by this ATS." ::= { atsOutputPhaseEntry 10 } atsOutputMaxPercentLoad OBJECT-TYPE SYNTAX INTEGER ACCESS read-only STATUS mandatory DESCRIPTION "The maximum percentage of the ATS load capacity in VA measured at redundancy @ (n + x) presently being used on this output phase since the last time this variable was read or reset (atsStatusResetMaxMinValues). Returns (-1) if unsupported." ::= { atsOutputPhaseEntry 11 } atsOutputMinPercentLoad OBJECT-TYPE SYNTAX INTEGER ACCESS read-only STATUS mandatory DESCRIPTION "The minimum percentage of the ATS load capacity in VA measured at redundancy @ (n + x) presently being used on this output phase since the last time this variable was read or reset (atsStatusResetMaxMinValues). Returns (-1) if unsupported." ::= { atsOutputPhaseEntry 12 } atsOutputPower OBJECT-TYPE SYNTAX INTEGER ACCESS read-only STATUS mandatory DESCRIPTION "The output power in Watts, or -1 if it's unsupported by this ATS." ::= { atsOutputPhaseEntry 13 } atsOutputMaxPower OBJECT-TYPE SYNTAX INTEGER ACCESS read-only STATUS mandatory DESCRIPTION "The maximum output power in Watts measured since the last time this variable was read or reset (atsStatusResetMaxMinValues). Returns (-1) if unsupported." ::= { atsOutputPhaseEntry 14 } atsOutputMinPower OBJECT-TYPE SYNTAX INTEGER ACCESS read-only STATUS mandatory DESCRIPTION "The minimum output power in Watts measured since the last time this variable was read or reset (atsStatusResetMaxMinValues). Returns (-1) if unsupported." ::= { atsOutputPhaseEntry 15 } atsOutputPercentPower OBJECT-TYPE SYNTAX INTEGER ACCESS read-only STATUS mandatory DESCRIPTION "The percentage of the ATSpower capacity in Watts at redundancy @ (n + x) presently being used on this output phase, or -1 if it's unsupported by this ATS." ::= { atsOutputPhaseEntry 16 } atsOutputMaxPercentPower OBJECT-TYPE SYNTAX INTEGER ACCESS read-only STATUS mandatory DESCRIPTION "The maximum percentage of the ATSpower capacity in Watts measured at redundancy @ (n + x) presently being used on this output phase since the last time this variable was read or reset (atsStatusResetMaxMinValues). Returns (-1) if unsupported." ::= { atsOutputPhaseEntry 17 } atsOutputMinPercentPower OBJECT-TYPE SYNTAX INTEGER ACCESS read-only STATUS mandatory DESCRIPTION "The minimum percentage of the ATSpower capacity in Watts measured at redundancy @ (n + x) presently being used on this output phase since the last time this variable was read or reset (atsStatusResetMaxMinValues). Returns (-1) if unsupported." ::= { atsOutputPhaseEntry 18 } -- the dcmim2IdentSystem group dcmim2IdentSysFWVersion OBJECT-TYPE SYNTAX INTEGER ACCESS read-only STATUS mandatory DESCRIPTION "Integer representation of the power plant Master Controller firmware revision." ::= { dcmim2IdentSystem 1 } -- the dcmim2ControlSystem group dcmim2ControlRunFunctBatteryTest OBJECT-TYPE SYNTAX INTEGER { battTestOff (1), battTestOn (2) } ACCESS read-write STATUS mandatory DESCRIPTION "Getting this OID will return the battery functional test state. If the test is off, the battTestOff (1) value will be returned. If the test is on, the battTestOn (2) value will be returned. Setting this OID to battTestOff (1) will turn the battery functional test off. Setting this OID to battTestOn (2) will turn the battery functional test on." ::= { dcmim2ControlSystem 1 } dcmim2ControlRunCapacityBatteryTest OBJECT-TYPE SYNTAX INTEGER { battTestOff (1), battTestOn (2) } ACCESS read-write STATUS mandatory DESCRIPTION "Getting this OID will return the battery capacity test state. If the test is off, the battTestOff (1) value will be returned. If the test is on, the battTestOn (2) value will be returned. Setting this OID to battTestOff (1) will turn the battery capacity test off. Setting this OID to battTestOn (2) will turn the battery capacity test on." ::= { dcmim2ControlSystem 2 } -- the dcmim2ConfigSystem group dcmim2ConfigSysHighTempTrip OBJECT-TYPE SYNTAX INTEGER ACCESS read-write STATUS mandatory DESCRIPTION "Trip level (threshold) at which System High Temp alarm condition is created. Range 28 to 100 (degC). Values are represented in thousandths of a degree. Units are displayed in the scale shown in the 'dcmim2StatusSysTempUnits' OID (Celsius or Fahrenheit)." ::= { dcmim2ConfigSystem 1 } dcmim2ConfigSysHighTempReset OBJECT-TYPE SYNTAX INTEGER ACCESS read-write STATUS mandatory DESCRIPTION "Level at which System High Temp alarm condition is reset (cleared). Range 25 to (upper temp - 3) (degC). Values are represented in thousandths of a degree. Units are displayed in the scale shown in the 'dcmim2StatusSysTempUnits' OID (Celsius or Fahrenheit)." ::= { dcmim2ConfigSystem 2 } dcmim2ConfigSysLowTempTrip OBJECT-TYPE SYNTAX INTEGER ACCESS read-write STATUS mandatory DESCRIPTION "Trip level (threshold) at which System Low Temp alarm condition is created. Range -100 to 10 (degC). Values are represented in thousandths of a degree. Units are displayed in the scale shown in the 'dcmim2StatusSysTempUnits' OID (Celsius or Fahrenheit)." ::= { dcmim2ConfigSystem 3 } dcmim2ConfigSysLowTempReset OBJECT-TYPE SYNTAX INTEGER ACCESS read-write STATUS mandatory DESCRIPTION "Level at which System Low Temp alarm condition is reset (cleared). Range (lower temp + 3) to 13 (degC). Values are represented in thousandths of a degree. Units are displayed in the scale shown in the 'dcmim2StatusSysTempUnits' OID (Celsius or Fahrenheit)." ::= { dcmim2ConfigSystem 4 } -- the dcmim2ConfigBattery group dcmim2ConfigBattFloatVolt OBJECT-TYPE SYNTAX INTEGER ACCESS read-write STATUS mandatory DESCRIPTION "Battery Float Voltage defined at 25 degrees Celsius. Values are represented in thousandths of Volts (mV)." ::= { dcmim2ConfigBattery 1 } dcmim2ConfigBattMaxRecharge OBJECT-TYPE SYNTAX INTEGER ACCESS read-write STATUS mandatory DESCRIPTION "Battery Maximum Recharge Rate. This is the maximum current used during battery charging. Values are represented in thousandths of Amps (mA)." ::= { dcmim2ConfigBattery 2 } dcmim2ConfigBattMfgCapacity OBJECT-TYPE SYNTAX INTEGER ACCESS read-write STATUS mandatory DESCRIPTION "Battery capacity (Amp-Hour Size) as specified by the battery manufacturer. Values are represented in thousandths of Amp hours (mAHr)." ::= { dcmim2ConfigBattery 3 } dcmim2ConfigBattType OBJECT-TYPE SYNTAX INTEGER ACCESS read-write STATUS mandatory DESCRIPTION "Type of battery in the powerplant Valid values range from 0 to 254." ::= { dcmim2ConfigBattery 4 } dcmim2ConfigBattFunctTestDuration OBJECT-TYPE SYNTAX INTEGER ACCESS read-write STATUS mandatory DESCRIPTION "Duration of the battery functional test. Values are represented in thousandths of seconds (mSecs)." ::= { dcmim2ConfigBattery 5 } dcmim2ConfigBattFunctTestThresh OBJECT-TYPE SYNTAX INTEGER ACCESS read-write STATUS mandatory DESCRIPTION "Threshold the battery voltage of the system must remain above in order to pass the battery functional test. Values are represented in thousandths of Volts (mV)." ::= { dcmim2ConfigBattery 6 } dcmim2ConfigBattCapacityTestPercent OBJECT-TYPE SYNTAX INTEGER ACCESS read-write STATUS mandatory DESCRIPTION "Threshold for good battery capacity test results. Values range from 0 to 100 percent." ::= { dcmim2ConfigBattery 7 } dcmim2ConfigBattCapacityTestEndThresh OBJECT-TYPE SYNTAX INTEGER ACCESS read-write STATUS mandatory DESCRIPTION "Safeguard voltage at which battery capacity test will end if there is a battery problem. Values are represented in thousandths of Volts (mV)." ::= { dcmim2ConfigBattery 8 } dcmim2ConfigBattCapacityTestCurrent OBJECT-TYPE SYNTAX INTEGER ACCESS read-write STATUS mandatory DESCRIPTION "Constant current value used during battery capacity testing. Values are represented in thousandths of Amps (mA)." ::= { dcmim2ConfigBattery 9 } -- the dcmim2ConfigLVD group dcmim2ConfigLVDTableSize OBJECT-TYPE SYNTAX INTEGER ACCESS read-only STATUS mandatory DESCRIPTION "The number of DC powerplant LVDs controllable by this IP address." ::= { dcmim2ConfigLVD 1 } dcmim2ConfigLVDTable OBJECT-TYPE SYNTAX SEQUENCE OF DC2ConfigLVDEntry ACCESS not-accessible STATUS mandatory DESCRIPTION "Allows for accessing settings of the LVDs. The number of entries is contained in the dcmim2ConfigLVDTableSize OID." ::= { dcmim2ConfigLVD 2 } dcmim2ConfigLVDEntry OBJECT-TYPE SYNTAX DC2ConfigLVDEntry ACCESS not-accessible STATUS mandatory DESCRIPTION "The LVD to configure." INDEX { dcmim2ConfigLVDIndex } ::= { dcmim2ConfigLVDTable 1 } DC2ConfigLVDEntry ::= SEQUENCE { dcmim2ConfigLVDIndex INTEGER, dcmim2ConfigLVDTrip INTEGER, dcmim2ConfigLVDReset INTEGER, dcmim2ConfigLVDState INTEGER } dcmim2ConfigLVDIndex OBJECT-TYPE SYNTAX INTEGER ACCESS read-only STATUS mandatory DESCRIPTION "The index to the DC powerplant LVD." ::= { dcmim2ConfigLVDEntry 1 } dcmim2ConfigLVDTrip OBJECT-TYPE SYNTAX INTEGER ACCESS read-write STATUS mandatory DESCRIPTION "LVD Trip threshold. System bus voltage at which LVD will trip (open) during a battery backup operation. Values are represented in thousandths of Volts (mV)." ::= { dcmim2ConfigLVDEntry 2 } dcmim2ConfigLVDReset OBJECT-TYPE SYNTAX INTEGER ACCESS read-write STATUS mandatory DESCRIPTION "LVD Reset threshold. System bus voltage at which LVD will reset (close) after AC power has been restored. Values are represented in thousandths of Volts (mV)." ::= { dcmim2ConfigLVDEntry 3 } dcmim2ConfigLVDState OBJECT-TYPE SYNTAX INTEGER { statusClosed (1), statusOpened (2) } ACCESS read-only STATUS mandatory DESCRIPTION "Getting this OID will return statusClosed (1) if the LVD is closed. statusOpened (2) will be returned if the LVD is opened." ::= { dcmim2ConfigLVDEntry 4 } -- the dcmim2StatusSystem group dcmim2StatusSysRectCurrent OBJECT-TYPE SYNTAX INTEGER ACCESS read-only STATUS mandatory DESCRIPTION "System (Total Rectifier) current in thousandths of Amps (mA)." ::= { dcmim2StatusSystem 1 } dcmim2StatusSysLoadCurrent OBJECT-TYPE SYNTAX INTEGER ACCESS read-only STATUS mandatory DESCRIPTION "Load current in thousandths of Amps (mA)." ::= { dcmim2StatusSystem 2 } dcmim2StatusSysBusVoltage OBJECT-TYPE SYNTAX INTEGER ACCESS read-only STATUS mandatory DESCRIPTION "System bus voltage in thousandths of Volts (mV)." ::= { dcmim2StatusSystem 3 } dcmim2StatusSysAmbientTemp OBJECT-TYPE SYNTAX INTEGER ACCESS read-only STATUS mandatory DESCRIPTION "System temperature based on sensor on Master Controller PCB. Values are represented in thousandths of a degree. Units are displayed in the scale shown in the 'dcmim2StatusSysTempUnits' OID (Celsius or Fahrenheit)." ::= { dcmim2StatusSystem 4 } dcmim2StatusSysUpTime OBJECT-TYPE SYNTAX DisplayString ACCESS read-only STATUS mandatory DESCRIPTION "Length of time since the DC Powerplant controller has been powered up." ::= { dcmim2StatusSystem 5 } dcmim2StatusSysTempUnits OBJECT-TYPE SYNTAX INTEGER { celsius(1), fahrenheit(2) } ACCESS read-only STATUS mandatory DESCRIPTION "The temperature scale used to display the temperature in the DC system, Celsius(1) or Fahrenheit(2). This setting is based on the system preferences configuration in the agent." ::= { dcmim2StatusSystem 6 } -- the dcmim2StatusRectifier group dcmim2StatusRectTableSize OBJECT-TYPE SYNTAX INTEGER ACCESS read-only STATUS mandatory DESCRIPTION "The number of DC powerplant rectifiers viewable by this IP address." ::= { dcmim2StatusRectifier 1 } dcmim2StatusRectTable OBJECT-TYPE SYNTAX SEQUENCE OF DC2StatusRectEntry ACCESS not-accessible STATUS mandatory DESCRIPTION "Allows for accessing settings of the rectifiers. The number of entries is contained in the dcmim2StatusRectTableSize OID." ::= { dcmim2StatusRectifier 2 } dcmim2StatusRectEntry OBJECT-TYPE SYNTAX DC2StatusRectEntry ACCESS not-accessible STATUS mandatory DESCRIPTION "The rectifier to gather status from." INDEX { dcmim2StatusRectIndex } ::= { dcmim2StatusRectTable 1 } DC2StatusRectEntry ::= SEQUENCE { dcmim2StatusRectIndex INTEGER, dcmim2StatusRectDevType INTEGER, dcmim2StatusRectID INTEGER, dcmim2StatusRectPhyAddr INTEGER, dcmim2StatusRectFail INTEGER, dcmim2StatusRectCurrent INTEGER } dcmim2StatusRectIndex OBJECT-TYPE SYNTAX INTEGER ACCESS read-only STATUS mandatory DESCRIPTION "The index to the DC powerplant rectifier." ::= { dcmim2StatusRectEntry 1 } dcmim2StatusRectDevType OBJECT-TYPE SYNTAX INTEGER ACCESS read-only STATUS mandatory DESCRIPTION "This OID shows the rectifier device type." ::= { dcmim2StatusRectEntry 2 } dcmim2StatusRectID OBJECT-TYPE SYNTAX INTEGER ACCESS read-only STATUS mandatory DESCRIPTION "This OID shows the rectifier ID. This enumerates the number of the rectifier within a group of rectifiers." ::= { dcmim2StatusRectEntry 3 } dcmim2StatusRectPhyAddr OBJECT-TYPE SYNTAX INTEGER ACCESS read-only STATUS mandatory DESCRIPTION "This OID shows the rectifier physical address (the address on the bus)." ::= { dcmim2StatusRectEntry 4 } dcmim2StatusRectFail OBJECT-TYPE SYNTAX INTEGER { statusTrue (1), statusFalse (2) } ACCESS read-only STATUS mandatory DESCRIPTION "Getting this OID will return statusTrue (1) if the rectifier has failed. statusFalse (2) will be returned if the rectifier has not failed." ::= { dcmim2StatusRectEntry 5 } dcmim2StatusRectCurrent OBJECT-TYPE SYNTAX INTEGER ACCESS read-only STATUS mandatory DESCRIPTION "This OID shows the individual rectifier current in thousandths of Amps (mA)." ::= { dcmim2StatusRectEntry 6 } -- the dcmim2StatusBattery group dcmim2StatusBattFloatVolt OBJECT-TYPE SYNTAX INTEGER ACCESS read-only STATUS mandatory DESCRIPTION "Battery Float Voltage represented in thousandths of Volts (mV)." ::= { dcmim2StatusBattery 1 } dcmim2StatusBattCurrent OBJECT-TYPE SYNTAX INTEGER ACCESS read-only STATUS mandatory DESCRIPTION "Battery Current: This OID shows the battery current in thousandths of Amps (mA)." ::= { dcmim2StatusBattery 2 } dcmim2StatusBattTemp OBJECT-TYPE SYNTAX INTEGER ACCESS read-only STATUS mandatory DESCRIPTION "Battery Temperature: Values are represented in thousandths of a degree. Units are displayed in the scale shown in the 'dcmim2StatusSysTempUnits' OID (Celsius or Fahrenheit)." ::= { dcmim2StatusBattery 3 } dcmim2StatusBattMfgCapacity OBJECT-TYPE SYNTAX INTEGER ACCESS read-only STATUS mandatory DESCRIPTION "Battery capacity (Amp-Hour Size) as specified by the battery manufacturer. Values are represented in thousandths of Amp hours (mAHr)." ::= { dcmim2StatusBattery 4 } dcmim2StatusBattTestCapacity OBJECT-TYPE SYNTAX INTEGER ACCESS read-only STATUS mandatory DESCRIPTION "Battery capacity (Amp-Hour Size) as determined by the battery capacity test. Values are represented in thousandths of Amp hours (mAHr)." ::= { dcmim2StatusBattery 5 } dcmim2StatusBattFunctTestResult OBJECT-TYPE SYNTAX INTEGER{ functTestNotPerformed (1), functTestInProcess (2), functTestInterrupted (3), functTestPass (4), functTestFail (5) } ACCESS read-only STATUS mandatory DESCRIPTION "Results of the last battery functional test that was run." ::= { dcmim2StatusBattery 6 } dcmim2StatusBattCapacityTestResult OBJECT-TYPE SYNTAX INTEGER{ capacityTestNotPerformed (1), capacityTestInProcess (2), capacityTestInterrupted (3), capacityTestPass (4), capacityTestFail (5) } ACCESS read-only STATUS mandatory DESCRIPTION "Results of the last battery capacity test that was run." ::= { dcmim2StatusBattery 7 } -- the dcmim2StatusLVD group dcmim2StatusLVDTableSize OBJECT-TYPE SYNTAX INTEGER ACCESS read-only STATUS mandatory DESCRIPTION "The number of DC powerplant LVDs accessible by this IP address." ::= { dcmim2StatusLVD 1 } dcmim2StatusLVDTable OBJECT-TYPE SYNTAX SEQUENCE OF DC2StatusLVDEntry ACCESS not-accessible STATUS mandatory DESCRIPTION "Allows for accessing the LVDs. The number of entries is contained in the dcmim2StatusLVDTableSize OID." ::= { dcmim2StatusLVD 2 } dcmim2StatusLVDEntry OBJECT-TYPE SYNTAX DC2StatusLVDEntry ACCESS not-accessible STATUS mandatory DESCRIPTION "The LVD to access." INDEX { dcmim2StatusLVDIndex } ::= { dcmim2StatusLVDTable 1 } DC2StatusLVDEntry ::= SEQUENCE { dcmim2StatusLVDIndex INTEGER, dcmim2StatusLVDState INTEGER } dcmim2StatusLVDIndex OBJECT-TYPE SYNTAX INTEGER ACCESS read-only STATUS mandatory DESCRIPTION "The index to the DC powerplant LVD." ::= { dcmim2StatusLVDEntry 1 } dcmim2StatusLVDState OBJECT-TYPE SYNTAX INTEGER { statusClosed (1), statusOpened (2) } ACCESS read-only STATUS mandatory DESCRIPTION "Getting this OID will return statusClosed (1) if the LVD is closed. statusOpened (2) will be returned if the LVD is opened." ::= { dcmim2StatusLVDEntry 2 } -- the dcmim2StatusAlarms group dcmim2StatusAlarmsTableSize OBJECT-TYPE SYNTAX INTEGER ACCESS read-only STATUS mandatory DESCRIPTION "The number of DC powerplant alarms viewable by this IP address." ::= { dcmim2StatusAlarms 1 } dcmim2StatusAlarmsTable OBJECT-TYPE SYNTAX SEQUENCE OF DC2StatusAlarmsEntry ACCESS not-accessible STATUS mandatory DESCRIPTION "Allows for accessing system alarms. The number of entries is contained in the dcmim2StatusAlarmsTableSize OID." ::= { dcmim2StatusAlarms 2 } dcmim2StatusAlarmsEntry OBJECT-TYPE SYNTAX DC2StatusAlarmsEntry ACCESS not-accessible STATUS mandatory DESCRIPTION "The alarm to display." INDEX { dcmim2StatusAlarmsIndex } ::= { dcmim2StatusAlarmsTable 1 } DC2StatusAlarmsEntry ::= SEQUENCE { dcmim2StatusAlarmsIndex INTEGER, dcmim2StatusAlarmsText DisplayString } dcmim2StatusAlarmsIndex OBJECT-TYPE SYNTAX INTEGER ACCESS read-only STATUS mandatory DESCRIPTION "The index of the system alarm." ::= { dcmim2StatusAlarmsEntry 1 } dcmim2StatusAlarmsText OBJECT-TYPE SYNTAX DisplayString ACCESS read-only STATUS mandatory DESCRIPTION "The 16 character text describing the active alarm condition." ::= { dcmim2StatusAlarmsEntry 2 } -- External Environmental Monitor emIdentFirmwareRevision OBJECT-TYPE SYNTAX DisplayString ACCESS read-only STATUS mandatory DESCRIPTION "The firmware revision of the Environmental Monitor." ::= { emIdent 1 } emConfigProbesNumProbes OBJECT-TYPE SYNTAX INTEGER ACCESS read-only STATUS mandatory DESCRIPTION "The number of temperature and humidity probes available." ::= { emConfig 1 } emConfigProbesTable OBJECT-TYPE SYNTAX SEQUENCE OF EmConfigProbesEntry ACCESS not-accessible STATUS mandatory DESCRIPTION "A list of probes supported by the Environmental Monitor and their configurations." ::= { emConfig 2 } emConfigProbesEntry OBJECT-TYPE SYNTAX EmConfigProbesEntry ACCESS not-accessible STATUS mandatory DESCRIPTION "The Environmental Monitor probe configurations." INDEX { emConfigProbeNumber } ::= { emConfigProbesTable 1 } EmConfigProbesEntry ::= SEQUENCE { emConfigProbeNumber INTEGER, emConfigProbeName DisplayString, emConfigProbeHighTempThreshold INTEGER, emConfigProbeLowTempThreshold INTEGER, emConfigProbeTempUnits INTEGER, emConfigProbeHighHumidThreshold INTEGER, emConfigProbeLowHumidThreshold INTEGER, emConfigProbeHighTempEnable INTEGER, emConfigProbeLowTempEnable INTEGER, emConfigProbeHighHumidEnable INTEGER, emConfigProbeLowHumidEnable INTEGER } emConfigProbeNumber OBJECT-TYPE SYNTAX INTEGER ACCESS read-only STATUS mandatory DESCRIPTION "The index into an Environmental Monitor probe entry." ::= { emConfigProbesEntry 1 } emConfigProbeName OBJECT-TYPE SYNTAX DisplayString ACCESS read-write STATUS mandatory DESCRIPTION "A descriptive name of the probe set by the user, possibly denoting its location or purpose." ::= { emConfigProbesEntry 2 } emConfigProbeHighTempThreshold OBJECT-TYPE SYNTAX INTEGER ACCESS read-write STATUS mandatory DESCRIPTION "The high temperature alarm threshold for the probe. Units are displayed in the scale selected in the 'emConfigProbeTempUnits' OID (Celsius or Fahrenheit)." ::= { emConfigProbesEntry 3 } emConfigProbeLowTempThreshold OBJECT-TYPE SYNTAX INTEGER ACCESS read-write STATUS mandatory DESCRIPTION "The low temperature alarm threshold for the probe. Units are displayed in the scale selected in the 'emConfigProbeTempUnits' OID (Celsius or Fahrenheit)." ::= { emConfigProbesEntry 4 } emConfigProbeTempUnits OBJECT-TYPE SYNTAX INTEGER { celsius(1), fahrenheit(2) } ACCESS read-only STATUS mandatory DESCRIPTION "The temperature scale used to display the temperature thresholds of the probe, Celsius(1) or Fahrenheit(2). This setting is based on the system preferences configuration in the agent." ::= { emConfigProbesEntry 5 } emConfigProbeHighHumidThreshold OBJECT-TYPE SYNTAX INTEGER ACCESS read-write STATUS mandatory DESCRIPTION "The high humidity alarm threshold for the probe in percent relative humidity." ::= { emConfigProbesEntry 6 } emConfigProbeLowHumidThreshold OBJECT-TYPE SYNTAX INTEGER ACCESS read-write STATUS mandatory DESCRIPTION "The low humidity alarm threshold for the probe in percent relative humidity." ::= { emConfigProbesEntry 7 } emConfigProbeHighTempEnable OBJECT-TYPE SYNTAX INTEGER { disabled(1), enabled(2) } ACCESS read-write STATUS mandatory DESCRIPTION "The high temperature alarm enable/disable for the probe. No alarm will be generated if this value is set to disabled(1). The alarm will be generated if this value is set to enabled(2) and the threshold has been violated." ::= { emConfigProbesEntry 8 } emConfigProbeLowTempEnable OBJECT-TYPE SYNTAX INTEGER { disabled(1), enabled(2) } ACCESS read-write STATUS mandatory DESCRIPTION "The low temperature alarm enable/disable for the probe. No alarm will be generated if this value is set to disabled(1). The alarm will be generated if this value is set to enabled(2) and the threshold has been violated." ::= { emConfigProbesEntry 9 } emConfigProbeHighHumidEnable OBJECT-TYPE SYNTAX INTEGER { disabled(1), enabled(2) } ACCESS read-write STATUS mandatory DESCRIPTION "The high humidity alarm enable/disable for the probe. No alarm will be generated if this value is set to disabled(1). The alarm will be generated if this value is set to enabled(2) and the threshold has been violated." ::= { emConfigProbesEntry 10 } emConfigProbeLowHumidEnable OBJECT-TYPE SYNTAX INTEGER { disabled(1), enabled(2) } ACCESS read-write STATUS mandatory DESCRIPTION "The low humidity alarm enable/disable for the probe. No alarm will be generated if this value is set to disabled(1). The alarm will be generated if this value is set to enabled(2) and the threshold has been violated." ::= { emConfigProbesEntry 11 } emConfigContactsNumContacts OBJECT-TYPE SYNTAX INTEGER ACCESS read-only STATUS mandatory DESCRIPTION "The number of contacts supported by the Environmental Monitor." ::= { emConfig 3 } emConfigContactsTable OBJECT-TYPE SYNTAX SEQUENCE OF EmConfigContactsEntry ACCESS not-accessible STATUS mandatory DESCRIPTION "A list of contacts supported by the Environmental Monitor and their configurations." ::= { emConfig 4 } emConfigContactsEntry OBJECT-TYPE SYNTAX EmConfigContactsEntry ACCESS not-accessible STATUS mandatory DESCRIPTION "The Environmental Monitor contact configurations." INDEX { emConfigContactNumber } ::= { emConfigContactsTable 1 } EmConfigContactsEntry ::= SEQUENCE { emConfigContactNumber INTEGER, emConfigContactName DisplayString, emConfigContactEnable INTEGER } emConfigContactNumber OBJECT-TYPE SYNTAX INTEGER ACCESS read-only STATUS mandatory DESCRIPTION "The index of an Environmental Monitor contact." ::= { emConfigContactsEntry 1 } emConfigContactName OBJECT-TYPE SYNTAX DisplayString ACCESS read-write STATUS mandatory DESCRIPTION "A descriptive name for an Environmental Monitor contact set by the user, possibly denoting its location or purpose." ::= { emConfigContactsEntry 2 } emConfigContactEnable OBJECT-TYPE SYNTAX INTEGER { disabled(1), enabled(2) } ACCESS read-write STATUS mandatory DESCRIPTION "An Environmental Monitor contact alarm enable/disable. No alarm will be generated if the contact is disabled(1). An alarm will be generated if the contact is enabled(2) and the contact has been faulted." ::= { emConfigContactsEntry 3 } emStatusCommStatus OBJECT-TYPE SYNTAX INTEGER { noComm(1), comm(2), commLost(3) } ACCESS read-only STATUS mandatory DESCRIPTION "The communication status between the agent and the Environmental Monitor. noComm(1), Communication has never been established. comm(2), Communication has been established. commLost(3), Communication was established, but was lost." ::= { emStatus 1 } emStatusProbesNumProbes OBJECT-TYPE SYNTAX INTEGER ACCESS read-only STATUS mandatory DESCRIPTION "The number of available probes on the Environmental Monitor." ::= { emStatus 2 } emStatusProbesTable OBJECT-TYPE SYNTAX SEQUENCE OF EmStatusProbesEntry ACCESS not-accessible STATUS mandatory DESCRIPTION "A list of probes supported by the Environmental Monitor and their status." ::= { emStatus 3 } emStatusProbesEntry OBJECT-TYPE SYNTAX EmStatusProbesEntry ACCESS not-accessible STATUS mandatory DESCRIPTION "The status of the probe." INDEX { emStatusProbeNumber } ::= { emStatusProbesTable 1 } EmStatusProbesEntry ::= SEQUENCE { emStatusProbeNumber INTEGER, emStatusProbeName DisplayString, emStatusProbeStatus INTEGER, emStatusProbeCurrentTemp INTEGER, emStatusProbeTempUnits INTEGER, emStatusProbeCurrentHumid INTEGER, emStatusProbeHighTempViolation INTEGER, emStatusProbeLowTempViolation INTEGER, emStatusProbeHighHumidViolation INTEGER, emStatusProbeLowHumidViolation INTEGER } emStatusProbeNumber OBJECT-TYPE SYNTAX INTEGER ACCESS read-only STATUS mandatory DESCRIPTION "The index of the probe." ::= { emStatusProbesEntry 1 } emStatusProbeName OBJECT-TYPE SYNTAX DisplayString ACCESS read-only STATUS mandatory DESCRIPTION "A descriptive name for the probe set by the user, possibly denoting its location or purpose." ::= { emStatusProbesEntry 2 } emStatusProbeStatus OBJECT-TYPE SYNTAX INTEGER { disconnected(1), connected(2) } ACCESS read-only STATUS mandatory DESCRIPTION "The connected status of the probe, either disconnected(1) or connected(2)." ::= { emStatusProbesEntry 3 } emStatusProbeCurrentTemp OBJECT-TYPE SYNTAX INTEGER ACCESS read-only STATUS mandatory DESCRIPTION "The current temperature reading from the probe displayed in the units shown in the 'emStatusProbeTempUnits' OID (Celsius or Fahrenheit)." ::= { emStatusProbesEntry 4 } emStatusProbeTempUnits OBJECT-TYPE SYNTAX INTEGER { celsius(1), fahrenheit(2) } ACCESS read-only STATUS mandatory DESCRIPTION "The temperature scale used to display the temperature thresholds of the probe, Celsius(1) or Fahrenheit(2). This setting is based on the system preferences configuration in the agent." ::= { emStatusProbesEntry 5 } emStatusProbeCurrentHumid OBJECT-TYPE SYNTAX INTEGER ACCESS read-only STATUS mandatory DESCRIPTION "The current humidity reading from the probe in percent relative humidity." ::= { emStatusProbesEntry 6 } emStatusProbeHighTempViolation OBJECT-TYPE SYNTAX INTEGER { noViolation(1), highTempViolation(2), disabled(3) } ACCESS read-only STATUS mandatory DESCRIPTION "The high temperature violation status of the probe temperature reading. This OID will show a highTempViolation(2) if the current temperature reading shown in the 'emStatusProbeCurrentTemp' OID is greater than or equal to the high temperature threshold value, the 'emConfigProbeHighTempThreshold' OID, and the value of the 'emConfigProbeHighTempEnable' OID is enabled. Otherwise it will show noViolation(1). If the 'emConfigProbeHighTempEnable' OID is disabled, this OID will show disabled(3)." ::= { emStatusProbesEntry 7 } emStatusProbeLowTempViolation OBJECT-TYPE SYNTAX INTEGER { noViolation(1), lowTempViolation(2), disabled(3) } ACCESS read-only STATUS mandatory DESCRIPTION "The high temperature violation status of the probe temperature reading. This OID will show a lowTempViolation(2) if the current temperature reading shown in the 'emStatusProbeCurrentTemp' OID is less than or equal to the low temperature threshold value, the 'emConfigProbeLowTempThreshold' OID, and the value of the 'emConfigProbeLowTempEnable' OID is enabled. Otherwise it will show noViolation(1). If the 'emConfigProbeLowTempEnable' OID is disabled, this OID will show disabled(3)." ::= { emStatusProbesEntry 8 } emStatusProbeHighHumidViolation OBJECT-TYPE SYNTAX INTEGER { noViolation(1), highHumidViolation(2), disabled(3) } ACCESS read-only STATUS mandatory DESCRIPTION "The high humidity violation status of the probe humidity reading. This OID will show a highTempViolation(2) if the current humidity reading shown in the 'emStatusProbeCurrentHumid' OID is greater than or equal to the high humidity threshold value, the 'emConfigProbeHighHumidThreshold' OID, and the value of the 'emConfigProbeHighHumidEnable' OID is enabled. Otherwise it will show noViolation(1). If the 'emConfigProbeHighHumidEnable' OID is disabled, this OID will show disabled(3)" ::= { emStatusProbesEntry 9 } emStatusProbeLowHumidViolation OBJECT-TYPE SYNTAX INTEGER { noViolation(1), lowHumidViolation(2), disabled(3) } ACCESS read-only STATUS mandatory DESCRIPTION "The low humidity violation status of the probe humidity reading. This OID will show a lowTempViolation(2) if the current humidity reading shown in the 'emStatusProbeCurrentHumid' OID is less than or equal to the low humidity threshold value, the 'emConfigProbeLowHumidThreshold' OID, and the value of the 'emConfigProbeLowHumidEnable' OID is enabled. Otherwise it will show noViolation(1). If the 'emConfigProbeLowHumidEnable' OID is disabled, this OID will show disabled(3)." ::= { emStatusProbesEntry 10 } emStatusContactsNumContacts OBJECT-TYPE SYNTAX INTEGER ACCESS read-only STATUS mandatory DESCRIPTION "The number of contacts supported by the Environmental Monitor." ::= { emStatus 4 } emStatusContactsTable OBJECT-TYPE SYNTAX SEQUENCE OF EmStatusContactsEntry ACCESS not-accessible STATUS mandatory DESCRIPTION "A list of contacts supported by the Environmental Monitor and their status." ::= { emStatus 5 } emStatusContactsEntry OBJECT-TYPE SYNTAX EmStatusContactsEntry ACCESS not-accessible STATUS mandatory DESCRIPTION "The status of the contact." INDEX { emStatusContactNumber } ::= { emStatusContactsTable 1 } EmStatusContactsEntry ::= SEQUENCE { emStatusContactNumber INTEGER, emStatusContactName DisplayString, emStatusContactStatus INTEGER } emStatusContactNumber OBJECT-TYPE SYNTAX INTEGER ACCESS read-only STATUS mandatory DESCRIPTION "The index of the Environmental Monitor contact." ::= { emStatusContactsEntry 1 } emStatusContactName OBJECT-TYPE SYNTAX DisplayString ACCESS read-only STATUS mandatory DESCRIPTION "A descriptive name for the Environmental Monitor contact set by the user, possibly denoting its location or purpose." ::= { emStatusContactsEntry 2 } emStatusContactStatus OBJECT-TYPE SYNTAX INTEGER { noFault(1), fault(2), disabled(3) } ACCESS read-only STATUS mandatory DESCRIPTION "The status of the Environmental Monitor contact. The status will show noFault(1) if the contact is in the normal state and the 'emConfigContactEnable' OID is enabled. The status will show a fault(2) if the contact is faulted and the 'emContactEnable' OID is enabled. If the 'emConfigContactEnable' OID is disabled, the status will show disabled(3)." ::= { emStatusContactsEntry 3 } -- Integrated Environmental Monitor (IEM) iemIdentHardwareRevision OBJECT-TYPE SYNTAX DisplayString ACCESS read-only STATUS mandatory DESCRIPTION "The hardware revision of the Integrated Environmental Monitor." ::= { iemIdent 1 } iemConfigProbesNumProbes OBJECT-TYPE SYNTAX INTEGER ACCESS read-only STATUS mandatory DESCRIPTION "The number of temperature and humidity probes available." ::= { iemConfig 1 } iemConfigProbesTable OBJECT-TYPE SYNTAX SEQUENCE OF IemConfigProbesEntry ACCESS not-accessible STATUS mandatory DESCRIPTION "A list of probes supported by the Environmental Monitor and their configurations." ::= { iemConfig 2 } iemConfigProbesEntry OBJECT-TYPE SYNTAX IemConfigProbesEntry ACCESS not-accessible STATUS mandatory DESCRIPTION "The Environmental Monitor probe configurations." INDEX { iemConfigProbeNumber } ::= { iemConfigProbesTable 1 } IemConfigProbesEntry ::= SEQUENCE { iemConfigProbeNumber INTEGER, iemConfigProbeName DisplayString, iemConfigProbeHighTempThreshold INTEGER, iemConfigProbeLowTempThreshold INTEGER, iemConfigProbeTempUnits INTEGER, iemConfigProbeHighHumidThreshold INTEGER, iemConfigProbeLowHumidThreshold INTEGER, iemConfigProbeHighTempEnable INTEGER, iemConfigProbeLowTempEnable INTEGER, iemConfigProbeHighHumidEnable INTEGER, iemConfigProbeLowHumidEnable INTEGER } iemConfigProbeNumber OBJECT-TYPE SYNTAX INTEGER ACCESS read-only STATUS mandatory DESCRIPTION "The index to a Environmental Monitor probe entry." ::= { iemConfigProbesEntry 1 } iemConfigProbeName OBJECT-TY